| Plan Review Stops For Permit 15100123 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2015-10-21 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2015-10-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-10-16 |
Time |
15:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2015-10-30 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-10-30 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
|
Time |
|
Sent To |
I |
|
| Notes |
| 2015-10-30 12:16:39 | THIS ADDITIONAL ELECTRICAL REVIEW WAS CREATED TO | | | COMPLETE THE PREVIOUS ELECTRICAL REVIEW BECAUSE THE | | | SYSTEM LOCKED ME OUT. | | | ALL PREVIOUSLY ADDRESSED DEFICIENCIES HAVE BEEN | | | SATISFACTORILY ADDRESSED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-10-30 |
Time |
9:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-10-26 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-10-26 |
Time |
19:15 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-10-26 |
Time |
17:05 |
Sent To |
|
|
| Notes |
| 2015-10-26 19:22:29 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION | | | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE ???2011 | | | EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH | | | EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS | | | APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED. | | | 1. GENERAL NOTES #12: DO YOU REALLY WANT TO RUN A #2CU | | | GROUND CONDUCTOR TO THE 15 -20 AMP 125 VAC OUTLET? | | | CORRECT YOUR NOTE ACCORDINGLY. | | | 2. IN YOUR NOTES YOU SEEK TO OBTAIN A 5 OHM READING ON | | | THE GROUNDING. I BELIEVE THAT SUCH A READING IS | | | UNOBTAINABLE, ARE YOU SURE YOU DON?T MEAN 25 OHM? | | | 3. IN ADDITION TO GROUND THE GENERATOR, A FOUNDATION | | | GROUND TO THE GENERATOR PAD STEEL SHALL BE RUN AS WELL. | | | PER NEC 250.66. | | | 4. PROVIDE A FEEDER DIAGRAM AS DIRECTED IN NEC 215.5. | | | THIS DIAGRAM SHALL INCLUDE LOAD CALCS AND CONDUCTOR | | | SIZING. | | | THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN | | | MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED | | | FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED | | | TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG | | | WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE, | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY | | | APPRECIATED. | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2015-10-22 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2015-10-22 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2015-10-22 |
Time |
16:30 |
Sent To |
|
|
| Notes |
| 2015-10-22 16:40:11 | 5801 ERNEST STREET - DIESEL GENERATOR AND FUEL TANK | | | ONLY | | | PERMIT #15100123 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS SUITABLE FOR | | | COMBUSTIBLE LIQUIDS (DIESEL FUEL). | | | | | | PROVIDE PERMANENT, WEATHERPROOF "NO SMOKING OR OPEN | | | FLAME" SIGNAGE. | | | | | | 1000 GALLON FUEL TANK SHALL BE PROTECTED FROM | | | MECHANICAL OR VEHICULAR DAMAGE WITH APPROPRIATELY SIZE | | | AND SPACED BOLLARDS. | | | | | | PROVIDE PERMANENT WEATHERPROOF DIAMOND PLACARDS PER | | | NFPA 704 INDICATING THE HEALTH, FLAMMABILITY AND | | | REACTIVITY RATING OF THE HAZARDOUS MATERIALS. PLACARDS | | | SHALL BE LOCATED ON | | | (1) STATIONARY ABOVEGROUND TANKS | | | (2) STATIONARY ABOVEGROUND CONTAINERS | | | (3) AT ENTRANCES TO LOCATIONS WHERE HAZARDOUS MATERIALS | | | ARE STORED, DISPENSED, USED, OR HANDLED IN QUANTITIES | | | REQUIRING A PERMIT | | | (4) AT OTHER ENTRANCES AND LOCATIONS DESIGNATED BY THE | | | FIRE DEPARTMENT | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2015-10-24 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-10-24 |
Time |
04:33 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-10-24 |
Time |
03:43 |
Sent To |
|
|
| Notes |
| 2015-10-24 04:34:42 | THE GENERATOR IS POWERED BY DIESEL FUEL AND NOT LP OR | | | NATURAL GAS. PLUMBING REVIEW NOT REQUIRED. TKL. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-10-30 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2015-10-30 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2015-10-29 |
Time |
16:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-10-27 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2015-10-27 |
Time |
07:53 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2015-10-09 |
Time |
09:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2015-10-30 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2015-10-30 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2015-10-30 |
Time |
12:42 |
Sent To |
|
|
| Notes |
| 2015-10-30 12:42:58 | ADOBE DIGITALLY SIGNED PLANS |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2015-10-26 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2015-10-26 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2015-10-26 |
Time |
16:19 |
Sent To |
|
|
| Notes |
|
|