| 2015-10-09 15:57:30 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15100011 |
| | ADD: 700 S. ROSEMARY AVE. SUITE # 232 |
| | CONT: TBD |
| | TEL: (856-6655 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. OCT. 09/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1 THE DEMOLITION PLAN INDICATES THE EXISTING |
| | DOUBLE ENTRY DOORS ARE TO BE RELOCATED. BOTH SHEETS A2 |
| | & A7 SHOW NEW DOUBLE ENTRY DOORS, THE DOOR WIDTH BEING |
| | (2) 2'-0" DOORS. PLEASE COMPLY WITH 2014 FBC-B |
| | BUILDING. 1008.1.1 SIZE OF DOORS. THE MINIMUM WIDTH OF |
| | EACH DOOR OPENING SHALL BE SUFFICIENT FOR THE OCCUPANT |
| | LOAD THEREOF AND SHALL PROVIDE A CLEAR WIDTH OF 32 |
| | INCHES (813 MM). CLEAR OPENINGS OF DOORWAYS WITH |
| | SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF |
| | THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES |
| | (1.57 RAD). WHERE THIS SECTION REQUIRES A MINIMUM CLEAR |
| | WIDTH OF 32 INCHES (813 MM) AND A DOOR OPENING INCLUDES |
| | TWO DOOR LEAVES WITHOUT A MULLION, ONE LEAF SHALL |
| | PROVIDE A CLEAR OPENING WIDTH OF 32 INCHES (813 MM). |
| | |
| | DISCREPANCY IN PLANS, SHEET A9 INDICATES (2) 3'-0" |
| | DOORS. |
| | |
| | 2) SHEET A7 THE LIFE SAFETY PLAN DOES NOT INDICATE WHAT |
| | THE OCCUPANT LOAD IS FOR THE TENANT SPACE OFFICE AND |
| | KITCHEN WERE NOT FIGURED INTO THE EQUATION.2014 FBC-B |
| | TABLE 1004.1.2. |
| | |
| | 3A) PLEASE PROVIDE ON THE LIFE SAFETY SHEET A7 THE |
| | ALLOWABLE OCCUPANT LOAD PER EGRESS DOOR. 2014 FBC-B |
| | 1005.3.2 OTHER EGRESS COMPONENTS. THE CAPACITY, IN |
| | INCHES (MM), OF MEANS OF EGRESS COMPONENTS OTHER THAN |
| | STAIRWAYS SHALL BE CALCULATED BY MULTIPLYING THE |
| | OCCUPANT LOAD SERVED BY SUCH COMPONENT BY A MEANS OF |
| | EGRESS CAPACITY FACTOR OF 0.2 INCH (5.1 MM) PER |
| | OCCUPANT. |
| | |
| | 3B) 2014 FBC-B 1005.5. DISTRIBUTION OF EGRESS CAPACITY. |
| | WHERE MORE THAN ONE EXIT, OR ACCESS TO MORE THAN ONE |
| | EXIT, IS REQUIRED, THE MEANS OF EGRESS SHALL BE |
| | CONFIGURED SUCH THAT THE LOSS OF ANY ONE EXIT, OR |
| | ACCESS TO ONE EXIT, SHALL NOT REDUCE THE AVAILABLE |
| | CAPACITY TO LESS THAN 50 PERCENT OF THE REQUIRED |
| | CAPACITY. |
| | |
| | 4) SHEET A7 THE LIFE SAFETY PLAN SHOWS EGRESS PATHS |
| | THROUGH MAUALLY SLIDDING GLASS DOORS. THERE APPEARS TO |
| | BE (2) AREAS THAT HAVE SLIDDING GLASS DOORS, THE |
| | SLIDDING GLASS DOORS BETWEEN BAR AREA 12 AND BAR AREA |
| | 20, IT APPEARS THIS AREA IS TRYING TO BE USED AS A |
| | EGRESS PATH. PLEASE REVIEW 1008.1.2. EGRESS DOORS ARE |
| | TO BE PIVOTED OR SIDE HINGED SWING DOORS. |
| | |
| | 5) SHEET A7 THE OCCUPANT LOAD AROUND BAR # 12 THE MAIN |
| | BAR TO THE MAIN ENTRY HAS APPROXIMATELY 50 OCCUPANT |
| | LOAD COUNTING THE OCCUPANT LOAD BEHIND THE BAR. PLEASE |
| | SHOW COMPLIANCE WITH: |
| | |
| | 1028.10.1.2 SEATING AT TABLE AISLE ACCESSWAY LENGTH. |
| | THE LENGTH OF TRAVEL ALONG THE AISLE ACCESSWAY SHALL |
| | NOT EXCEED 30 FEET (9144 MM) FROM ANY SEAT TO THE POINT |
| | WHERE A PERSON HAS A CHOICE OF TWO OR MORE PATHS OF |
| | EGRESS TRAVEL TO SEPARATE EXITS. |
| | |
| | 6) SHEET A7 EXTERIOR DINING ROOM 20 HAS A COLUMN NEXT |
| | TO THE TABLE THE SEAT JUST TO THE SOUTH OF THE COLUMN |
| | HAS TO TRAVEL APPROXIMATELY 40 FEET BEFORE THERE ARE |
| | (2) CHOICES IN EXITING, THE COMMON PATH OF TRAVEL HAS |
| | BEEN EXCEEDED. |
| | |
| | 1028.10.1.2 SEATING AT TABLE AISLE ACCESSWAY LENGTH. |
| | THE LENGTH OF TRAVEL ALONG THE AISLE ACCESSWAY SHALL |
| | NOT EXCEED 30 FEET (9144 MM) FROM ANY SEAT TO THE POINT |
| | WHERE A PERSON HAS A CHOICE OF TWO OR MORE PATHS OF |
| | EGRESS TRAVEL TO SEPARATE EXITS. |
| | |
| | 7) SHEET A7 THE EXTERIOR BAR 20 IT APPEARS THERE ARE 8 |
| | BAR STOOLS NEXT TO THE SLIDING GLASS DOORS THAT T DOES |
| | NOT HAVE A 32 INCH EGRESS DOOR OPENING. 2014 FBC-B |
| | 1008.1.1 SIZE OF DOOR. |
| | |
| | 8) SHEET A2 & A7 BOTH SHOW A 14 INCH TALL STAGE OR |
| | RAISED PLATFORM, THE STAGE SHOWS A STEP BUT NO VERTICAL |
| | ACCESSIBILITY. PLEASE SHOW COMPLIANCE WITH 2014 |
| | FBC-ACCESSIBILITY CODE 201.1.1. |
| | |
| | 9) SHEET A7 INDICATES THERE IS 11 ACCESSIBLE LOCATIONS |
| | FOR WHEELCHAIR SETTING, THEN IN SMALLER LETTERING THE |
| | PLANS INDICATE ONLY EIGHT AND THERE IS ONLY 8 ONTHE |
| | PLANS. 2014 FBC-ACCESSIBLITY 226.1. WITH THE INTERIOR |
| | AND EXTERIOR SEATTING THE OCCUPANT SEAT COUNT IS 212 |
| | REQUIRING 11 ACCESSIBLE SEATING AREAS. |
| | |
| | 10) SHEET A2 AND A7 BOTH INDICATE NEW HINGED ENTRY |
| | DOORS AND HORIZONTAL SLIDING DOORS. 2010 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | |
| | 11) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | |
| | 12) MISSING WIND DESIGN CRITERIA FOR THE NEW OPENINGS. |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING |
| | INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN, |
| | REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF |
| | THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE: |
| | |
| | 12.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND |
| | GUST), MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND |
| | SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 12.2. RISK CATEGORY. |
| | |
| | 12.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. |
| | |
| | 12.4 APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 12.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| | M2). |
| | |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | |
| | 13) SHEET A2 AND A7 SHOW WOOD BARRELS SET OUT FROM THE |
| | WALL AS A WALL FINISH. PLEASE SHOW COMPLIANCE WITH [F] |
| | 806.1.2 COMBUSTIBLE DECORATIVE MATERIALS. THE |
| | PERMISSIBLE AMOUNT OF DECORATIVE MATERIALS MEETING THE |
| | FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 |
| | SHALL NOT EXCEED 10 PERCENT OF THE SPECIFIC WALL OR |
| | CEILING AREA TO WHICH IT IS ATTACHED. |
| | |
| | 14) SHEET A2 & A7 BOTH SHOW DROPPED WOOD FRAMING FOR A |
| | DECRATIVE CEILING, PLEASE SHOW COMPLIANCE WITH: |
| | 803.1.1 INTERIOR WALL AND CEILING FINISH MATERIALS. |
| | INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE |
| | CLASSIFIED IN ACCORDANCE WITH ASTM E 84 OR UL 723. SUCH |
| | INTERIOR FINISH MATERIALS SHALL BE GROUPED IN THE |
| | FOLLOWING CLASSES IN ACCORDANCE WITH THEIR FLAME SPREAD |
| | AND SMOKE-DEVELOPED INDEXES. |
| | |
| | CLASS A:FLAME SPREAD INDEX 0-25; SMOKE- |
| | DEVELOPED INDEX 0-450. |
| | |
| | CLASS B:=FLAME SPREAD INDEX 26-75; SMOKE- |
| | DEVELOPED INDEX 0-450. |
| | |
| | CLASS C:FLAME SPREAD INDEX 76-200; SMOKE- |
| | DEVELOPED INDEX 0-450. |
| | |
| | 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |