Plan Review Details - Permit 15091225
| Plan Review Stops For Permit 15091225 |
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
1 |
Status |
P |
Date |
2015-12-21 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2015-12-21 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2015-12-21 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2015-12-21 13:06:57 | PER SYBILLE WELTER, ART IN PUBLIC PLACES (AIPP) | | | COORDINATOR, THE DEVELOPER HAS SUBMITTED THE REQUIRED | | | ART ASSESSMENT APPLICATION INCLUDING ESCROWED FUNDS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2017-06-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2017-06-21 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2017-06-21 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2017-06-21 11:27:53 | PROJECT INFORMATION: | | | CONSTRUCTION TYPE: 14-II-A - 5TH ED TYPE II-A | | | UNITS: 1 | | | FLOORS: 4 | | | BEDROOMS: | | | ROOMS: | | | SQ FT LIVABLE: 62661 | | | SQ FT FOOTPRINT: 19159 | | | SQ FT ROOF: 19159 | | | | | | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF | | | KNOWN): NGVD29 | | | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): | | | XX.XX | | | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: | | | XX.XX | | | OCC LOAD: 1519 | | | PROP USE: RETAIL | | | SPRINKLER SYS? Y | | | SPRK REQ'D? Y | | | BATHRMS: 4 | | | | | | BLDG CODE: FL 2014 | | | OCC CLASS: 5TH ED M | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2016-01-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-01-06 |
Time |
17:52 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-12-30 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2016-01-06 18:31:24 | ****PROVISOS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | SEPARATE PERMITS REQUIRED FOR: | | | UNDERGROUND FIRE LINE | | | COURTYARD (WALLS/FOUNDATIONS, PAVILION STRUCTURES) | | | LANDSCAPE | | | IRRIGATION | | | SITE LIGHTING | | | HARDSCAPE | | | BIKE RACKS | | | DUMPSTER ENCLOSURE | | | FOUNTAINS | | | PAVING | | | SIGNAGE | | | FIRE PROTECTION | | | FIRE ALARM | | | FABRIC COVERED AWNINGS | | | | | | PRODUCT APPROVALS FOR ALL COMPONENTS AND CLADDING ARE | | | TO BE SUBMITTED PRIOR TO INSTALLATION, REVIEWED BY DOR | | | PRIOR TO SUBMITTAL. COMPONENTS AND CLADDING TO COMPLY | | | WITH THE DESIGN PRESSURES ON PAGE S102. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-11-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2015-11-18 |
Time |
17:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-11-18 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2015-11-18 17:33:23 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. **PENDING RESPONSE FROM DBPR** | | | | | | 2. ENERGY CALCS REQUIRED, FBC ENERGY CONSERVATION 103. | | | | | | 3. FBC 501.2, REVISE PLAN TO INDICATE LOCATION OF | | | ADDRESS IDENTIFICATION ON THE BUILDING. | | | | | | 4. THIRD FLOOR SQUARE FOOT AREA ON SHEET A003 IS NOT | | | CONSISTENT WITH THE SQUARE FOOT AREA ON A020, PLEASE | | | RECONCILE FBC 107. VERIFY ALL FLOORS. THIS IS TO BE | | | DONE PRIOR TO IMPACT FEE ASSESSMENT. | | | | | | 6. FBC 1007.1, ACCESSIBILITY 207.1, REVISE PLAN TO | | | STATE WHICH OPTION IS ELECTED FOR ACCESSIBLE MEANS OF | | | EGRESS. MEANS OF EGRESS SHALL COMPLY WITH SECTION | | | 1003.2.13 OF THE IBC 2000 OR SECTION 1007 OF THE IBC | | | 2003 EDITION. REVISE PLAN TO CLARIFY COMPLIANCE WITH | | | EACH REQUIREMENT OF THE OPTION ELECTED. | | | | | | 7. ADVISORY ONLY, WHEN APPLICATION IS SUBMITTED FOR | | | PARKING LOT PAVING AND STRIPING, A050 OR RELATED CIVIL | | | SHEET, REVISE PLAN TO PROVIDE THE FOLLOWING | | | INFORMATION: | | | TOTAL NUMBER OF PARKING SPACES | | | NUMBER OF ACCESSIBLE SPACES | | | | | | FBC 2014 ACCESSIBILITY 208.2 (PARKING SPACES), 502 | | | (PARKING SPACES). | | | | | | 8. PROVIDE THE VALUE OF THE ITEMS WHICH ARE TO BE ON | | | SEPARATE PERMIT AS PER CORRESPONDENCE BETWEEN STEVE | | | KENNEDY AND WAYNE CHUBB, FBC 109, FBC 107. | | | | | | AT THIS TIME, IT APPEARS THAT SEPARATE PERMITS WILL BE | | | REQUIRED FOR: | | | | | | RETRACTABLE AWNINGS (UNLESS ALL INFORMATION PROVIDED IN | | | RESUBMITTAL, SEE OTHER COMMENT) | | | FREESTANDING TRELLIS AND RETRACTABLE AWNING | | | PAVING, HARDSCAPE AND STRIPING | | | SITE LIGHTING | | | FOUNTAINS | | | LANDSCAPING | | | DUMPSTER ENCLOSURES | | | SIGNAGE (STRUCTURAL DETAIL OF SIGN CONSTRUCTION, | | | STRUCTURAL DETAIL FOR ATTACHMENT, ELECTRICAL | | | INFORMATION NOT INCLUDED IN THE PERMIT SUBMITTAL) | | | BICYCLE RACKS | | | | | | 9. ADVISORY ONLY, SITE LIGHTING IS TO BE ON SEPARATE | | | PERMIT. WHEN SUBMITTING, PROVIDE ENGINEERING FOR THE | | | SITE LIGHTING AND SITE LIGHTING FIXTURES, FBC 107. THIS | | | INFORMATION WAS NOT INCLUDED IN THE SUBMITTAL PACKAGE. | | | | | | 10. FBC 2014 ACCESSIBILITY 404.2.4.1, SHOW MANEUVERING | | | CLEARANCE, PULL SIDE (18IN MIN) FOR THE FOLLOWING | | | DOORS: | | | LEVEL 1 WOMENS AND MENS WC, SHEET A120, A101 | | | LEVEL 3 DOORS 340.1, 340.2 | | | | | | 10. SHEET A120 SPECS AMERICAN STANDARD CADET 3. FBC | | | 2014 ACCESSIBILITY 604.4, SEAT HEIGHT TO BE 17 IN | | | MINIMUM AND 19 IN MAXIMUM. IT IS NOT CLEAR WHICH CADET | | | 3 MODEL IS PROPOSED, BUT SEAT HEIGHTS ON THE | | | MANUFACTURER WEBSITE WERE15IN AND 16.5 IN (TWO | | | DIFFERENT MODELS CHECKED). REVISE PLAN TO SHOW SEAT | | | HEIGHT OR SEAT HEIGHT RANGE AND CLARIFY CADET 3 MODEL | | | PROPOSED (OR REMOVE MODEL SPEC). | | | | | | 11. SHEET A120, SPECIFY DRINKING FOUNTAIN HEIGHTS OR | | | HEIGHT RANGES, FBC 2014 ACCESSIBILITY 602.4, 602.7. | | | | | | 12. PLANS SHOW THE RETRACTABLE AWNING AS "BY OWNER." IF | | | AWNINGS ARE TO BE INCLUDED IN THIS PERMIT, PROVIDE | | | STRUCTURAL DETAILS FOR THE RETRACTABLE AWNINGS, FBC | | | 107, INCLUDING WIND DESIGN CRITERIA FBC 1609, FASTENING | | | INFORMATION, FABRIC INFORMATION TO SHOW COMPLIANCE WITH | | | FBC 3105. IF ALL REQUIRED INFORMATION IS NOT PROVIDED, | | | A SEPARATE PERMIT FOR THE AWNINGS WILL BE REQUIRED. IT | | | IS NOT CLEAR WHETHER THIS IS TO MEET THE SAME WIND | | | REQUIREMENTS OF THE BUILDING, OR IF IT IS A RISK | | | CATEGORY 1, OR DESIGNED USING FBC3105.4. | | | | | | 13. DUE TO PARKING CONFIGURATION, IT APPEARS THAT VALET | | | PARKING WILL BE AVAILABLE. SEE FBC 503.3.2 AND .3; | | | PLEASE REVISE PLAN TO INDICATE PULL UP SPACE AND ACCESS | | | AISLE MARKING. | | | | | | 14. PROVIDE STRUCTURAL DETAILS FOR THE STATIONARY | | | AWNINGS, FBC 107, INCLUDING WIND DESIGN CRITERIA FBC | | | 1609, IF THEY ARE TO BE INCLUDED IN THIS PERMIT RATHER | | | THAN BEING INCLUDED ON A SEPARATE PERMIT. | | | | | | 15. A428 AND OTHER LOCATIONS, PLYWOOD SHEATHING SHOWN; | | | REVISE TO SPECIFY FRT OR INCLUDE APPLICABLE EXCEPTION | | | FBC TABLE 602. | | | | | | 16. S421, REVISE PLAN TO INCLUDE PAGE NUMBER FOR THE | | | "CMU REINF SCHED" REFERRED TO IN DETAIL 19, FBC 107. | | | | | | 17. S421, VERTICAL STEEL REQUIRED IS NOT CLEAR, DETAIL | | | 20. TWO ARROWS ARE SHOWN BUT NOT SPECIFIED, TEXT STATES | | | "#4 @ 16IN", DOES THIS MEAN TWO #4 AT 16IN OC? FBC 107. | | | | | | 18. S002, RCSC REFERENCE NOT CONSISTENT WITH THE FBC | | | 2014. REVISE AND CHECK ALL STANDARDS; SEE FBC CHAPTER | | | 35. IF DESIGNER WOULD LIKE TO PROPOSE AN ALTERNATE, | | | THIS MUST BE REQUESTED USING ALTERNATIVE MATERIALS AND | | | METHODS FBC 104.11. CONTACT ME VIA EMAIL FOR FURTHER | | | INFORMATION IF THIS IS DESIGNER'S INTENT. | | | | | | 19. PROVISO: ADVISORY ONLY, PRODUCT APPROVALS FOR ALL | | | COMPONENTS AND CLADDING ARE TO BE SUBMITTED PRIOR TO | | | INSTALLATION, REVIEWED BY DOR PRIOR TO SUBMITTAL. | | | COMPONENTS AND CLADDING TO COMPLY WITH THE PRESSURE ON | | | PAGE S102. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-01-20 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-01-20 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2016-01-20 |
Time |
12:30 |
Sent To |
|
|
| Notes |
| 2016-01-20 16:27:22 | ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN | | | SATISFACTORILY ADDRESSED. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-11-23 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-11-23 |
Time |
18:41 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-11-19 |
Time |
18:04 |
Sent To |
|
|
| Notes |
| 2015-11-23 18:42:58 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION | | | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF | | | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, | | | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST | | | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF | | | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. | | | PG. E050 | | | 1. UNLESS PRIOR ARRANGEMENTS ARE MADE WITH ELECTRICAL | | | INSPECTOR, ALL TRENCHING SHALL REMAIN OPEN FOR | | | INSPECTIONS. NO SITE TUBES WILL BE ACCEPTED. | | | 2. ALL SITE LIGHTING SHALL BE UNDER SEPARATE PERMIT. | | | PG. E201; E202; E203; E204 | | | 1. NEC 314.27(B), BOXES SPECIFICALLY LISTED FOR THE | | | APPLICATION SHALL BE USED FOR ALL FLOOR OUTLETS. | | | 2. NEC 406.9(B), ALL 15 & 20 AMP 125 AND 250 VOLT | | | NONLOCKING RECEPTACLES INSTALLED IN WET LOCATIONS SHALL | | | BE LISTED WEATHER RESISTANT. | | | 3. NEC 600.5, EVERY COMMERCIAL ESTABLISHMENT SHALL HAVE | | | IN AN ACCESSIBLE LOCATION AT EACH ENTRY ACCESSIBLE TO | | | PEDESTRIANS AT LEAST ONE OUTLET FOR SIGNAGE. | | | 4. NEC 210.62, THERE SHALL BE A SHOW WINDOW OUTLET FOR | | | EVERY 12 FT. OF SHOW WINDOW OR MAJOR PORTION THEREOF OF | | | SHOW WINDOW MEASURED HORIZONTALLY. THIS MAY NOT APPLY | | | TO EVERY SPACE AS ALL MAY NOT HAVE SHOW WINDOWS. | | | 5. NEC 300.21, OPENINGS INTO OR THROUGH FIRE RATED | | | WALLS, PARTITIONS, FLOORS OR CEILINGS SHALL BE | | | FIRESTOPPED USING APPROVED METHODS TO MAINTAIN FIRE | | | RESISTANCE RATING. | | | 6. ALL ENLARGED AREA WILL BE REVIEWED AND COMMENTED | | | UPON AT THEIR RESPECTIVE PAGES/VIEWS. | | | PG. E301; E302; E303; E304 | | | 1. NEC 700.12, THE LIGHTING CIRCUIT FEEDING EMERGENCY | | | AND EXIT LIGHTS SHALL BE THE CIRCUIT AS FOR THE AREA | | | THEY OCCUPY UNLESS THERE ARE THREE OR MORE LIGHTING | | | CIRCUITS FOR THAT AREA. | | | 2. SEE NOTES 3 & 4 ABOVE WITH REGARDS TO SIGN AND SHOW | | | WINDOW OUTLETS. | | | 3. LAYERS DO NOT APPEAR TO BE PROPERLY ALIGNED NOR ARE | | | WALLS CLEARLY IDENTIFIED TO ASCERTAIN EXIT LIGHT | | | REQUIREMENTS. | | | 4. FBC-E C402.4.8, ALL RECESSED LUMINAIRES INSTALLED IN | | | THE BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND | | | SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND | | | UNCONDITIONED AIR SPACES. | | | PG. E402 | | | 1. NEC 210.8(B)(2), THIRD LEVEL PREP KITCHEN AREA 340, | | | ALL 15 VOLT, 15 ? 20 AMP SINGLE PHASE OUTLETS IN | | | KITCHENS SHALL HAVE GFCI PROTECTION FOR PERSONNEL. | | | 2. NEC 210.8 (B)(5), SECOND LEVEL BREAKROOM 231, | | | RECEPTACLES INSTALLED WITHIN 6 FT OF THE OUTSIDE EDGE | | | OF A SINK SHALL HAVE GFCI PROTECTION FOR PERSONNEL. | | | PG. E702 | | | 1. FBC-E C402.4.8, ALL RECESSED LUMINAIRES INSTALLED IN | | | THE BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND | | | SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND | | | UNCONDITIONED AIR SPACES. | | | PG. E1101, E1102 | | | 1. NEC 760.41(B) FIRE ALARM CIRCUITS DISCONNECTING | | | MEANS SHALL HAVE A RED IDENTIFICATION, SHALL BE | | | ACCESSIBLE ONLY TO QUALIFIED PERSONNEL AND SHALL BE | | | IDENTIFIED AS ?FIRE ALARM CIRCUIT.? | | | | | | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE | | | MENTIONED DEFICIENCIES. | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE | | | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE | | | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD | | | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE | | | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. | | | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2015-12-08 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
2015-12-08 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
2015-12-08 |
Time |
14:36 |
Sent To |
|
|
| Notes |
| 2015-12-08 14:38:06 | ALSO REVIEWED UNDER E15080032 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2016-01-12 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-01-12 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-01-12 |
Time |
13:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2015-10-27 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-10-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-10-16 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2015-10-22 16:33:20 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1. SHEET 007 A.020, THE EXIT PATH FROM THE WEST DOORS | | | LEADING THROUGH THE COURTYARD, APPEARS TOO NARROW | | | INBETWEEN FOR THE OCCUPANCY LOAD. NO DIMENSIONS ARE | | | INDICATED FOR THE WIDTH BETWEEN THE WATER FOUNTAINS AND | | | LANDSCAPE. | | | | | | 2. SHEET A.605, INDICATES A DOOR SCHEDULE; HOWEVER, A | | | COLUMN IN THE TABLE REFERENCES A HARDWARE PACKAGE. I | | | HAVE BEEN UNABLE TO IDENTIFY THE SHEETINDICATING THE | | | HARDWARE PACKAGE INFORMATION. | | | | | | 3. SHEET A-101, INDICATES DOORS 151.1, 152.1 & 132.1, | | | 132.2 THAT OPEN UP INTO THE EXIT ACCESS WAY. PER NFPA | | | 101 CHAPTER 7, MEANS OF EGRESS | | | 7.2.1.4.3 DOOR LEAF ENCROACHMENT | | | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS | | | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE | | | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, | | | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT | | | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A | | | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, | | | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: | | | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN | | | EXISTING BUILDING. | | | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS | | | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED | | | WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY | | | OPEN. | | | | | | PLEASE PROVIDE FOR COMPLIANCE WITH THE CODE. | | | | | | 4. SHEET A-107, F3, INDICATES A 2 PEDESTRIAN SWING | | | GATES. THERE IS NO INDICATION OF ANY LATCHING OR EXIT | | | HARDWARE. PER NFPA 101 SECTION 7.2.1.5 THE LOCK/LATCH | | | RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE DOOR | | | WITH NOT MORE THAN ONE RELEASING OPERATION. THE | | | RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF | | | OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING | | | CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF | | | BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE | | | TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST | | | TO OPERATE. | | | | | | PLEASE PROVIDE FOR COMPLAINCE WITH THE CODE AND FOR | | | PANIC HARDWARE PER NFPA 101 7.2.1.7. | | | | | | 5. FIRE FIGHTER?S EMERGENCY OPERATIONS. | | | NFPA 101 9.4.3.1 ALL NEW ELEVATORS SHALL CONFORM TO THE | | | FIRE FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF | | | ASME A17.1/CSA B44, SAFETY CODE FOR ELEVATORS. | | | | | | PLEASE PROVIDE FOR COMPIANCE WITH THE CODE. | | | | | | 6. PLEASE PROVIDE DOCUMENTATION THAT THIS BUILDING DOES | | | NOT MEET THE REQUIRERMENTS OF A HIGH RISE AND THE | | | REQUIREMENTS PROVISIONS OF NFPA 11.8. | | | | | | 7. BASED ON REVIERW OF THE ABOVE ADDITIONAL | | | REQUIREMENTS MAY BE PROVIDED | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-02-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-02-18 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-02-08 |
Time |
09:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-02-03 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2016-02-03 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2015-12-22 |
Time |
14:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-12-08 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2015-12-08 |
Time |
15:08 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2015-10-06 |
Time |
13:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2016-01-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-01-11 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-01-11 |
Time |
12:10 |
Sent To |
|
|
| Notes |
| 2016-01-11 12:20:19 | MU-2015-019031-0000 | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2015-11-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2015-11-18 |
Time |
15:55 |
Rev Time |
|
| Received By |
shill |
Date |
2015-11-09 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2015-11-09 15:07:34 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED; | | | 561-233-5025 FOR MORE INFORMATION. | | | | | | THE SQUARE FOOT AREA ON THE PLAN SUBMITTED FOR IMPACT | | | FEES FOR THE FOUNDATION PERMIT DIFFERS FROM THE ISSUED | | | FOUNDATION PERMIT. IMPACT FEES ARE TO BE RE-ASSESSED ON | | | THE NEW SQUARE FOOT AREA. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2016-02-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-02-18 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-02-18 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2016-02-18 11:18:26 | MECHANICAL PROVISOS: | | | PERMIT #15091225 | | | 2/18/16 | | | | | | 1 ) C408.2 FBC-14 ENERGY CONSERVATION: MECHANICAL | | | SYSTEMS COMMISSIONING AND COMPLETION REQUIREMENTS. | | | PRIOR TO PASSING THE FINAL MECHANICAL INSPECTION, THE | | | REGISTERED DESIGN PROFESSIONAL SHALL PROVIDE EVIDENCE | | | OF MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION IN | | | ACCORDANCE THE PROVISIONS OF THIS SECTION. | | | CONSTRUCTION DOCUMENT NOTES SHALL CLEARLY INDICATE | | | PROVISIONS FOR COMMISSIONING AND COMPLETION | | | REQUIREMENTS IN ACCORDANCE WITH THIS SECTION AND ARE | | | PERMITTED TO REFER TO SPECIFICATIONS FOR FURTHER | | | REQUIREMENTS. COPIES OF ALL DOCUMENTATION SHALL BE | | | GIVEN TO THE OWNER AND MADE AVAILABLE TO THE CODE | | | OFFICIAL UPON REQUEST IN ACCORDANCE WITH SECTIONS | | | C408.2.4 AND C408.2.5. | | | A) C408.2.1 COMMISSIONING PLAN. | | | A COMMISSIONING PLAN SHALL BE DEVELOPED BY A REGISTERED | | | DESIGN PROFESSIONAL OR APPROVED AGENCY AND SHALL | | | INCLUDE THE FOLLOWING ITEMS: | | | 1. A NARRATIVE DESCRIPTION OF THE ACTIVITIES THAT WILL | | | BE ACCOMPLISHED DURING EACH PHASE OF COMMISSIONING, | | | INCLUDING THE PERSONNEL INTENDED TO ACCOMPLISH EACH OF | | | THE ACTIVITIES. | | | 2. A LISTING OF THE SPECIFIC EQUIPMENT, APPLIANCES OR | | | SYSTEMS TO BE TESTED AND A DESCRIPTION OF THE TESTS TO | | | BE PERFORMED. | | | 3. FUNCTIONS TO BE TESTED, INCLUDING, BUT NOT LIMITED | | | TO CALIBRATIONS AND ECONOMIZER CONTROLS. | | | 4. CONDITIONS UNDER WHICH THE TEST WILL BE PERFORMED. | | | AT A MINIMUM, TESTING SHALL AFFIRM WINTER AND SUMMER | | | DESIGN CONDITIONS AND FULL OUTSIDE AIR CONDITIONS. | | | 5. MEASURABLE CRITERIA FOR PERFORMANCE. | | | | | | B) C408.2.2 AIR DISTRIBUTION SYSTEM TESTING, ADJUSTING | | | AND BALANCING. | | | CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT A WRITTEN | | | BALANCE REPORT BE PROVIDED TO THE OWNER OR THE | | | DESIGNATED REPRESENTATIVE OF THE BUILDING OWNER FOR | | | HVAC SYSTEMS SERVING ZONES WITH A TOTAL CONDITIONED | | | AREA EXCEEDING 5000 SQUARE FEET (465 M2). AIR | | | DISTRIBUTION SYSTEMS SHALL BE TESTED, ADJUSTED, AND | | | BALANCED BY A LICENSED ENGINEER OR A COMPANY OR | | | INDIVIDUAL HOLDING A CURRENT CERTIFICATION FROM A | | | RECOGNIZED TESTING AND BALANCING AGENCY ORGANIZATION IN | | | ACCORDANCE WITH GENERALLY ACCEPTED ENGINEERING | | | STANDARDS. | | | | | | C) C408.2.4 PRELIMINARY COMMISSIONING REPORT. | | | A PRELIMINARY REPORT OF COMMISSIONING TEST PROCEDURES | | | AND RESULTS SHALL BE COMPLETED AND CERTIFIED BY THE | | | REGISTERED DESIGN PROFESSIONAL OR APPROVED AGENCY AND | | | PROVIDED TO THE BUILDING OWNER. THE REPORT SHALL BE | | | IDENTIFIED AS ?PRELIMINARY COMMISSIONING REPORT? AND | | | SHALL IDENTIFY: | | | 1. ITEMIZATION OF DEFICIENCIES FOUND DURING TESTING | | | REQUIRED BY THIS SECTION THAT HAVE NOT BEEN CORRECTED | | | AT THE TIME OF REPORT PREPARATION. | | | 2. DEFERRED TESTS THAT CANNOT BE PERFORMED AT THE TIME | | | OF REPORT PREPARATION BECAUSE OF CLIMATIC CONDITIONS. | | | 3. CLIMATIC CONDITIONS REQUIRED FOR PERFORMANCE OF THE | | | DEFERRED TESTS. | | | | | | D) C408.2.4.1 ACCEPTANCE OF REPORT. | | | BUILDINGS, OR PORTIONS THEREOF, SHALL NOT PASS THE | | | FINAL MECHANICAL INSPECTION UNTIL SUCH TIME AS THE CODE | | | OFFICIAL HAS RECEIVED A LETTER OF TRANSMITTAL FROM THE | | | BUILDING OWNER ACKNOWLEDGING THAT THE BUILDING OWNER | | | HAS RECEIVED THE PRELIMINARY COMMISSIONING REPORT. | | | | | | E) C408.2.4.2 COPY OF REPORT. | | | THE CODE OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A | | | COPY OF THE PRELIMINARY COMMISSIONING REPORT BE MADE | | | AVAILABLE FOR REVIEW BY THE CODE OFFICIAL. | | | | | | F) C408.2.5.4 FINAL COMMISSIONING REPORT. | | | A REPORT OF TEST PROCEDURES AND RESULTS IDENTIFIED AS | | | "FINAL COMMISSIONING REPORT" SHALL BE DELIVERED TO THE | | | BUILDING OWNER AND SHALL INCLUDE: | | | 1. RESULTS OF FUNCTIONAL PERFORMANCE TESTS. | | | 2. DISPOSITION OF DEFICIENCIES FOUND DURING TESTING, | | | INCLUDING DETAILS OF CORRECTIVE MEASURES USED OR | | | PROPOSED. | | | 3. FUNCTIONAL PERFORMANCE TEST PROCEDURES USED DURING | | | THE COMMISSIONING PROCESS INCLUDING MEASURABLE CRITERIA | | | FOR TEST ACCEPTANCE, PROVIDED HEREIN FOR REPEATABILITY. | | | EXCEPTION: DEFERRED TESTS WHICH CANNOT BE PERFORMED AT | | | THE TIME OF REPORT PREPARATION DUE TO CLIMATIC | | | CONDITIONS. | | | | | | 2) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS. | | | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS | | | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE | | | NOT SUBMITTED AT THE TIME OF THE | | | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE | | | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL | | | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF | | | THE BUILDING OFFICIAL. THE REGISTERED DESIGN | | | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE | | | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR | | | REVIEW BY THE BUILDING OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | A) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT | | | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE | | | DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | 3) FINAL APPROVAL OF THE ALTERNATE METHOD OF | | | CONSTRUCTION OF THE ACCESS PANELS FOR ABOVE CEILING AC | | | EQUIPMENT MECHANICAL IS CONTINGENT ON A LETTER OF | | | ACKNOWLEDGEMENT FROM THE RESTORATION HARDWARE FACILITY | | | MANAGER, AND YOU ALSO INCLUDE THE DISASSEMBLY PROCEDURE | | | INSTRUCTIONS IN THE O & M MANUAL THAT THE | | | CONTRACTOR/DESIGN TEAM WILL PROVIDED TO RESTORATION | | | HARDWARE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2016-02-03 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-02-03 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-02-03 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2016-02-03 15:49:22 | 3RD REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15091225 | | | 2/3/15 | | | | | | 1) THE ENGINEER AND ARCHITECT FAILED TO PROVIDE | | | ACCURATELY CORRECTED PLANS FOR THE PROJECT UNDER THEIR | | | REQUEST FOR A MID-CYCLE REVIEW. PLEASE NOTE THAT | | | NUMEROUS PHONE CALLS AND EMAILS WERE SENT TO ME FROM | | | THE DESIGN PROFESSIONALS AND EVERY ATTEMPT WAS MADE BY | | | MYSELF TO BRING THE PROJECT INTO COMPLIANCE. AT THIS | | | TIME THEY ARE REQUESTING THAT I CLOSE THE 3RD REVIEW | | | STOP IN ORDER TO NOW UPLOAD THE CORRECTED AND REVISED | | | PLAN SHEETS INTO PROJECT DOX. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2015-12-31 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-12-31 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-12-30 |
Time |
14:46 |
Sent To |
|
|
| Notes |
| 2015-12-31 15:22:12 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15091225 | | | 12/31/15 | | | | | | 1) ENERGY CALCULATION FORM 506-2014 HAS BEEN SUBMITTED, | | | HOWEVER IT APPEARS THAT THE EFFICIENCY RATING CRITERA | | | USED FOR THE HEAT PUMPS DOES NOT MATCH THE CRITERIA | | | SPECIFIED IN TABLE C403.2.3(11) FBC-14 ENERGY | | | CONSERVATION.PLEASE REVIEW AND CORRECT THE DOCUMENT. | | | 2) AC COOLING AND HEATING LOAD CALCULATIONS HAVE BEEN | | | SUBMITTED, HOWEVER IT APPEARS THAT THE SYSTEM | | | SELECTIONS ON THE PLANS ARE SOMEWHAT OVERSIZED IN | | | CAPACITY WHEN COMPARED WITH THE CALCULATIONS. MOST | | | NOTABLE ARE HP-2 AND HP-7 EACH HAVING A CALCULATED | | | COOLING CAPACITY OF 18.7 TONS, BUT A SYSTEM SELECTION | | | AT 24 TONS (SEE SCHEDULE ON M-401, MODULE 1 & 2 DAIKIN | | | RXYQ144-12 TONS EACH). REFER TO SECTION C403.2.2 AND | | | INDICATE COMPLIANCE. PLEASE NOTE THAT HP-8 MODULE 1 | | | DAIKIN RXYQ120 APPEARS TO BE MISLABELED AT 16 TONS IN | | | THE SCHEDULE. | | | 3) IN REFERENCE TO THE ARCHITECT'S RESPONSES TO 1ST | | | REVIEW COMMENTS #2, 3, 4, 5, & 6, PLEASE REVIEW THE | | | FOLLOWING REQUIREMENTS FOR DEFERRED SUBMITTALS. | | | DEFERRED SUBMITTALS: | | | A) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS. | | | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS | | | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE | | | NOT SUBMITTED AT THE TIME OF THE | | | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE | | | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL | | | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF | | | THE BUILDING OFFICIAL. THE REGISTERED DESIGN | | | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE | | | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR | | | REVIEW BY THE BUILDING OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | B) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT | | | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE | | | DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | 4) THE ARCHITECT'S RESPONSE TO COMMENT #5 INDICATES THE | | | CONDENSING UNITS WILL BE "POSTED UP ABOVE THE ROOF ON | | | DUNNAGE GREATER THAN 8" WHICH IS ACCEPTABLE". PLEASE | | | SEE TABLE 1522.3 FBC-14 BUILDING WHICH DETERMINES ROOF | | | MOUNTED EQUIPMENT HEIGHTS REQUIREMENTS. THE WIDTH OF | | | THE DAIKIN UNITS WILL DETERMINE THEIR INDIVIDUAL LEG | | | MOUNTING HEIGHTS WHICH SHALL BE BETWEEN 14- 48 INCHES | | | ABOVE THE FINISHED ROOF PER THE TABLE. | | | 5) IN LIEU OF A SEPARATE PERMIT FOR THE KITCHEN EXHAUST | | | (AS INDICATED IN THE ARCHITECT'S RESPONSE TO 1ST REVIEW | | | COMMENT #5), PLEASE SUBMIT MANUFACTURER'S | | | SPECIFICATIONS FOR THE HOOD SYSTEM, INDICATE HOW | | | MAKE-UP AIR WILL BE PROVIDED, AND PROVIDE A | | | CALCULATION. | | | 6) COMMENT #3 FROM THE 1ST REVIEW WILL STAND PENDING | | | ACCEPTANCE BY THE BUILDING OFFICIAL OF AN ALTERNATIVE | | | METHOD FOR ACCESS AND SERVICE PANEL INSTALLATIONS FOR | | | THE VRV UNITS ABOVE THE CEILINGS. UPON ACCEPTANCE THE | | | PLANS SHALL BE REVISED TO SHOW THE LOCATIONS AND | | | DIMENSIONS OF THE ALTERNATE ACCESS PANELS. | | | 7) PLEASE NOTE THAT THE REQUESTED AC LOAD CALCULATIONS | | | AND PRELIMINARY COMMISSIONING REPORT WERE NOT UPLOADED | | | INTO PROJECT DOCS AT THE TIME OF THIS REVIEW, HOWEVER | | | THEY WERE EMAILED TO MY COMPUTER AFTER I CALLED THE | | | ARCHITECT'S OFFICE. THE DOCUMENTS MUST BE UPLOADED FOR | | | FINAL MECHANICAL APPROVAL OF THE PLANS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-11-03 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-11-03 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-11-03 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2015-11-03 08:48:42 | 1ST REVIEW: FBC 2014 MECHANICAL, FBC 2014 ENERGY | | | CONSERVATION | | | PERMIT #15091225 | | | 11/3/15 | | | | | | 1) SHEET A-003: PLEASE ADD THE 2014 (FIFTH EDITION) | | | FLORIDA BUILDING CODE- ENERGY CONSERVATION TO THE LIST | | | OF APPLICABLE CODES. REFER TO THE FOLLOWING SECTIONS OF | | | THE CODE CALLED OUT BELOW AND SHOW COMPLIANCE: | | | A ) PROVIDE AC COOLING AND HEATING CALCULATIONS IN | | | ACCORDANCE WITH SECTION C403.2.1 FBC-14 ENERGY | | | CONSERVATION- CALCULATION OF HEATING AND COOLING LOADS. | | | DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE | | | PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR | | | ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE | | | COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT | | | WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE | | | MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE | | | SIZING CALCULATION SHALL BE SUBMITTED WITH THE | | | APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND | | | COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD | | | REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY | | | SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE | | | WITH THE ASHRAE HVAC SYSTEMS AND EQUIPMENT HANDBOOK. | | | ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN | | | APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE | | | DESIGN PARAMETERS SPECIFIED IN CHAPTER 3. | | | B) PROVIDE ENERGY CALCULATIONS IN ACORDANCE WITH | | | SECTION C101.2 AND C101.5. | | | C) REFER TO SECTION C408 SYSTEM COMMISSIONING INCLUSIVE | | | OF ALL SUB-SECTIONS AND SUBMIT A COMMISSIONING PLAN. | | | PLEASE NOTE THAT PRELIMINARY AND FINAL REPORTS ON THE | | | SYSTEMS SHALL BE PROVIDED PER SECTIONS C408.2.4 AND | | | C408.2.5.4. | | | 2) SHEET M101: A) PROVIDE FSD SYMBOLS WHERE THE DUCTS | | | ARE PENETRATING THE RATED SHAFT BY THE TOILET ROOMS. B) | | | SHOW THE EXACT LOCATIONS OF THE FIRE-RATED ACCESS DOORS | | | AT BOTH OF THE RATED SHAFTS, PROVIDE INSTALLATION | | | DETAILS, AND A SUBMITTAL FOR THE DOOR REVIEWED AND | | | APPROVED BY THE DESIGN PROFESSIONAL OF RECORD. C) | | | PLEASE PLACE NOTE #7 AT ALL SHAFT DAMPER LOCATIONS: THE | | | NOTE IS MSSING IN SEVERAL PLACES. | | | 3) M101, M102, M103, & M104: REFER TO SECTION 306.1 | | | ACCESS AND SERVICE SPACE: PROVIDE THE DIMENSIONS OF THE | | | VRV ACCESS PANELS AND PROVIDE SECTION CUTS OF THE | | | PANELS AND INSTALLATION DETAILS. PLEASE NOTE THAT THE | | | CLEAR OPENING DIMENSIONS OF THE PANELS SHALL BE LARGE | | | ENOUGH TO REPLACE THE UNITS WITHOUT REMOVING PERMANENT | | | CONSTRUCTION. | | | 4) M300: PROVIDE INSTALLATION AND SUPPORT DETAILS FOR | | | THE VRV'S AND EXHAUST FANS, AND DUCT HANGING AND | | | CONNECTION DETAILS IN COMPLIANCE WITH THE CURRENT | | | SMACNA STANDARDS. | | | 5) MP100, M300: SITE SPECIFIC WIND LOAD ENGINEERING IS | | | REQUIRED FOR INSTALLATION OF THE ROOFTOP HP CONDENSERS, | | | THE ERV, THE EXHAUST AND UPBLAST FANS, AND THE GRAVITY | | | VENTILATIOR- REFER TO SECTION 301.15 FBC-14 MECHANICAL. | | | PLEASE NOTE THAT IN ACCORDANCE WITH THIS SECTION, AND | | | SECTIONS 237433 AND 238126 OF THE PROJECT MANUAL, THE | | | ERV AND HP CONDENSERS MUST ALSO BE CERTIFIED FOR WIND | | | RESISTANCE. PROVIDE THE WIND LOAD DESIGN CRITERIA AND | | | DESIGN PRESSURES ON THE PLAN, AND COMPLETE DETAILS FOR | | | ATTACHING THE VARIOUS CURBS, STANDS AND SUPPORTS TO THE | | | STRUCTURE, AND MOUNTING THE APPLIANCES AND EQUIPMENT TO | | | THE SUPPORTS. ALL SUBMITTALS PERTAINING TO THE | | | INSTALLATIONS INCLUDING MIAMI-DADE NOA'S, FL, PRODUCT | | | APPROVALS, MANUFACTURER'S SPECIFICATIONS ETC. SHALL BE | | | REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL OF | | | RECORD. PROVIDE SECTION CUTS ON THE PLAN THAT INDICATE | | | THE HEIGHTS OF THE AC EQUIPMENT ABOVE THE FINISHED | | | SURFACES OF THE ROOF- REFER TO TABLE 1522.3 FBC-14 | | | BUILDING. SEE ALSO SECTION 1522.3.4 FOR ELECTRICAL | | | CONDUITS AND MECHANICAL PIPING MOUNTED ON ROOF DECKS | | | AND PROVIDE DETAILS. | | | 6) PROVIDE A SUBMITTAL PACKAGE REVIEWED AND APPROVED BY | | | THE DESIGN PROFESSIONAL OF RECORD THAT INCLUDES THE AC | | | EQUIPMENT, THE FIRE/SMOKE DAMPERS, THE DUCT SMOKE | | | DETECTORS, THE FANS, THE LOUVERS, THE ACCESS DOORS, THE | | | MOD'S, REFRIGERANT AND CONDENSATE PIPING INSULATIONS | | | (INSULATIONS SHALL BE PLENUM-RATED) ETC. PLEASE NOTE | | | MIAMI-DADE NOA'S AND/OR FL. PRODUCT APPROVALS ARE | | | REQUIRED FOR ALL EXTERIOR COMPONENTS SUCH AS THE | | | EXHAUST FANS AND LOUVERS | | | 7) PROVIDE UL TESTED AND APPROVED FIRESTOPPING SYSTEMS | | | COPIED ONTO THE PLANS FOR ALL PIPES, DUCTS, CONDUITS | | | ETC. PENETRATING FIRE-RATED WALLS AND FLOOR/CEILING | | | ASSEMBLIES. | | | 8) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR | | | KITCHEN HOOD AND EXHAUST SYSTEMS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2016-02-11 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-02-11 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-02-10 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2016-02-11 15:28:53 | FOUNTAINS ARE NOT APPROVED UNDER THIS PERMIT. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2016-01-23 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-01-23 |
Time |
07:47 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-01-23 |
Time |
06:35 |
Sent To |
|
|
| Notes |
| 2016-01-23 07:39:42 | 1) SHT. A102 - SHOW THE REQUIRED CLEAR FLOOR SPACE FOR | | | THE BREAK ROOM SINK ON THE 2ND LEVEL ON THE PLANS PER | | | THE 2014 FBC-ACCESS. SEC. 606.2.IS THE SINK DESIGNED | | | FOR A FORWARD OR PARALLEL APPROACH? IF FOR A PARALLEL | | | APPROACH, IT APPEARS AS THOUGH THE REFRIGERATOR MAY | | | INTERFERE WITH ACCESS TO THE FAUCET CONTROLS BY SOMEONE | | | IN A WHEELCHAIR. CLARIFY. | | | 2) SHT. 120 DETAIL D/3 - THE SHOWER CONTROLS SHALL BE | | | LOCATED A MAXIMUM OF 27 INCHES FROM THE SIDE WALL | | | BEHIND THE SEAT PER THE 2014 FBC-ACCESS. SEC.608.5.3. | | | SHOW THIS ON THE DETAIL. | | | 3) SHT. P300 - DETAIL #13 - DOWNSPOUTS FOR ROOF | | | DRAINAGE SHALL DISCHARGE A MINIMUM OF ONE FOOT FROM THE | | | BUILDING WALL PER THE 2014 FBC SEC. 1503.7. | | | 4) SHT. P201 - SUBMIT NOTES FOR NUMBERS 1-4 SURROUNDED | | | BY A HEXAGON. WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2016-01-05 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-01-05 |
Time |
12:04 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-01-05 |
Time |
12:04 |
Sent To |
|
|
| Notes |
| 2016-01-05 12:09:48 | 2ND REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1.SHEET P201 + P100 HORIZONTAL DRY VENTS ARE NOT | | | PERMITTED PER FBC PL SEC 905.3 + 905.4 | | | DRY VENTS SHALL CONNECT TO HORIZONTAL DRAIN ABOVE THE | | | CENTER LINE AT A 45 DEGREE ANGLE OR GREATER AND MUST | | | RUN VERTICALLY TO 6IN ABOVE FLOOD LEVEL RIM OF HIGHEST | | | FIXTURE. | | | (A) THE MOP SINK IN ROOM 132 SHOWS A HORIZONTAL DRY | | | VENT. | | | (B) THE STAND PIPE FOR THE ELEVATOR SUMP PIT DRAIN | | | SHOWS A DRY VENT. | | | (C)THE FLOOR DRAIN AND STAND PIPE FOR SPRINKLER DRAIN | | | IN ROOM 151 SHOWS A DRY VENT. | | | | | | 2. SHEET P201 + P100 HORIZONTAL DRY VENTS ARE NOT | | | PERMITTED PER FBC PL SEC 905.3 + 905.4 | | | DRY VENTS SHALL CONNECT TO HORIZONTAL DRAIN ABOVE THE | | | CENTER LINE AT A 45 DEGREE ANGLE OR GREATER AND MUST | | | RUN VERTICALLY TO 6IN ABOVE FLOOD LEVEL RIM OF HIGHEST | | | FIXTURE. | | | (A)THE MOP SINK AND FLOOR SINK IN PREP KIT ROOM 340 | | | SHOWS A DRY VENT. | | | | | | 3. SHEET P201 THE 3IN + 2IN VENTS FROM 3RD FL ABOVE | | | PREP KIT AREA MUST TIE INTO VENT ABOVE FLOOD LEVEL RIM | | | OF FIXTURES ON 4TH FLOOR IT IS SHOWING BEING TIED INTO | | | HORIZONTAL DRAIN BELOW 3RD FLOOR. PER FBC PL SEC 905.4 | | | | | | 4. PLEASE PROVIDE SPECS FOR DOMESTIC PUMP THAT SHOWS | | | THE SPECIFIC STANDARDS THAT THE PUMP MEETS THE SPECS | | | THAT ARE PROVIDED DO NOT SHOW SPECIFIC STANDARDS ONLY | | | GENERIC ONES. PER WPB AMEND TO FBC SEC107.2.1 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2015-10-19 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2015-10-19 |
Time |
06:48 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2015-10-19 |
Time |
06:48 |
Sent To |
|
|
| Notes |
| 2015-10-19 09:19:55 | | | | | | | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1.WATER CLOSET SHALL COMPLY WITH FBC ACC. SEC 604.2 | | | LOCATION. | | | THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR | | | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE | | | OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM | | | TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR | | | PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17 | | | INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM | | | FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY | | | ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2. | | | WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR | | | RIGHT-HAND APPROACH. | | | 2.GRAB BARS SHALL COMPLY WITH FBC ACC SEC 609.4 | | | POSITION OF GRAB BARS. | | | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, | | | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) | | | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF | | | THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR | | | CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE | | | INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM) | | | MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH | | | FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE | | | HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A | | | BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1. | | | 3.SHOWER SEATS SHALL COMPLY WITH FBC SEC 610.3 SHOWER | | | COMPARTMENT SEATS. | | | WHERE A SEAT IS PROVIDED IN A STANDARD ROLL-IN SHOWER | | | COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE | | | INSTALLED ON THE SIDE WALL ADJACENT TO THE CONTROLS, | | | AND SHALL EXTEND FROM THE BACK WALL TO A POINT WITHIN 3 | | | INCHES (75 MM) OF THE COMPARTMENT ENTRY. WHERE A SEAT | | | IS PROVIDED IN AN ALTERNATE ROLL-IN TYPE SHOWER | | | COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE | | | INSTALLED ON THE FRONT WALL OPPOSITE THE BACK WALL, AND | | | SHALL EXTEND FROM THE ADJACENT SIDE WALL TO A POINT | | | WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. IN | | | TRANSFER-TYPE SHOWERS, THE SEAT SHALL EXTEND FROM THE | | | BACK WALL TO A POINT WITHIN 3 INCHES (75 MM) OF THE | | | COMPARTMENT ENTRY. THE TOP OF THE SEAT SHALL BE 17 | | | INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM | | | ABOVE THE BATHROOM FINISH FLOOR. SEATS SHALL COMPLY | | | WITH 610.3.1 OR 610.3.2. | | | 3.SHOWER CONTROLS SHALL COMPLY WITH FBC ACC. 608.6 | | | SHOWER SPRAY UNIT AND WATER. | | | A SHOWER SPRAY UNIT WITH A HOSE 59 INCHES (1500 MM) | | | LONG MINIMUM THAT CAN BE USED BOTH AS A FIXED-POSITION | | | SHOWER HEAD AND AS A HAND-HELD SHOWER SHALL BE | | | PROVIDED. THE SHOWER SPRAY UNIT SHALL HAVE AN ON/OFF | | | CONTROL WITH A NON-POSITIVE SHUT-OFF. IF AN | | | ADJUSTABLE-HEIGHT SHOWER HEAD ON A VERTICAL BAR IS | | | USED, THE BAR SHALL BE INSTALLED SO AS NOT TO OBSTRUCT | | | THE USE OF GRAB BARS. SHOWER SPRAY UNITS SHALL DELIVER | | | WATER THAT IS 120?F (49?C) MAXIMUM | | | 3.PROVIDE SPEC SHEETS ON ELEVATOR SUMP PUMP AND WATER | | | HEATERS AND BOOSTERPUMP. PER WPB AMEND TO FBC | | | SEC.107.2.1 | | | 4. SHEET P201 PLEASE CLARIFY WHAT IS THE 6IN. STANDPIPE | | | FOR SPRINKLER,WHAT IS THIS PIPE BEING USED FOR. WPB | | | AMEND TO FBC SEC 107.2.1 | | | 5. SHEET P201 THE 4IN. SOIL STACK THAT IS CONNECTING TO | | | THE BUILDING DRAIN IN THE MIDDLE OF THE BATHROOM GROUP | | | ON THE FIRST FLOOR IS REQUIRED TO CONNECT DOWN STEAM OF | | | THE BATHROOM GROUP. PER FBC P SEC 912.2.1 | | | 6. SHEET P201 THE BREAKROOM SINK P-5 IS NOT VENTED | | | SHALL COMPLY WITH FBC P SEC 910.1 | | | 7. PLEASE PROVIDE ISOMETRIC THREE DIMENSIONAL RISER | | | DIAGRAMS THE DRAWINGS ON SHEET P201 ARE NOT SUITABLE | | | FOR THE PURPOSE OF A COMPREHENSIVE PLAN REVIEW PER WPB | | | AMEND.TO FBC SEC 107.2.1 | | | WHEN NEW DRAWING ARE PROVIDE A COMPLETE PLUMBING REVIEW | | | WILL BE DONE THERE MAY BE ADDITIONAL COMMENTS. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2015-12-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2015-12-07 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-12-07 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2015-12-07 16:29:23 | ****PROVISO**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PROVISO: ADVISORY ONLY, PRODUCT APPROVALS FOR ALL | | | COMPONENTS AND CLADDING ARE TO BE SUBMITTED PRIOR TO | | | INSTALLATION, REVIEWED BY DOR PRIOR TO SUBMITTAL. | | | COMPONENTS AND CLADDING TO COMPLY WITH THE PRESSURE ON | | | PAGE S102. | | | | | | NO ROOFING PRODUCT APPROVALS SUBMITTED. A SEPARATE | | | PERMIT, PRODUCT APPROVAL REVIEWED BY DOR, AND | | | ENGINEERING (IF APPLICABLE) ARE REQUIRED. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2016-02-19 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2016-02-19 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2016-02-19 |
