Plan Review Details - Permit 15100052
Plan Review Stops For Permit 15100052
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-05 Cont ID  
Sent By shill Date 2015-10-05 Time 17:06 Rev Time 0.00
Received By shill Date 2015-10-05 Time 17:06 Sent To  
Notes
2015-10-05 17:10:13****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 5TH EDITION 2014
  
 PROFLEX MSC 90 TESTS PROVIDED
  
 SLAB THICKNESS NOT PROVIDED
  
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 THE TEST REPORT PROVIDED INCLUDES A DROPPED GYPSUM
 CEILING (NOT ACCEPTABLE) AND AN 8" SLAB.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 THE TEST REPORT PROVIDED INCLUDES A DROPPED GYPSUM
 CEILING (NOT ACCEPTABLE) AND AN 8" SLAB; NO SLAB
 THICKNESS INFORMATION WAS PROVIDED.
  
 3. MY UNDERSTANDING FROM THIS MANUFACTURER IS THAT THE
 ONLY PROFLEX PRODUCT WHICH HAS THE THREE COMPLIANT
 TESTS IS RCU250, IF THE BUILDING HAS AN 8" SLAB (CANNOT
 BE THINNER).
  
 3. TO AVOID MULTIPLE PLAN REVIEWS, A PRELIMINARY REVIEW
 WILL BE DONE VIA EMAIL UNDER THE FOLLOWING CONDITIONS:
  
 QUALIFIER IS TO STATE THE SLAB THICKNESS AND PROVIDE
 EVIDENCE AS TO HOW THIS INFORMATION WAS DETERMINED IF
 THE SLAB THICKNESS STATED IS OVER 6 INCHES.
  
 QUALIFIER IS TO PROVIDE INFORMATION REGARDING THE
 PROPOSED FLOORING; MATERIAL, THICKNESS, AND METHOD OF
 INSTALLATION (FLOATING, MORTAR BED, GLUE, THINSET,
 ETC.).
  
 QUALIFIER IS TO REVIEW THE COMMENT LIST AND TEST
 REPORTS.
  
 FOR THE TWO ACOUSTICAL TEST REPORTS, QUALIFIER TO
 HIGHLIGHT THE ASSEMBLY (SPECIFICALLY WHERE NO DROPPED
 CEILING WAS USED IN THE TEST) AS WELL AS THE TEST
 RESULT. THIS IS TYPICALLY FOUND ON THE SECOND PAGE OF
 THE TEST REPORT.
  
 FOR THE FLAME SPREAD TEST REPORT, QUALIFIER IS TO
 HIGHLIGHT THE TEST STANDARD (SHOULD BE EITHER ASTM E 84
 OR UL 723) AND TEST RESULT.
  
 FOR THE FLAME SPREAD TEST REPORT, QUALIFIER IS TO
 HIGHLIGHT THE ASSEMBLY TESTED. IF THE FLAME SPREAD WAS
 DONE WITH TILE, TILE SIDE EXPOSED TO THE FLAME, THIS IS
 ACCEPTABLE FOR TILE APPLICATIONS BUT NOT ACCEPTABLE FOR
 OTHER APPLICATIONS SUCH AS WOOD OR LAMINATE.
  
 DUE TO CURRENT WORK LOAD AND LACK OF TIME TO MAINTAIN
 TARGET TURNAROUND TIMES, IF APPLICANT IS UNABLE TO
 COMPLY WITH ITEM 4, THE COURTESY REVIEW VIA EMAIL WILL
 NOT BE DONE. PLEASE RESUBMIT AT THE BUILDING DIVISION
 COUNTER.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-05 Cont ID  
Sent By shill Date 2015-10-05 Time 17:12 Rev Time 0.00
Received By shill Date 2015-10-05 Time 17:12 Sent To  
Notes
2015-10-02 12:54:44BLDG <5K (PER SK)