Plan Review Details - Permit 15091280
Plan Review Stops For Permit 15091280
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-12-15 Cont ID  
Sent By jgomez Date 2015-12-15 Time 14:31 Rev Time 0.00
Received By jgomez Date 2015-12-15 Time 14:22 Sent To  
Notes
2015-12-15 14:40:06BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- ENERGY CALCULATIONS SUBMITTED;
 A)PROVIDE THE INSPECTION CHECKLIST AS REQUIRED BY SEC.
 R405.4.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-12-11 Cont ID  
Sent By jgomez Date 2015-12-11 Time 09:19 Rev Time 0.00
Received By jgomez Date 2015-12-11 Time 09:19 Sent To E
Notes
2015-12-11 09:44:45RESIDENTIAL (R3) GARAGE CONVERSION TO FAMILY ROOM
 REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE: BUILDING REVIEW MAY BE APPROVED ONCE I GET THE
 IMPACT FEES STAMPED PLANS WITH COPY OF PAID RECEIPT (IF
 REQUIRED) AND WITH THE INFORMATION REQUESTED FOR THE
 ENERGY CALCULATIONS BELOW. PLEASE CONTACT JULIO WHEN
 THIS INFORMATION IS PROVIDED TO FINISH MY REVIEW.
  
  
 1- CONVERSION OF GARAGE TO FAMILY ROOM REQUIRES IMPACT
 FEES ASSESSMENT. BRING PLANS TO PALM BEACH COUNTY (2300
 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. BRING BACK
 COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES
 ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED
 LAND DEVELOPMENT CODE.
  
 2-ENERGY CALCULATIONS SUBMITTED;
 A)OWNER/AGENT TO CERTIFY CODE COMPLIANCE AT THE BOTTOM
 OF THE FORM AS REQUIRED BY SEC. R103.1.1.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMITTING
 OFFICE AND JURISDICTION NUMBER. SEC. R101.5.1.1.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 C) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 D) BUILDER TO COMPLETE THE COMPLETE INSPECTION
 CHECKLIST AS REQUIRED BY SEC. R405.4.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-06 Cont ID  
Sent By jgomez Date 2015-11-06 Time 14:20 Rev Time 0.00
Received By jgomez Date 2015-11-06 Time 07:32 Sent To  
Notes
2015-11-06 14:45:54RESIDENTIAL (R3) ALTERATION/ADDITION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- A) PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 NOTE: ENERGY CALCULATIONS WILL NOT BE REQUIRED IF THE
 HOUSE IS A TRUE CONTRIBUTING HISTORIC HOUSE. I AM
 WAITING FROM THE HISTORIC PRESERVATION PLANNER RESPONSE
 REGARDING THE HISTORIC CONTRIBUTION OF THE HOUSE.
  
 11/9/15 RECEIVED CONFIRMATION FROM THE HISTORIC
 PRESERVATION PLANNER: THIS IS NOT A CONTRIBUTING
 HISTORIC HOUSE.
  
 B) PLEASE PROVIDE INFORMATION ON PLANS AND ENERGY
 CALCULATIONS AS REQUIRED BY SEC. R103.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). SPECIFY INSULATION ON
 WALLS, CEILINGS, ETC.
  
 2- THE PROPOSED USE OF THE GARAGE IS NOT CLEAR.
 ACCORDING TO THE PLANS SUBMITTED THE GARAGE USE IS NOT
 LONGER AS A GARAGE BUT AS HABITABLE SPACE. THE SPACE IS
 GOING TO BE AIR CONDITIONED AND LOOKS MORE LIKE AN
 ENTERTAINMENT ROOM THAN A GARAGE. ALSO, THE SPACE IS
 NOT FUNCTIONAL AS A GARAGE BECAUSE THE GARAGE DOOR IS
 PROPOSED TO BE INOPERABLE. PLAN REVIEW CAN NOT BE
 PROPERLY DONE IF THE PROPOSED PLANS DON'T MATCH THE
 PROPOSED USE. IF THE INTENTION IS TO HAVE AN
 ENTERTAINMENT ROOM, THEN CLEARLY IDENTIFY ROOM AS SO.
 SEC. 107.2.1 CITY AMENDMENTS.
 IF THE ROOM STAYS AS GARAGE, THEN IT NEEDS TO CLEARLY
 SHOW USE AS A GARAGE. NOTE: THE A/C WOULDN'T COMPLY
 BECAUSE RETURN AIR CAN'T BE TAKEN FROM THE GARAGE.
 ALSO, TAKE INTO ACCOUNT THAT ENERGY CALCULATIONS MAY
 NOT PASS BASED ON THE AMOUNT OF GLAZING IN THE GARAGE
 AND THE INFILTRATION THRU THE GARAGE DOOR.
  
 3- SHEET A-1: STRUCTURAL NOTES REFERENCE THE 2010 CODE
 AND SEC. 1609. THE CURRENT CODE IS THE FBC-RESIDENTIAL,
 5TH EDITION (2014) AND THE CORRECT SEC. IS R301. REVISE
 AS REQUIRED . SEC. 107.2.1 CITY AMENDMENTS.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED FAC
 61G20-3.002(33) FOR:
 A) FRENCH DOOR TRANSOM MULLION AS SHOWN ON PLANS. AND,
 CLEARLY IDENTIFY MULLION SIZE TO VERIFY THE DESIGN
 PRESSURES. SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-12-15 Cont ID  
Sent By skennedy Date 2015-12-15 Time 14:15 Rev Time 0.00
Received By skennedy Date 2015-12-15 Time 14:15 Sent To  
Notes
2015-12-15 14:16:063RD REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
  
 PROVISIONALLY APPROVED:
  
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM.
 NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET
 NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
 FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED
 BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER
 INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT.
 FBCRE4002.14 TAMPER-RESISTANT RECEPTACLES.
 IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE LISTED
 TAMPER-RESISTANT RECEPTACLES.
 (2) WALL SPACE. AS USED IN THIS SECTION, A WALL SPACE
 SHALL
 INCLUDE THE FOLLOWING:
 (1) ANY SPACE 600 MM (2 FT) OR MORE IN WIDTH (INCLUDING
 SPACE MEASURED AROUND CORNERS) AND UNBROKEN ALONG
 THE FLOOR LINE BY DOORWAYS AND SIMILAR OPENINGS,
 FIREPLACES,
 AND FIXED CABINETS
 (2) THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR
 WALLS,
 EXCLUDING SLIDING PANELS
 (3) THE SPACE AFFORDED BY FIXED ROOM DIVIDERS, SUCH AS
 FREESTANDING BAR-TYPE COUNTERS OR RAILINGS
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-12-14 Cont ID  
Sent By mvaldes Date 2015-12-14 Time 08:36 Rev Time 0.00
Received By mvaldes Date 2015-12-14 Time 08:36 Sent To  
Notes
2015-12-14 08:59:511ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM.
 NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET
 NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
 FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED
 BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER
 INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT.
 FBCRE4002.14 TAMPER-RESISTANT RECEPTACLES.
 IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE LISTED
 TAMPER-RESISTANT RECEPTACLES.
 (2) WALL SPACE. AS USED IN THIS SECTION, A WALL SPACE
 SHALL
 INCLUDE THE FOLLOWING:
 (1) ANY SPACE 600 MM (2 FT) OR MORE IN WIDTH (INCLUDING
 SPACE MEASURED AROUND CORNERS) AND UNBROKEN ALONG
 THE FLOOR LINE BY DOORWAYS AND SIMILAR OPENINGS,
 FIREPLACES,
 AND FIXED CABINETS
 (2) THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR
 WALLS,
 EXCLUDING SLIDING PANELS
 (3) THE SPACE AFFORDED BY FIXED ROOM DIVIDERS, SUCH AS
 FREESTANDING BAR-TYPE COUNTERS OR RAILINGS
2015-12-11 14:04:53NEW REVISED DRAWINGS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-11-03 Cont ID  
Sent By mvaldes Date 2015-11-03 Time 10:04 Rev Time 0.00
Received By dharvey Date 2015-11-03 Time 10:04 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-10-01 Cont ID  
Sent By fmittner Date 2015-10-01 Time 10:34 Rev Time 0.00
Received By fmittner Date 2015-10-01 Time 10:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-15 Cont ID  
Sent By jgomez Date 2015-12-15 Time 14:55 Rev Time 0.00
Received By jgomez Date 2015-12-15 Time 14:25 Sent To  
Notes
2015-12-15 14:25:40IMPACT FEES RE-SUBMITTAL. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-14 Cont ID  
Sent By mvaldes Date 2015-12-14 Time 10:07 Rev Time 0.00
Received By mvaldes Date 2015-12-01 Time 10:48 Sent To  
Notes
2015-12-01 10:49:32R01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-06 Cont ID  
Sent By jgomez Date 2015-11-06 Time 17:27 Rev Time 0.00
Received By jgomez Date 2015-10-02 Time 07:50 Sent To  
Notes
2015-10-02 10:00:07R07
2015-10-02 07:50:5910/2 TO INCOMING
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-12-15 Cont ID  
Sent By jgomez Date 2015-12-15 Time 14:52 Rev Time 0.00
Received By jgomez Date 2015-12-15 Time 14:52 Sent To  
Notes
2015-12-15 14:53:52$180.65 PAID. MU-2015-028838.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-12-11 Cont ID  
Sent By jgomez Date 2015-12-11 Time 14:05 Rev Time 0.00
Received By jgomez Date 2015-12-11 Time 14:05 Sent To  
Notes
2015-12-11 14:05:591- CONVERSION OF GARAGE TO FAMILY ROOM REQUIRES IMPACT
 FEES ASSESSMENT. BRING PLANS TO PALM BEACH COUNTY (2300
 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. BRING BACK
 COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES
 ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED
 LAND DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-11-06 Cont ID  
Sent By jgomez Date 2015-11-06 Time 16:13 Rev Time 0.00
Received By jgomez Date 2015-11-06 Time 16:13 Sent To  
Notes
2015-11-06 16:15:06AFTER CLARIFICATION OF THE USED OF GARAGE AS GARAGE OR
 ENTERTAINMENT CENTER IMPACT FEES ASSESSMENT MAY BE
 REQUIRED. SEE BUILDING REVIEW COMMENTS. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-12-11 Cont ID  
Sent By jgomez Date 2015-12-11 Time 15:03 Rev Time 0.00
Received By jgomez Date 2015-12-11 Time 15:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-06 Cont ID  
Sent By jgomez Date 2015-11-06 Time 17:27 Rev Time 0.00
Received By jgomez Date 2015-11-06 Time 17:27 Sent To  
Notes
2015-11-06 17:31:39RESIDENTIAL (R3) ALTERATION/ADDITION MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- A/C RETURN AIR CAN'T BE TAKEN FROM THE GARAGE. SEC.
 1602.2 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-12-07 Cont ID  
Sent By gjohnson Date 2015-12-07 Time 10:20 Rev Time 0.00
Received By gjohnson Date 2015-12-07 Time 10:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-10-13 Cont ID  
Sent By gjohnson Date 2015-10-13 Time 11:37 Rev Time 0.00
Received By gjohnson Date 2015-10-13 Time 11:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-10-01 Cont ID  
Sent By fmittner Date 2015-10-01 Time 10:34 Rev Time 0.00
Received By fmittner Date 2015-10-01 Time 10:34 Sent To B
Notes
***NONE***