Plan Review Details - Permit 15091281
Plan Review Stops For Permit 15091281
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-04 Cont ID  
Sent By tklarge Date 2015-10-04 Time 07:54 Rev Time 0.00
Received By tklarge Date 2015-09-29 Time 15:42 Sent To  
Notes
2015-09-29 15:44:05ROUTED TO PLUMBING

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-10-05 Cont ID  
Sent By tklarge Date 2015-10-05 Time 09:38 Rev Time 0.00
Received By tklarge Date 2015-10-05 Time 09:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-10-04 Cont ID  
Sent By tklarge Date 2015-10-04 Time 07:54 Rev Time 0.00
Received By tklarge Date 2015-10-04 Time 07:39 Sent To  
Notes
2015-10-04 07:50:41PLUMBING REPAIR TUNNEL WORK
 A CLEAR AND LEGIBLE SANITARY RISER DIAGRAM SHALL BE
 SUBMITTED SHOWING ALL PIPE SIZES, CONNECTION POINTS TO
 EXISTING PIPING, HOW THE NEW PIPE WILL BE SUPPORTED,
 THE TYPE OF ADAPTERS USED FOR THE CONNECTIONS TO
 EXISTING PIPE, AND THE LOCATIONS OF REQUIRED CLEANOUTS.
 DETAILS AND BACKFILLING PROCEDURES SHALL BE SUBMITTED
 THAT CLEARLY SHOW HOW THE STRUCTURAL INTEGRITY OF THE
 CONCRETE SLAB WILL BE MAINTAINED DURING EXCAVATION AND
 BACKFILLING. STRUCTURAL FOAM IS NOT PERMITTED BELOW
 GROUND PER THE FLORIDA BUILDING CODE, RESIDENTIAL,
 SECTION R318.8 AND THE FLORIDA BUILDING CODE, BUILDING,
 SECTION 2603.9.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  