Plan Review Details - Permit 15100182
Plan Review Stops For Permit 15100182
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-28 Cont ID  
Sent By ccole Date 2015-10-28 Time 16:52 Rev Time 0.00
Received By ccole Date 2015-10-26 Time 10:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-08 Cont ID  
Sent By cpuell Date 2015-10-08 Time 12:59 Rev Time 0.00
Received By cpuell Date 2015-10-07 Time 14:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-10-28 Cont ID  
Sent By ccole Date 2015-10-28 Time 16:52 Rev Time 0.00
Received By ccole Date 2015-10-28 Time 16:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-10-08 Cont ID  
Sent By ccole Date 2015-10-08 Time 12:28 Rev Time 0.00
Received By ccole Date 2015-10-08 Time 12:17 Sent To  
Notes
2015-10-08 12:35:021ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15100182
 MASTER #15040093
 10/8/15
  
 1) SHOW THE REQUIRED CLEARANCE DISTANCE MEASUREMENTS
 FOR THE AIR HANDLER IN THE CLOSET IN COMPLIANCE WITH
 SECTION M1305.1.1 FBC-10 RESIDIENTIAL- MINIMUM 4" ALONG
 THE SIDES, BACK. AND TOP WITH A TOTAL WIDTH OF THE
 ENCLOSING SPACE BEING AT LEAST 12 INCHES WIDER THAN THE
 AIR HANDLER.
 2) PROVIDE DETAILS AND SHOW THE EXHAUST DUCT RUNS FOR
 THE DRYER AND BATH FANS: INDICATE THE TYPE AND SIZE OF
 EXHAUST DUCTS, DUCT RUNS AND LENGTHS, AND EXHAUST
 TERMINATION LOCATIONS- REFER TO SECTION M1502 FOR DRYER
 EXHAUST REQUIREMENTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-10-28 Cont ID  
Sent By cpuell Date 2015-10-28 Time 17:09 Rev Time 0.00
Received By cpuell Date 2015-10-28 Time 17:09 Sent To  
Notes
2015-10-28 17:09:31PLANS DIGITALLY SIGNED


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved