Plan Review Details - Permit 15100050
Plan Review Stops For Permit 15100050
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-10-21 Cont ID  
Sent By ccole Date 2015-10-21 Time 11:36 Rev Time 0.00
Received By ccole Date 2015-10-21 Time 11:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-16 Cont ID  
Sent By ccole Date 2015-10-16 Time 11:21 Rev Time 0.00
Received By ccole Date 2015-10-16 Time 11:21 Sent To  
Notes
2015-10-16 11:28:481ST REVIEW: FBC 2014 BUILDING
 PERMIT #15100050
 10/16/15
  
 1) PLEASE REFER TO LIMITATION #7 ON PAGE 16 OF THE
 SUBMITTED NOA#14-0224.03 CERTINTEED MODIFIED BITUMEN:
 PERIMETER AND CORNER AREAS SHALL COMPLY WITH THE
 ENHANCED UPLIFT PRESSURE REQUIREMENTS OF THESES AREA.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION AND BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH RAS 117. CALCULATIONS PREPARED, SIGNED AND SEALED
 BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER,
 REGISTERED ARCHITECT, OR REGISTERED ROOF CONSULTANT.
  
 CHRISTOPHER L. COLE
 BUIDINGL PLANS EXAMINER
 561-805-6719
 [email protected]
  