Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-02-03 Cont ID  
Sent By jwitmer Date 2016-02-03 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2016-02-03 Time 07:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-06 Cont ID  
Sent By jwitmer Date 2015-11-06 Time 14:12 Rev Time  
Received By jwitmer Date 2015-11-06 Time 10:46 Sent To ENG
Notes
2015-11-06 14:12:15BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100091
 ADD: 1805 BELVEDERE RD.
 CONT: TBD
 TEL: (?????????????????????
 E-MAIL:?????????????????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. NOV. 06/2015
 ACTION: DENIED
  
 1) SHEET D-1 NOTES 4 AND 11, NOTE 11 INDICATE THE
 DEMOLITION OF CANOPY, THE NOTE INDICATES SEE ASBESTOS
 REPORT. NO SUCH REPORT HAS BEEN SUBMITTED TO THE
 BUILDING DEPARTMENT FOR THE RECORD RETENSION PROTION OF
 THE BUILDING DEPARTMENT.
  
 2) NOTE 4 INDICATES THE DIMOLITION OF THE PORT-COCHERE
 CANOPY. THERE IS NO MENTION OF THIS WORK ON THE PERMIT
 APPLICATION. PLEASE PROVIDE A NARRATIVE AS TO WHAT WORK
 WILL BE INCLUDED UNDER THIS PERMIT. THE VALUE OF
 $10,000.00 IS LOW FOR THE AMOUNT OF WORK WHICH IS
 INCLUSIVE WITHIN THE PLANS. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-16 Cont ID  
Sent By rlecky Date 2016-02-16 Time 14:20 Rev Time 0.00
Received By rlecky Date 2016-02-16 Time 14:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-05 Cont ID  
Sent By ppetty Date 2015-11-05 Time 14:25 Rev Time 0.00
Received By ppetty Date 2015-11-06 Time 14:06 Sent To  
Notes
2015-11-06 14:10:50PLEASE SHOW LOCATION OF SERVICE+LATERAL
 AND REUSED PIPE AND WIRE IF ANY
 11/6/2015 PP 561-644-7305

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2016-02-29 Cont ID  
Sent By Mgonzale Date 2016-02-29 Time   Rev Time 1.00
Received By mgonzale Date 2016-02-29 Time   Sent To I
Notes
2016-02-29 09:36:58NO CONFLICT WITH CITY OF WPB UTILITIES.
  
 EOR WILL CERTIFY TO CITY OF WPB.
  
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-11-16 Cont ID  
Sent By Mgonzale Date 2015-11-16 Time   Rev Time 1.00
Received By mgonzale Date 2015-11-16 Time   Sent To I
Notes
2015-11-16 14:24:32PLEASE ADDRESS OTHER DICIPLINE'S PLAN REVIEW COMMENTS:
  
 NOTE ON PLANS THAT SITE DEMO AND RESTORATION WILL NOT
 CAUSE ADVERSE DRAINAGE AFFECTS TO SURROUNFING
 PROPERTIES.
  
 NOTE ON PLANS PERVIOUS AND IMPERVIOUS TOTALS. (THIS
 COULD CHANGE THE STORM WATER FEES ON YOUR ACCOUNT)
  
 NOTE ON PLANS THAT THERE WILL NOT BE STRUCTURAL
 ELEVATION CHANGE ON-SITE NOR THAT DRAINAGE SYSTEM WILL
 BE ALTERED.
  
 NOTE ON PLANS THAT SWPPP (STORM WATER POLLUTION
 PREVENTION BMP'S BEST MANAGEMENT PRACTICES WILL BE USED
 WHEN IMPACT REQUIRES STORMWATER RUN OFF PROTECTION.
 REFER TO POLLUTION CONTROL DETAILS AS PER CITY OF WPB
 STANDARDS. HTTP://WPB.ORG/ENGINEERING/ENGINEERING-SERVI
 CES/ENGINEERING-STANDARDS/
  
 REF: CITY ORDINANCE 3132-98, SECTION 32-18(A): "...IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO DIRECTLY OR
 INDIRECTLY DEPOSIT, DISCHARGE, SPILL, OR DUMP INTO ANY
 OF THE PUBLIC WATERS OR MUNICIPAL SEPARATE STORM SEWER
 SYSTEM WITHIN THE CITY, ANY SUBSTANCE OTHER THAN THAT
 COMPOSED ENTIRELY OF STORM WATER." AND, SECTION
 32-18(C): "NO PERSON MAY MAINTAIN, USE OR ESTABLISH ANY
 DIRECT OR INDIRECT CONNECTION TO THE STORM WATER SYSTEM
 THAT RESULTS IN ANY DISCHARGE IN VIOLATION OF THIS
 ORDINANCE. THIS PROHIBITION IS RETROACTIVE AND APPLIES
 TO CONNECTIONS MADE IN THE PAST, REGARDLESS OF WHETHER
 MADE UNDER A PERMIT, OR OTHER AUTHORIZATION, OR WHETHER
 PERMISSIBLE UNDER LAWS OR PRACTICES APPLICABLE OR
 PREVAILING AT THE TIME THE CONNECTION WAS MADE."
  
 REF: WEST PALM BEACH, FLORIDA, CODE OF ORDINANCES >>
 PART II - CODE OF ORDINANCES >> CHAPTER 94 -ZONING AND
 LAND DEVELOPMENT REGULATIONS >> ARTICLE XVII. - FLOOD
 PREVENTION AND CONTROL.
  
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-01 Cont ID  
Sent By cpuell Date 2016-03-01 Time 08:27 Rev Time 0.00
Received By cpuell Date 2016-01-25 Time 11:10 Sent To  
Notes
2016-01-26 11:10:19B21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-17 Cont ID  
Sent By lmarchan Date 2015-11-17 Time 13:11 Rev Time 0.00
Received By lmarchan Date 2015-10-05 Time 07:59 Sent To  
Notes
2015-10-06 08:01:53B31

Review Stop P PLUMBING
Rev No 2 Status N Date 2016-01-30 Cont ID  
Sent By tklarge Date 2016-01-30 Time 07:14 Rev Time 0.00
Received By tklarge Date 2016-01-30 Time 07:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-11-06 Cont ID  
Sent By gjohnson Date 2015-10-14 Time 09:04 Rev Time 0.00
Received By gjohnson Date 2015-11-06 Time 14:12 Sent To  
Notes
2015-11-06 14:25:511ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE CIVIL DRAWING SHOWING SEWRER MAIN AND
 WATER METER LOCATION
 PER WPB AEND. TO FBC SEC 107.2.1
 2. PLEASE PROVIDE MORE DETAIL IS ALL PLUMBING ON
 PROPERTY GOING TO BE ABANDON OR WILL SOME STAY IN
 SERVICE .
 3. SHOW WATER SOURCE FOR DEMO WITH BACKFLOW DEVICE.
 PER WPB AMEND. TO FBC SEC 107.1.2

Review Stop Z ZONING
Rev No 2 Status P Date 2016-02-29 Cont ID  
Sent By sgraham Date 2016-01-28 Time 16:14 Rev Time 0.00
Received By ajones Date 2016-01-28 Time 16:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-11-03 Cont ID  
Sent By sgraham Date 2015-11-03 Time 16:16 Rev Time 0.00
Received By sgraham Date 2015-11-03 Time 16:16 Sent To  
Notes
2015-11-03 16:18:2311/3/15 ZONING FAILED
  
 1. LANDSCAPE ISLAND CAN NOT BE REMOVED ON THE END OF
 THE PARKING LOTS, ONLY WHEN LOCATED IN THE MIDDLE OF
 THE LOT.