Plan Review Details - Permit 15100123
Plan Review Stops For Permit 15100123
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-10-21 Cont ID  
Sent By   Date 2015-10-21 Time   Rev Time 0.00
Received By jwitmer Date 2015-10-16 Time 15:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-10-30 Cont ID  
Sent By albarran Date 2015-10-30 Time 12:14 Rev Time 0.00
Received By albarran Date   Time   Sent To I
Notes
2015-10-30 12:16:39THIS ADDITIONAL ELECTRICAL REVIEW WAS CREATED TO
 COMPLETE THE PREVIOUS ELECTRICAL REVIEW BECAUSE THE
 SYSTEM LOCKED ME OUT.
 ALL PREVIOUSLY ADDRESSED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By albarran Date 2015-10-30 Time 9:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-10-26 Cont ID  
Sent By albarran Date 2015-10-26 Time 19:15 Rev Time 0.00
Received By albarran Date 2015-10-26 Time 17:05 Sent To  
Notes
2015-10-26 19:22:29THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE ???2011
 EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH
 EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS
 APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED.
 1. GENERAL NOTES #12: DO YOU REALLY WANT TO RUN A #2CU
 GROUND CONDUCTOR TO THE 15 -20 AMP 125 VAC OUTLET?
 CORRECT YOUR NOTE ACCORDINGLY.
 2. IN YOUR NOTES YOU SEEK TO OBTAIN A 5 OHM READING ON
 THE GROUNDING. I BELIEVE THAT SUCH A READING IS
 UNOBTAINABLE, ARE YOU SURE YOU DON?T MEAN 25 OHM?
 3. IN ADDITION TO GROUND THE GENERATOR, A FOUNDATION
 GROUND TO THE GENERATOR PAD STEEL SHALL BE RUN AS WELL.
 PER NEC 250.66.
 4. PROVIDE A FEEDER DIAGRAM AS DIRECTED IN NEC 215.5.
 THIS DIAGRAM SHALL INCLUDE LOAD CALCS AND CONDUCTOR
 SIZING.
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE,
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-10-22 Cont ID  
Sent By wjolin Date 2015-10-22 Time 16:40 Rev Time 0.00
Received By wjolin Date 2015-10-22 Time 16:30 Sent To  
Notes
2015-10-22 16:40:115801 ERNEST STREET - DIESEL GENERATOR AND FUEL TANK
 ONLY
 PERMIT #15100123
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS SUITABLE FOR
 COMBUSTIBLE LIQUIDS (DIESEL FUEL).
  
 PROVIDE PERMANENT, WEATHERPROOF "NO SMOKING OR OPEN
 FLAME" SIGNAGE.
  
 1000 GALLON FUEL TANK SHALL BE PROTECTED FROM
 MECHANICAL OR VEHICULAR DAMAGE WITH APPROPRIATELY SIZE
 AND SPACED BOLLARDS.
  
 PROVIDE PERMANENT WEATHERPROOF DIAMOND PLACARDS PER
 NFPA 704 INDICATING THE HEALTH, FLAMMABILITY AND
 REACTIVITY RATING OF THE HAZARDOUS MATERIALS. PLACARDS
 SHALL BE LOCATED ON
 (1) STATIONARY ABOVEGROUND TANKS
 (2) STATIONARY ABOVEGROUND CONTAINERS
 (3) AT ENTRANCES TO LOCATIONS WHERE HAZARDOUS MATERIALS
 ARE STORED, DISPENSED, USED, OR HANDLED IN QUANTITIES
 REQUIRING A PERMIT
 (4) AT OTHER ENTRANCES AND LOCATIONS DESIGNATED BY THE
 FIRE DEPARTMENT
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2015-10-24 Cont ID  
Sent By tklarge Date 2015-10-24 Time 04:33 Rev Time 0.00
Received By tklarge Date 2015-10-24 Time 03:43 Sent To  
Notes
2015-10-24 04:34:42THE GENERATOR IS POWERED BY DIESEL FUEL AND NOT LP OR
 NATURAL GAS. PLUMBING REVIEW NOT REQUIRED. TKL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-30 Cont ID  
Sent By lmarchan Date 2015-10-30 Time 12:41 Rev Time 0.00
Received By lmarchan Date 2015-10-29 Time 16:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-27 Cont ID  
Sent By lmarchan Date 2015-10-27 Time 07:53 Rev Time 0.00
Received By lmarchan Date 2015-10-09 Time 09:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-10-30 Cont ID  
Sent By lmarchan Date 2015-10-30 Time 12:42 Rev Time 0.00
Received By lmarchan Date 2015-10-30 Time 12:42 Sent To  
Notes
2015-10-30 12:42:58ADOBE DIGITALLY SIGNED PLANS

Review Stop Z ZONING
Rev No 1 Status P Date 2015-10-26 Cont ID  
Sent By jroach Date 2015-10-26 Time 16:19 Rev Time 0.00
Received By jroach Date 2015-10-26 Time 16:19 Sent To  
Notes
***NONE***