| 2015-10-08 16:53:02 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15100027 |
| | 10/8/15 |
| | |
| | 1) SHEET M1.1: REFER TO SECTION 606.2.1 RETURN AIR |
| | SYSTEMS. |
| | SMOKE DETECTORS SHALL BE INSTALLED IN RETURN AIR |
| | SYSTEMS WITH A DESIGN CAPACITY GREATER THAN 2,000 CFM |
| | (0.9 M3/S) IN THE RETURN AIR DUCT OR PLENUM UPSTREAM OF |
| | ANY FILTERS, EXHAUST AIR CONNECTIONS, OUTDOOR AIR |
| | CONNECTIONS, OR DECONTAMINATION EQUIPMENT AND |
| | APPLIANCES. |
| | PLEASE REVISE THE PLAN TO SHOW A DUCT SMOKE DETECTOR IN |
| | THE RETURN AIR SYSTEM AND PROVIDE DETAILS INDICATING |
| | COMPLIANCE WITH- |
| | A) 606.4 CONTROLS OPERATION. |
| | UPON ACTIVATION, THE SMOKE DETECTORS SHALL SHUT DOWN |
| | ALL OPERATIONAL CAPABILITIES OF THE AIR DISTRIBUTION |
| | SYSTEM IN ACCORDANCE WITH THE LISTING AND LABELING OF |
| | APPLIANCES USED IN THE SYSTEM. AIR DISTRIBUTION SYSTEMS |
| | THAT ARE PART OF A SMOKE CONTROL SYSTEM SHALL SWITCH TO |
| | THE SMOKE CONTROL MODE UPON ACTIVATION OF A DETECTOR. |
| | B) 606.4.1 SUPERVISION. |
| | THE DUCT SMOKE DETECTORS SHALL BE CONNECTED TO A FIRE |
| | ALARM SYSTEM WHERE A FIRE ALARM SYSTEM IS REQUIRED BY |
| | THE FLORIDA FIRE PREVENTION CODE. THE ACTUATION OF A |
| | DUCT SMOKE DETECTOR SHALL ACTIVATE A VISIBLE AND |
| | AUDIBLE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED |
| | LOCATION. |
| | 2) EXHAUST SYSTEMS ARE REQUIRED FOR THE FITTING ROOMS |
| | AT A RATE OF .25 CFM/SQ.FT. REFER TO TABLE 403.3 AND |
| | REVISE THE PLAN ACCORDINGLY. |
| | 3) SHUTOFF DAMPER CONTROLS ARE REQUIRED THAT WILL |
| | AUTOMATICALLY SHUT OFF THE OUTSIDE AIR SUPPLY WHEN THE |
| | SYSTEM OR SPACE IS NOT IN USE- REFER TO SECTION |
| | C403.2.4.4 FBC-14 ENERGY CONSERVATION. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |