Plan Review Details - Permit 15091231
Plan Review Stops For Permit 15091231
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-02-24 Cont ID  
Sent By jgomez Date 2016-02-23 Time 18:12 Rev Time 0.00
Received By jgomez Date 2016-02-23 Time 18:12 Sent To  
Notes
2016-02-23 18:22:59 
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR;
 (A) SINGLE HUNG WINDOWS. DESIGN PRESSURES ON THE NEW MI
 WINDOWS PRODUCT APPROVAL FL 17499 SUBMITTED DON'T MEET
 THE DESIGN PRESSURES CALCULATED BY THE ENGINEER.
 (B) GLASS BLOCK AS SHOWN ON PLANS. NOA 12-0406.05
 SUBMITTED WAS VOID.
  
 2- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT APPROVAL
 PRIOR TO SUBMITTAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-01-25 Cont ID  
Sent By jgomez Date 2016-01-22 Time 18:06 Rev Time 0.00
Received By jgomez Date 2016-01-22 Time 17:29 Sent To  
Notes
2016-01-22 17:52:48RESIDENTIAL (R3) ADDITION, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) GARAGE DOOR THAT MEETS THE ENGINEER OF RECORD
 CALCULATED DESIGN PRESSURES. SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE: GARAGE OVERHEAD DOOR SHOWN ON FLORIDA PRODUCT
 APPROVAL FL5678-R3 SUBMITTED DOESN'T MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER OF RECORD. (REPEAT
 COMMENT).
  
 2- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT APPROVAL
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 3- REVISE THE ENERGY CALCULATIONS SUBMITTED:
 A) THE CEILING INFORMATION SHOWN ON ITEM #10 DOESN'T
 MATCH PLANS. PLANS CALL FOR AN UNVENTED ATTIC NOT
 VENTED. SEE PLANS AND REVISE AS REQUIRED. SEC. R103.2
 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) REVISE CLIMATE ZONE ON PAGE 2 OF 5. SEE CLIMATE
 ZONES ON TABLE C301.1 OF FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014) AND REVISE AS REQUIRED.
  
 C) REVISE ROOF TYPE ON PAGE 2 OF 5 TO MATCH PLANS.
 PLANS SHOW GABLE ROOF NOT HIP. SEE PLANS AND REVISE ASS
 REQUIRED. SEC. R103.2 OF FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 D) REVISE DOOR TYPE SHOWN ON PAGE 3 OF 5. PLANS AND
 PRODUCT APPROVAL SUBMITTED DON'T SHOW ANY WOOD DOORS.
 PRODUCT APPROVAL SUBMITTED IS FOR ALUMINUM GLAZED
 DOORS. THESE DOORS NEED TO BE INCLUDED IN THE WINDOWS
 SEC. AS REQUIRED BY SEC. R405.5.3.3 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 E) THE ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 NEEDS TO BE COMPLETED BY THE BUILDER AS REQUIRED BY
 SEC. R405.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 F) THE AIR BARRIER AND INSULATION INSPECTION COMPONENT
 CRITERIA NEEDS TO BE COMPLETED AS REQUIRED BY SEC.
 R405.4.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 G) COMPLETE INFORMATION ON TOP OF FORM, INCLUDING
 BUILDER'S NAME, PERMITTING OFFICE AND JURISDICTION
 NUMBER. SEC. R101.5.1.1.2 OF FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
 NOTE: PROVIDE THE CORRECT NAME OF THE BUILDER. THIS IS
 NOT AN OWNER/BUILDER CONSTRUCTION.
  
 H) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION
 SHOWN ON PAGE 3 OF 4 TO MATCH PLANS. SEC. R405.5.3.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING
 THE DEFAULT FACTOR FOR GLAZING.
  
 4- ENERGY CALCULATIONS ARE TAKING THE CEILING FAN
 CREDIT. PLANS TO SHOW THE MINIMUM SIZE OF CEILING FAN
 AS REQUIRED BY TABLE R405.7.6 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE PUT TOGETHER TWO NEW SET OF DRAWINGS BY
 INSERTING REVISED DRAWINGS AND REMOVING OLD DRAWINGS.
 DON'T STAPLE OLD DRAWINGS TO NEW SET.. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-12-10 Cont ID  
Sent By jgomez Date 2015-12-09 Time 16:54 Rev Time 0.00
Received By jgomez Date 2015-12-09 Time 16:54 Sent To  
Notes
2015-12-09 16:59:11RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
 ****NOTE:
 THERE ARE TWO OPTIONS TO ADDRESS COMMENTS BELOW. PERMIT
 MAY BE ISSUED WITH PROVISO OR CONTRACTOR MAY RE-SUBMIT
 INFORMATION ADDRESSING THE COMMENTS. PROVISO MEANS THAT
 CONTRACTOR WILL ADDRESS ALL THE COMMENTS AFTER THE
 PERMIT IS ISSUED. REVISION FEES WILL APPLY. CONTRACTOR
 TO ADVICE PREFERRED OPTION: PROVISO OR RE-SUBMITTAL.
  
 1- GARAGE DOOR LEADING TO THE INTERIOR OF THE HOUSE:
 PROVIDE SPECIFICATIONS SHOWING COMPLIANCE WITH SEC.
 R302.5.1 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 SPECIFY FIRE RATED DOOR AND SELF CLOSING.
 RESPONSE: THERE ARE NOT SPECIFICATIONS FOR SELF-CLOSING
 DOOR.
  
 2- DETAIL 4/S-2: SPECIFY SPACING FOR THE #5 REBAR AT
 EXISTING PARAPET EXTENSION. SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE: SPACING OF #5 REBARS WAS NOT SPECIFIED.
  
 3- TYPICAL STEM WALL SECTION ON SHEET S-2:
 A) PROVIDE ICYNENE ICC EVALUATION REPORT. (2 COPIES).
 ICC REPORT TO BE REVIEWED AND APPROVED BY THE ENGINEER
 OF RECORD PRIOR TO SUBMITTAL TO THIS OFFICE. SEC.
 107.3.4.1 CITY AMENDMENTS.
 RESPONSE: ICC EVALUATION REPORT SUBMITTED EXPIRED ON
 FEBRUARY 1, 2015, PROVIDE CURRENT REPORT.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) GARAGE DOOR THAT MEETS THE ENGINEER OF RECORD
 CALCULATED DESIGN PRESSURES. SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE: NO PRODUCT APPROVAL SUBMITTED.
  
 5- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT APPROVAL
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 6- REVISE THE ENERGY CALCULATIONS SUBMITTED:
 A) COMPLETE INFORMATION ON TOP OF FORM, INCLUDING
 BUILDER'S NAME AND PERMITTING OFFICE. SEC. R101.5.1.1.2
 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT
 COMMENT).
  
 B) OWNER/AGENT TO PROPERLY SIGN AND DATE BOTTOM OF
 FORM. THE FORM SUBMITTED WAS NOT SIGNED BY THE OWNER.
 IT ONLY STATES "TIESHA & RONALD SMALL". THIS IS NOT A
 SIGNATURE. R103.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014). (REPEAT COMMENT).
  
 C) REVISE THE DOORS INFORMATION ON PAGE 3 OF 4. THERE
 IS NOT INSULATED WOOD DOOR ON THE WEST ELEVATION. THIS
 DOOR NEEDS TO BE CONSIDERED AS GLAZING AS REQUIRED BY
 SEC. R405.5.3.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). SEE PRODUCT APPROVAL SUBMITTED. (REPEAT
 COMMENT).
  
 D) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION
 SHOWN ON PAGE 3 OF 4 TO MATCH PLANS. SEC. R405.5.3.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT
 COMMENT). NOTE: ALSO, COORDINATE GLAZING AREA WITH ITEM
 #6(C) ABOVE. (REPEAT COMMENT).
  
 E) THE BUILDER NEEDS TO COMPLETE AND SIGN/DATE THE
 BOTTOM OF THE ENERGY PERFORMANCE LEVEL CARD (EPL). SEC.
 R405.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 F) CLIMATE ZONE SHOWN ON PAGE 2 OF 5 IS INCORRECT. SEE
 TABLE R301.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014) AND REVISE.
  
 G) INSULATION R-VALUE SHOWN ON ITEM #10 IS INCORRECT.
 SEE PLANS AND REVISE AS REQUIRED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 H) REVISE R-VALUE ON CEILING INFORMATION ON PAGE 2 OF
 5. SEE PLANS AND REVISE AS REQUIRED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING
 THE DEFAULT FACTOR FOR GLAZING.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE PUT TOGETHER TWO NEW SET OF DRAWINGS BY
 INSERTING REVISED DRAWINGS AND REMOVING OLD DRAWINGS.
 DON'T STAPLE OLD DRAWINGS TO NEW SET.. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-29 Cont ID  
Sent By jgomez Date 2015-10-29 Time 15:16 Rev Time 0.00
Received By jgomez Date 2015-10-29 Time 14:05 Sent To  
Notes
2015-10-29 15:17:39RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS.
 CODE: FBC, 5TH EDITION (2014).
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- WINDOWS ON THE NORTH WALL OF EXISTING BEDROOMS #1
 AND #2 ARE GOING TO BE BLOCKED TO ALLOW FOR THE NEW
 ADDITION. EGRESS IS GOING TO BE REDUCED. SPECIFY AT
 LEAST ONE WINDOW TYPE AND SIZE FOR EACH BEDROOM THAT
 WILL COMPLY WITH THE EGRESS REQUIREMENTS OF SEC. R310
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- SIZE OF NEW ENTRY DOOR NEEDS TO COMPLY WITH SEC.
 R311.2 OF FBC-RESIDENTIAL, 5TH EDITION (2014). THE DOOR
 LEAF SHALL PROVIDE A MINIMUM CLEAR WIDTH OF 32". PAIR
 OF 5'-0" X 6'-8" FRENCH DOORS SPECIFIED PROVIDES 2'-6"
 LEAF DOOR WHICH DOESN'T ALLOW 32" CLEAR OPENING. REVISE
 SIZE OF DOORS AS REQUIRED.
  
 4- GARAGE DOOR LEADING TO THE INTERIOR OF THE HOUSE:
 PROVIDE SPECIFICATIONS SHOWING COMPLIANCE WITH SEC.
 R302.5.1 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 SPECIFY FIRE RATED DOOR AND SELF CLOSING.
  
 5- SPECIFY CARBON MONOXIDE ALARMS BY EXISTING BEDROOMS
 AS REQUIRED BY SEC. R315 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 6- A) SPECIFY ATTIC ACCESS SIZE. ALSO, LOCATION OF
 ATTIC ACCESS TO COMPLY WITH SEC. R807 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). CHECK FOR HEIGHT
 CLEARANCE.
  
 B) DESIGN PARAMETERS ON SHEET S-3: SPECIFY THE ATTIC
 LIVE LOAD AS REQUIRED BY TABLE R301.5 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). CLEARLY SPECIFY IF
 DESIGNING ATTIC WITH OR WITHOUT STORAGE. SEE GENERAL
 ROOF NOTE #13 AND FOOTNOTES ON TABLE R301.5 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 7- DETAIL 4/S-2: SPECIFY SPACING FOR THE #5 REBAR AT
 EXISTING PARAPET EXTENSION. SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 8- TYPICAL STEM WALL SECTION ON SHEET S-2:
 A) LOCATION OF FOAM ICYNENE INSULATION SHOWN ON THE
 TYPICAL WALL IS INCORRECT. ICYNENE FOAM INSULATION IS
 USED TO ENCLOSE THE BUILDING THERMAL ENVELOPE AT THE
 UNDERSIDE OF THE ROOF SHEATHING SO ATTIC VENTILATION IS
 NOT REQUIRED. REVISE AS REQUIRED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014)
  
 B) PROVIDE ICYNENE ICC EVALUATION REPORT. (2 COPIES).
 ICC REPORT TO BE REVIEWED AND APPROVED BY THE ENGINEER
 OF RECORD PRIOR TO SUBMITTAL TO THIS OFFICE. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 C) CLARIFY IF ENGINEER IS DESIGNING AN UNVENTED ATTIC
 OR VENTED ATTIC. WALL SECTIONS CALL FOR ICYNENE FOAM
 INSULATION AND THERE ARE ALSO SPECIFICATIONS FOR 7" X
 24" SCREEN VENTS AT 8'-0" O.C. SEC. R806 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 NOTE: COORDINATE WITH THE ENERGY CALCULATIONS TO AVOID
 CONFLICTS/DELAYS.
  
 9- TYPICAL WOOD BUCK TO CONCRETE CONNECTION DETAIL ON
 SHEET S-2:
 A) GARAGE DOOR PROPOSED COLUMNS ARE CONCRETE BLOCK
 FILLED CELLS NOT CONCRETE COLUMNS. IT MAKES A
 SIGNIFICANT STRUCTURAL DIFFERENCE. REVISE DETAIL
 LABELING AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) ENGINEER TO SPECIFY THE GARAGE DOOR CALCULATED
 DESIGN PRESSURES. SEC. R301 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 C) ENGINEER TO PROVIDE CALCULATIONS SHOWING THAT
 PROPOSED ANCHOR SPACING (30"O.C.) SPECIFIED FOR THE
 GARAGE DOOR STRUCTURAL BUCK DETAIL IS ADEQUATE TO
 RESIST THE CALCULATED DESIGN PRESSURES. SEC. 107.2.1.3
 CITY AMENDMENTS. NOTE: THE ATTACHMENT OF THE STRUCTURAL
 GARAGE BUCK IS THE DESIGNER OF RECORD RESPONSIBILITY
 NOT THE GARAGE DOOR PRODUCT APPROVAL. COORDINATE WITH
 GARAGE DOOR PRODUCT APPROVAL TO AVOID CONFLICTS.
  
 10- REVISE ROOF SHEATHING NAILING SPACING SHOWN ON THE
 COMPONENT AND CLADDING PRESSURES ZONES ON SHEET S-4 FOR
 ROOF ZONE 1 AND 2. NEED 6" O.C. NAIL SPACING NOT 12"
 O.C. AS REQUIRED BY SEC. R803.2.3.1 OF FBC-RESIDENTIAL,
 5TH EDITION (2014).
  
 11- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $80,000. THE
 PERMIT FEE BALANCE IS $1977.58.
  
 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ASPHALT SHINGLES. FLORIDA PRODUCT APPROVAL FL9792-R4
 SUBMITTED IS FOR 2010 FBC. NEED FLORIDA PRODUCT
 APPROVAL FOR THE CURRENT CODE IN EFFECT , 2014 CODE
 VERSION
  
 B) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL
 FL239-R17 SUBMITTED IS FOR 2010 FBC. NEED FLORIDA
 PRODUCT APPROVAL FOR THE CURRENT CODE IN EFFECT , 2014
 CODE VERSION
  
 C) GARAGE DOOR THAT MEETS THE ENGINEER OF RECORD
 CALCULATED DESIGN PRESSURES. SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 D) FRENCH DOORS IN NEW ENTRY. FLORIDA PRODUCT APPROVAL
 FL253-R11 SUBMITTED IS FOR 2010 FBC. NEED FLORIDA
 PRODUCT APPROVAL FOR THE CURRENT CODE IN EFFECT , 2014
 CODE VERSION
  
 E) WINDOW MULLIONS. AND CLEARLY MARK SIZE OF MULLION
 USED TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF
 SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 13- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 14-REVISE THE ENERGY CALCULATIONS SUBMITTED (NOTE:
 COORDINATE WITH PLANS TO AVOID CONFLICTS/DELAYS):
 A) ADDRESS ON TOP FORM IS INCORRECT. ALSO, COMPLETE ALL
 THE INFORMATION ON TOP OF FORM, INCLUDING BUILDER'S
 NAME, PERMIT OFFICE AND JURISDICTION NUMBER. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 B) COORDINATE CEILING INFORMATION ON ITEM #10 WITH
 PLANS. PLANS NEED TO BE REVISED. THEY SHOW CONFLICTING
 INFORMATION: VENTED AND UNVENTED ATTICS. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) OWNER/AGENT TO PROPERLY SIGN AND DATE BOTTOM OF
 FORM. THE FORM SUBMITTED WAS NOT SIGNED BY THE OWNER.
 IT ONLY STATES "SMALL'S RESIDENCE". IDENTIFY WHO
 CERTIFIES AS OWNER/AGENT AS REQUIRED BY SEC. R103.1.1.2
 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 D) REVISE "SPACES" INFORMATION ON PAGE 2 OF 4. THERE IS
 NOT KITCHEN IN THIS ADDITION. SEC. R101.5.1.1.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 E) REVISE THE ROOF TYPE SHOWN ON PAGE 2 OF 4. THIS IS A
 GABLE TYPE OF ROOF NOT HIP. SEC. R101.5.1.1.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 F) REVISE THE DOORS INFORMATION ON PAGE 3 OF 4. THERE
 IS NOT INSULATED DOOR ON THE WEST ELEVATION. THIS DOOR
 NEEDS TO BE CONSIDERED AS GLAZING AS REQUIRED BY SEC.
 R405.5.3.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). SEE PRODUCT APPROVAL SUBMITTED.
  
 G) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION
 SHOWN ON PAGE 3 OF 4 TO MATCH PLANS. SEC. R405.5.3.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE PUT TOGETHER TWO NEW SET OF DRAWINGS BY
 INSERTING REVISED DRAWINGS AND REMOVING OLD DRAWINGS.
 DON'T STAPLE OLD DRAWINGS TO NEW SET.. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-01-14 Cont ID  
Sent By mvaldes Date 2016-01-14 Time 15:36 Rev Time 0.00
Received By mvaldes Date 2016-01-14 Time 15:36 Sent To  
Notes
2016-01-14 15:37:46FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 THIS PERMIT WILL BE APPROVED WITH A PROVISO AFCI
 PROTECTION REQUIRED PER NEC 210.12B

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-12-10 Cont ID  
Sent By jgomez Date 2015-12-10 Time 14:24 Rev Time 0.00
Received By mvaldes Date 2015-12-10 Time 18:04 Sent To  
Notes
2015-12-10 19:00:191ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
  
 NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
 FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED
 BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER
 INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT.
  
 C402.4.8 RECESSED LIGHTING.
 RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL
 ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED AND UNCONDITIONED SPACES. ALL RECESSED
 LUMINAIRES SHALL BE IC-RATED AND LABELED AS HAVING AN
 AIR LEAKAGE RATE OF NOT MORE THAN 2.0 CFM (0.944 L/S)
 WHEN TESTED IN ACCORDANCE WITH ASTM E 283 AT A 1.57 PSF
 (75 PA) PRESSURE DIFFERENTIAL. ALL RECESSED LUMINAIRES
 SHALL BE SEALED WITH A GASKET OR CAULK BETWEEN THE
 HOUSING AND INTERIOR WALL OR CEILING COVERING.
 75 % LAMPS MUST BE HIGH EFFCIENCY.
  
 GENERAL NOTE # 5 SHOWS THHN INSULATION HOWEVER NOT
 RATED FOR WET LOCATION NEED TO SHOW THWN / COMBINATION.
 W / H DOESN'T SHOW DISCONECTING MEANS WITHIN SIGHT.
  
 (1) ONE-FAMILY AND TWO-FAMILY DWELLINGS. FOR A
 ONEFAMILY
 DWELLING AND EACH UNIT OF A TWO-FAMILY DWELLING THAT
 IS AT GRADE LEVEL, AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE
 WHILE STANDING AT GRADE LEVEL AND LOCATED NOT MORE THAN
 2.0 M (61?2 FT) ABOVE GRADE SHALL BE INSTALLED AT THE
 FRONT AND BACK OF THE DWELLING.
  
 PROVIDE GFCI PROTECTION IN GARAGE , OUTDOORS , AND IN
 LAUNDRY ROOM.
2015-12-10 13:48:06NEW DRAWINGS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-11-03 Cont ID  
Sent By ppetty Date 2015-11-03 Time 08:34 Rev Time 0.00
Received By ppetty Date 2015-11-03 Time 08:34 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-02-24 Cont ID  
Sent By jgomez Date 2016-02-24 Time 16:37 Rev Time 0.00
Received By jgomez Date 2016-02-11 Time 10:27 Sent To  
Notes
2016-02-11 10:28:00RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-01-25 Cont ID  
Sent By jgomez Date 2016-01-25 Time 10:14 Rev Time 0.00
Received By jgomez Date 2016-01-13 Time 15:13 Sent To  
Notes
2016-01-13 15:14:09RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-11 Cont ID  
Sent By cpuell Date 2015-12-11 Time 08:09 Rev Time 0.00
Received By cpuell Date 2015-11-23 Time 12:35 Sent To  
Notes
2015-11-23 12:35:24RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-03 Cont ID  
Sent By cpuell Date 2015-11-03 Time 08:43 Rev Time 0.00
Received By cpuell Date 2015-09-29 Time 10:39 Sent To  
Notes
2015-09-29 10:39:09R11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-12-09 Cont ID  
Sent By jgomez Date 2015-12-09 Time 17:11 Rev Time 0.00
Received By jgomez Date 2015-12-09 Time 17:11 Sent To  
Notes
2015-12-09 17:13:10$180.65 PAID. MU-2015-027343.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-10-29 Cont ID  
Sent By jgomez Date 2015-10-29 Time 15:14 Rev Time 0.00
Received By jgomez Date 2015-10-29 Time 15:14 Sent To  
Notes
2015-10-29 15:16:081- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-02-24 Cont ID  
Sent By jgomez Date 2016-02-24 Time 10:53 Rev Time 0.00
Received By jgomez Date 2016-02-24 Time 10:53 Sent To  
Notes
2016-02-24 11:08:27OK TO ISSUE WITH PROVISO, PER MEETING WITH TERENCE
 SMALL (CONTRACTOR). TOLD HIM REVISION FEES WILL APPLY.
 HE SAID THEY MAY USE A BIGGER A/C UNIT FOR ENTIRE
 HOUSE.
  
 MECHANICAL REVIEW APPROVED WITH PROVISO:
  
 1- EQUIPMENT LISTED ON THIS PLAN EXCEEDS THE SIZE
 REQUIRED ON THE EQUIPMENT SIZING CALCULATIONS.
 EQUIPMENT IS NOT ALLOWED TO BE OVERSIZED. SEC.
 R403.6.1.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). REVISE EQUIPMENT AS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-01-25 Cont ID  
Sent By jgomez Date 2016-01-25 Time 10:23 Rev Time 0.00
Received By jgomez Date 2016-01-25 Time 10:14 Sent To  
Notes
2016-01-25 10:40:45RESIDENTIAL (R3) ADDITION, THIRD MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS USING
 APPROVED SOFTWARE AS REQUIRED BY SEC. R403.6.1 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT
 COMMENT).
 RESPONSE: NO INFORMATION WAS SUBMITTED.
  
 2- SHEET M-1:
 A) PROVIDE INFORMATION SHOWING COMPLIANCE WITH THE
 BALANCED RETURN AIR FOR THE MASTER BEDROOM AS REQUIRED
 BY SEC. M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE: 10" TRANSFER DUCT SIZE AS SHOWN ON A/C PLAN
 DOESN'T COMPLY. NEED 13" DUCT SIZE OR LARGER. (REPEAT
 COMMENT).
  
 B) INFORMATION ON THE CONDENSING UNIT MOUNTING DETAIL
 DOESN'T MATCH INFORMATION SHOWN ON THE FLORIDA PRODUCT
 APPROVAL FL14239-R3 SUBMITTED. REVISE AS REQUIRED TO
 MATCH. CLEARLY IDENTIFY SIZE, NUMBER AND LOCATION OF
 ANCHORS. SEE PRODUCT APPROVAL SUBMITTED. SEC. 107.2.1
 CITY AMENDMENTS. (REPEAT COMMENT. NOT ADDRESSED).
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE PUT TOGETHER TWO NEW SET OF DRAWINGS BY
 INSERTING REVISED DRAWINGS AND REMOVING OLD DRAWINGS.
 DON'T STAPLE OLD DRAWINGS TO NEW SET.. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-12-10 Cont ID  
Sent By jgomez Date 2015-12-10 Time 13:54 Rev Time 0.00
Received By jgomez Date 2015-12-10 Time 13:54 Sent To E
Notes
2015-12-10 13:54:38RESIDENTIAL (R3) ADDITION, SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
  
 ****NOTE:
 THERE ARE TWO OPTIONS TO ADDRESS COMMENTS BELOW. PERMIT
 MAY BE ISSUED WITH PROVISO OR CONTRACTOR MAY RE-SUBMIT
 INFORMATION ADDRESSING THE COMMENTS. PROVISO MEANS THAT
 CONTRACTOR WILL ADDRESS ALL THE COMMENTS AFTER THE
 PERMIT IS ISSUED. REVISION FEES WILL APPLY. CONTRACTOR
 TO ADVICE PREFERRED OPTION: PROVISO OR RE-SUBMITTAL.
  
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS USING
 APPROVED SOFTWARE AS REQUIRED BY SEC. R403.6.1 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT
 COMMENT).
 RESPONSE: COMPLETE EQUIPMENT SIZING CALCULATIONS WERE
 NOT SUBMITTED.
  
 2- SHEET M-1:
 A) PROVIDE INFORMATION SHOWING COMPLIANCE WITH THE
 BALANCED RETURN AIR FOR THE MASTER BEDROOM AS REQUIRED
 BY SEC. M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE: 10" TRANSFER DUCT SIZE AS SHOWN ON A/C PLAN
 DOESN'T COMPLY. NEED 13" DUCT SIZE OR LARGER.
  
 B) INFORMATION ON THE CONDENSING UNIT MOUNTING DETAIL
 DOESN'T MATCH INFORMATION SHOWN ON THE FLORIDA PRODUCT
 APPROVAL FL14239-R3 SUBMITTED. REVISE AS REQUIRED TO
 MATCH. CLEARLY IDENTIFY SIZE, NUMBER AND LOCATION OF
 ANCHORS. SEE PRODUCT APPROVAL SUBMITTED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE PUT TOGETHER TWO NEW SET OF DRAWINGS BY
 INSERTING REVISED DRAWINGS AND REMOVING OLD DRAWINGS.
 DON'T STAPLE OLD DRAWINGS TO NEW SET.. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-10-30 Cont ID  
Sent By jgomez Date 2015-10-30 Time 18:28 Rev Time 0.00
Received By jgomez Date 2015-10-30 Time 17:58 Sent To  
Notes
2015-10-30 18:32:52RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW COMMENTS.
 CODE: FBC, 5TH EDITION (2014).
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS USING APPROVED
 SOFTWARE AS REQUIRED BY SEC. R403.6.1 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). CALCULATIONS
 SUBMITTED ARE NOT FROM AN APPROVED SOFTWARE. SEE ACCA
 WEBSITE FOR APPROVED SOFTWARE.
  
 2- SHEET M-1:
 A) PROVIDE INFORMATION SHOWING COMPLIANCE WITH THE
 BALANCED RETURN AIR FOR THE MASTER BEDROOM AS REQUIRED
 BY SEC. M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) UPDATE CODE REFERENCED ON THE MECHANICAL NOTES.
 CURRENT CODE IS FBC- 5TH EDITION (2014).
  
 C) CONDENSING UNIT MOUNTING DETAIL SUBMITTED: PROVIDE
 ENGINEERING CALCULATIONS SHOWING THAT NUMBER AND SIZE
 OF ANCHORS SPECIFIED WILL RESIST THE CALCULATED WIND
 LOADS. AND, CLEARLY IDENTIFY LOCATION OF ANCHORS. SEC.
 107.2.1.3 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE PUT TOGETHER TWO NEW SET OF DRAWINGS BY
 INSERTING REVISED DRAWINGS AND REMOVING OLD DRAWINGS.
 DON'T STAPLE OLD DRAWINGS TO NEW SET.. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-01-25 Cont ID  
Sent By jgomez Date 2016-01-25 Time 10:46 Rev Time 0.00
Received By jgomez Date 2016-01-25 Time 10:46 Sent To  
Notes
2016-01-25 10:49:51PLUMBING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE WATER HEATER ACCESS DOOR. NEED LEVEL WORKING
 SPACE IN FRONT OF THE APPLIANCE. SEE MECHANICAL PLAN.

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-12-10 Cont ID  
Sent By jgomez Date 2015-12-10 Time 13:51 Rev Time 0.00
Received By jgomez Date 2015-12-10 Time 13:51 Sent To  
Notes
2015-12-10 13:48:34NEW DRAWINGS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-10-08 Cont ID  
Sent By tklarge Date 2015-10-08 Time 06:08 Rev Time 0.00
Received By tklarge Date 2015-10-08 Time 05:41 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2015-12-10 Cont ID  
Sent By jgomez Date 2015-12-10 Time 13:35 Rev Time 0.00
Received By jgomez Date 2015-12-10 Time 13:35 Sent To  
Notes
2015-12-10 13:36:35SHINGLES FLORIDA PRODUCT APPROVAL FL10124-R16.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-10-30 Cont ID  
Sent By jgomez Date 2015-10-30 Time 16:56 Rev Time 0.00
Received By jgomez Date 2015-10-30 Time 16:55 Sent To  
Notes
2015-10-30 16:56:431- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ASPHALT SHINGLES. FLORIDA PRODUCT APPROVAL FL9792-R4
 SUBMITTED IS FOR 2010 FBC. NEED FLORIDA PRODUCT
 APPROVAL FOR THE CURRENT CODE IN EFFECT , 2014 CODE
 VERSION
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-10-02 Cont ID  
Sent By sgraham Date 2015-10-02 Time 10:21 Rev Time  
Received By sgraham Date   Time   Sent To  
Notes
***NONE***