| 2015-11-09 14:37:27 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. G101, INCORPORATE THE INFORMATION IN THE RESPONSE |
| | LETTER REGARING THE PERCENTAGE OF OPENINGS FOR EACH |
| | WALL INTO THE PLAN IN ORDER TO SHOW COMPLIANCE WITH FBC |
| | TABLE 705.8. |
| | |
| | CHANGES TO THE PROPERTY LINE (REPLAT) REQUIRE THAT |
| | COMPLIANCE WITH FBC TABLE 705.8 (MAXIMUM AREA OF |
| | EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION |
| | DISTANCE) AND FBC TABLE 602 (FIRE RESISTANCE RATING |
| | REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE |
| | SEPARATION DISTANCE) BE SHOWN. |
| | |
| | ONLY EAST FACING NEW WALLS WERE ADDRESSED IN THE |
| | RESPONSE LETTER AND SHOW THE DISTANCE TO THE NEW |
| | PROPERTY LINE ON SHEET G101. AS THE PROPERTY LINE IS |
| | BEING RELOCATED, COMPLIANCE NEEDS TO BE SHOWN FOR THE |
| | EXISTING WALLS AND THE NEW WALLS WHICH FACE SOUTH. |
| | |
| | BASED ON INFORMATION PROVIDED: BEARING WALLS ARE |
| | REQUIRED TO BE 3 HOURS. STRUCTURAL FRAME IS REQUIRED TO |
| | BE 2 HOURS. PLAN SHOWS THESE WALLS AS 1 HR; PLEASE SEE |
| | FBC TABLE 602, FOOTNOTE A AND REVISE. |
| | |
| | 2. THE ART IN PUBLIC PLACES WAS SENT VIA EMAIL, CITY OF |
| | WEST PALM BEACH CODE OF ORDINANCES 78-123, 78-126. |
| | |
| | THIS REVISION WILL BE ISSUED WITH THE PROVISO THAT, BY |
| | DEC 23, 2015, THE APPROVAL WILL BE PROVIDED. PLEASE |
| | SEND A COPY OF THE APPROVAL WHEN AVAILABLE VIA EMAIL TO |
| | [email protected] IN ORDER TO DOCUMENT THE PERMIT FILE. |
| | |
| | 3. OK |
| | |
| | 4. ADVISORY ONLY, PRODUCT APPROVALS REVIEWED BY |
| | DESIGNER OF RECORD ARE TO BE SUBMITTED FOR REVIEW PRIOR |
| | TO INSTALLATION IF NOT SUBMITTED AT THIS TIME, FBC 107, |
| | FBC 1609 (SUBMITTAL, NO FEE). |
| | |
| | 5. ADVISORY ONLY; PARKING LOT STRIPING, AWNINGS, SIGNS |
| | AND OTHER INDEPENDENT STRUCTURE ELEMENTS REQUIRE |
| | SEPARATE PERMITS WHICH WOULD INCLUDE FEES, BUILDING |
| | PERMIT APPLICATIONS, PLANS AND REVIEWS. |
| | |
| | 6. ADVISORY ONLY; SPEC SHEETS IN APPENDIX WERE NOT |
| | REVIEWED. |
| | |
| | 7. PRIOR TO INSTALLATION, SUBMITTALS FOR THE UL |
| | ASSEMBLIES WILL BE REQUIRED. THE SUBMITTAL SHOULD |
| | INCLUDE THE UL ASSEMBLY WITH SPECIFIC OPTIONS ELECTED |
| | TO BE INDICATED. THE SUBMITTAL IS REQUIRED TO BE |
| | REVIEWED BY DOR. THE SUBMITTAL IS REQUIRED TO BE |
| | APPROVED THROUGH PLAN REVIEW PRIOR TO COMMENCEMENT. |
| | |
| | 8 TO 13. OK |
| | |
| | 14. RE-PLAT TO BE FILED WITHIN 45 DAYS OF PERMIT |
| | ISSUANCE (AGREEMENT BETWEEN OWNER AND DEVELOPMENT |
| | SERVICES). |
| | |
| | PLEASE PROVIDE THE PLAT BOOK AND PAGE NUMBER WHEN |
| | FILED. |
| | |
| | 15. OK |
| | |
| | **NEW COMMENT** |
| | |
| | 16. SIGNATURE PAGE FOR THE DIGITAL PLANS REQUIRED, OR |
| | PROVIDE HARDCOPY SIGNED AND SEALED PLANS FOR 14120908 |
| | (PLANS SUBMITTED HAD SOME INCONSISTENCIES WITH THE |
| | DIGITAL PLANS ISSUED). |
| | |
| | |
| | |