Plan Review Details - Permit 15100027
Plan Review Stops For Permit 15100027
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-01-04 Cont ID  
Sent By jwitmer Date 2015-12-16 Time 08:57 Rev Time 0.00
Received By jwitmer Date 2015-12-16 Time 07:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-10-13 Cont ID  
Sent By jwitmer Date 2015-10-13 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2015-10-13 Time 06:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-01-04 Cont ID  
Sent By ppetty Date 2016-01-04 Time 09:18 Rev Time 0.00
Received By ppetty Date 2016-01-04 Time 09:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-11-05 Cont ID  
Sent By ppetty Date 2015-11-05 Time 14:04 Rev Time 0.00
Received By ppetty Date 2015-11-05 Time 14:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-12-30 Cont ID  
Sent By scaldero Date 2015-12-30 Time 13:33 Rev Time 0.00
Received By scaldero Date 2015-12-30 Time 13:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-10-19 Cont ID  
Sent By scaldero Date 2015-10-19 Time 14:09 Rev Time 0.00
Received By scaldero Date 2015-10-19 Time 13:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-04 Cont ID  
Sent By ppetty Date 2016-01-04 Time 09:18 Rev Time 0.00
Received By ppetty Date 2015-12-10 Time 09:20 Sent To  
Notes
2015-12-11 09:20:18B35

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-05 Cont ID  
Sent By cpuell Date 2015-11-05 Time 14:20 Rev Time 0.00
Received By cpuell Date 2015-10-01 Time 13:39 Sent To  
Notes
2015-10-02 13:45:40B35

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-12-17 Cont ID  
Sent By ccole Date 2015-12-17 Time 07:21 Rev Time 0.00
Received By ccole Date 2015-12-17 Time 06:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-10-08 Cont ID  
Sent By ccole Date 2015-10-08 Time 16:30 Rev Time 0.00
Received By ccole Date 2015-10-08 Time 16:11 Sent To  
Notes
2015-10-08 16:53:021ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100027
 10/8/15
  
 1) SHEET M1.1: REFER TO SECTION 606.2.1 RETURN AIR
 SYSTEMS.
 SMOKE DETECTORS SHALL BE INSTALLED IN RETURN AIR
 SYSTEMS WITH A DESIGN CAPACITY GREATER THAN 2,000 CFM
 (0.9 M3/S) IN THE RETURN AIR DUCT OR PLENUM UPSTREAM OF
 ANY FILTERS, EXHAUST AIR CONNECTIONS, OUTDOOR AIR
 CONNECTIONS, OR DECONTAMINATION EQUIPMENT AND
 APPLIANCES.
 PLEASE REVISE THE PLAN TO SHOW A DUCT SMOKE DETECTOR IN
 THE RETURN AIR SYSTEM AND PROVIDE DETAILS INDICATING
 COMPLIANCE WITH-
 A) 606.4 CONTROLS OPERATION.
 UPON ACTIVATION, THE SMOKE DETECTORS SHALL SHUT DOWN
 ALL OPERATIONAL CAPABILITIES OF THE AIR DISTRIBUTION
 SYSTEM IN ACCORDANCE WITH THE LISTING AND LABELING OF
 APPLIANCES USED IN THE SYSTEM. AIR DISTRIBUTION SYSTEMS
 THAT ARE PART OF A SMOKE CONTROL SYSTEM SHALL SWITCH TO
 THE SMOKE CONTROL MODE UPON ACTIVATION OF A DETECTOR.
 B) 606.4.1 SUPERVISION.
 THE DUCT SMOKE DETECTORS SHALL BE CONNECTED TO A FIRE
 ALARM SYSTEM WHERE A FIRE ALARM SYSTEM IS REQUIRED BY
 THE FLORIDA FIRE PREVENTION CODE. THE ACTUATION OF A
 DUCT SMOKE DETECTOR SHALL ACTIVATE A VISIBLE AND
 AUDIBLE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION.
 2) EXHAUST SYSTEMS ARE REQUIRED FOR THE FITTING ROOMS
 AT A RATE OF .25 CFM/SQ.FT. REFER TO TABLE 403.3 AND
 REVISE THE PLAN ACCORDINGLY.
 3) SHUTOFF DAMPER CONTROLS ARE REQUIRED THAT WILL
 AUTOMATICALLY SHUT OFF THE OUTSIDE AIR SUPPLY WHEN THE
 SYSTEM OR SPACE IS NOT IN USE- REFER TO SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-12-16 Cont ID  
Sent By gjohnson Date 2015-12-16 Time 09:53 Rev Time 0.00
Received By gjohnson Date 2015-12-16 Time 09:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-10-08 Cont ID  
Sent By gjohnson Date 2015-10-08 Time 14:15 Rev Time 0.00
Received By gjohnson Date 2015-10-08 Time 14:15 Sent To  
Notes
2015-10-08 15:07:47 
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE DETAIL ON ACCESSIBILITY FOR WATER
 FOUNTAIN THE DETAIL ON SHEET A13.1
 PER WPB AMEND. 107.2.1
 2. SHEET G1.1 UNDER PLUMBING FIXTURES PUBLIC ACCESS NOT
 REQUIRED ,PLEASE SHOW TRAVEL DISTANCE NOT TO EXCEED 300
 FT. FROM MAIN ENTRANCE OF ANY STORE OR TENANT SPACE. TO
 PUBLIC BATHROOMS
 PER FBC P SEC 403.3.4
 3.SHEET G1.1 UNDER PLUMBING FIXTURES SERVICE SINK NOT
 REQUIRED .FBC P TABLE 403.1 MINIMUM NUMBER OF REQUIRED
 PLUMBING FIXTURES. SHOWS A SERVICE SINK IS REQUIRED.
 PLEASE CLARIFY.
 PER. WPB AMEND 107.2.1
 4. IS THE WATER FOUNTAIN EXISTING IF NOT PLEASE
 PROVIVED RISER DIAGRAM.
 PER WPB AMEND. 107.3.5.1.3(13)

Review Stop Z ZONING
Rev No 2 Status P Date 2015-12-16 Cont ID  
Sent By eschneid Date 2015-12-16 Time 16:25 Rev Time 0.00
Received By eschneid Date 2015-12-16 Time 16:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-10-23 Cont ID  
Sent By eschneid Date 2015-10-23 Time 09:56 Rev Time 0.25
Received By eschneid Date 2015-10-23 Time 09:56 Sent To  
Notes
2015-10-23 10:05:54PASSED
  
 1) SIGNS REQUIRE SEPARATE PERMITS WITH PLANS.
  
 2) ROOFTOP MECHANICAL EQUIPMENT SHALL BE SCREENED.