Time |
15:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
P |
Date |
2015-11-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2015-11-18 |
Time |
17:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-11-18 |
Time |
17:33 |
Sent To |
|
|
| Notes |
| 2015-11-18 17:34:11 | SEE THRESHOLD DOCUMENTS / AGREEMENT FOR 15080008 | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2016-01-26 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2016-01-26 |
Time |
18:33 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2016-01-25 |
Time |
13:20 |
Sent To |
|
|
| Notes |
| 2016-01-26 18:35:03 | PASSED - BUILDING ONLY. | | | | | | 1) SEE SEPARATE PERMITS FOR COMMENTS REGARDING OTHER | | | ELEMENTS OF THE PLANS. | | | | | | 2) SIGNS REQUIRE SEPARATE PERMITS, WITH PLANS. | | | | | | 3) PLEASE REMEMBER THAT IN ACCORDANCE WITH RESOLUTION | | | NO. 206-15, PRIOR TO THE ISSUANCE OF THE C.O., THE | | | FOLLOWING SHALL OCCUR: | | | | | | A. RECORD A PUBLIC ACCESS EASEMENT FOR ANY PUBLIC | | | SIDEWALKS OR UTILITIES ON THE SITE. THE EASEMENT | | | LANGUAGE SHALL BE APPROVED BY THE CITY ATTORNEY'S | | | OFFICE. | | | B. ABANDON THE UNUSED FPL EASEMENT ON THE NORTH | | | PROPERTY LINE. | | | C. CONSTRUCT THE PEDESTRIAN CROSSING OF WESTBOUND | | | OKEECHOBEE BOULEVARD FROM THE CITYPLACE OFFICE PARCEL | | | TO THE RESTORATION HARDWARE PARCEL IN ACCORDANCE WITH A | | | FLORIDA DEPARTMENT OF TRANSPORTATION RIGHT-OF-WAY | | | PERMIT APPROVAL AND TIE IT INTO THE SIDEWALK NETWORK ON | | | THE EAST SIDE OF THE RESTORATION HARDWARE SITE. A COPY | | | OF THE FLORIDA DEPARTMENT OF TRANSPORTATION | | | RIGHT-OF-WAY PERMIT SHALL BE PROVIDED TO THE PLANNING | | | DIVISION. | | | D. CONSTRUCT THE MODIFICATIONS TO THE PEDESTRIAN | | | CROSSING OF OKEECHOBEE BOULEVARD AT ROSEMARY AVENUE | | | (EAST SIDE) TO BE IN COMPLIANCE WITH PLANS APPROVED BY | | | THE FLORIDA DEPARTMENT OF TRANSPORTATION AND THE CITY. | | | A COPY OF THE FLORIDA DEPARTMENT OF TRANSPORTATION | | | RIGHT-OF-WAY PERMIT SHALL BE PROVIDED TO THE PLANNING | | | DIVISION. | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2015-11-05 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2015-11-05 |
Time |
13:22 |
Rev Time |
8.00 |
| Received By |
eschneid |
Date |
2015-11-05 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2015-11-05 13:24:54 | FAILED | | | | | | PROVIDE RESPONSES IN WRITING. | | | | | | 1) THE FIRST FLOOR PLANS DO NOT MATCH THE PLANS | | | APPROVED AS PART OF RESOLUTION NO. 206-15 OR THE MINOR | | | PD AMENDMENT SUBMITTAL ? WEST SIDE DOOR OPENINGS. | | | | | | 2) IF SHEET A-120 IS REVISED, PLEASE CLEARLY INDICATE | | | THAT THE LEVEL 1 BATHROOM DOORS WILL LOCK FROM THE | | | INSIDE. | | | | | | 3) THE AMOUNT OF GLAZING VISIBLE AT THE DOORWAY/TRANSOM | | | WINDOWS AND THE METAL AWNINGS COVERING THE | | | DOORWAY/TRANSOM WINDOWS HAS CHANGED FROM WHAT WAS | | | ORIGINALLY APPROVED BY RESOLUTION NO. 206-15. THE | | | BUILDING PERMIT (ALSO THE MINOR AMENDMENT PLANS) SHOWS | | | LESS GLAZING THAN WAS APPROVED (SEE CLOUDS ON PERMIT | | | SET FOR EXAMPLES). SOME OF THE GLAZING IS COVERED BY | | | LARGER OR RELOCATED METAL AWNINGS, WHILE OTHER GLAZING | | | HAS BEEN REMOVED AND REPLACED BY SOLID WALL. STAFF WILL | | | NOT APPROVE THE REDUCTION OR COVERING OF ADDITIONAL | | | GLAZING SINCE PROVIDING MAXIMUM GLAZING WAS AN INTEGRAL | | | PART OF THE CITY'S SUPPORT AND APPROVAL OF THE PROJECT. | | | THIS COMMENT APPLIES TO THE WEST, EAST, NORTH AND SOUTH | | | ELEVATIONS. SHEETS A201, 201A, 202, 202A | | | | | | 4) THE LANDSCAPE PLAN SUBMITTED AS PART OF THE PERMIT | | | DOES NOT MATCH THE LANDSCAPE PLAN APPROVED AS PART OF | | | RESOLUTION NO. 206-15. NO REVISED LANDSCAPE PLAN WAS | | | SUBMITTED AS PART OF THE CURRENT MINOR PD AMENDMENT | | | UNDER REVIEW. | | | | | | 5) THE REVISED LANDSCAPE LAYOUT OF THE ROOF PLAN | | | REQUIRES REVISED PLANS AS PART OF THE SUBMITTED MINOR | | | PD AMENDMENT. | | | | | | 6) THE LANDSCAPE DETAILS SHEET DOES NOT PROVIDE | | | INFORMATION ON THE ROOFTOP PLANTINGS. | | | | | | 7) SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR THE | | | FOLLOWING ITEMS THAT ARE EXTERIOR TO THE BUILDING: | | | | | | A. AWNINGS | | | B. PARKING LOT, INCLUDING STRIPING | | | C. LANDSCAPE PLEASE NOTE THAT THE LANDSCAPE WITHIN THE | | | RIGHT-OF-WAY REQUIRES FDOT PERMITS. | | | D. FOUNTAINS | | | E. SITE LIGHTING - PLEASE NOTE THAT THE LIGHTING WITHIN | | | THE RIGHT-OF-WAY REQUIRES FDOT PERMITS. | | | F. HARDSCAPE (ABOVE GROUND SITE WORK) | | | G. BICYCLE RACKS | | | H. WALLS, GATES AND THEIR COLUMNS | | | I. SIGNS | | | J. DUMPSTER ENCLOSURE - PLEASE NOTE THAT THE PERMIT SET | | | OF PLANS NO LONGER SHOW A GATE FOR THE TRANSFORMER, | | | THUS THE DUMPSTER IS NO LONGER FULLY SCREENED AS | | | REQUIRED BY CODE. | | | K. IRRIGATION - PLEASE NOTE THAT THE IRRIGATION WITHIN | | | THE RIGHT-OF-WAY REQUIRES FDOT PERMITS. | | | | | | 8) PLEASE REMEMBER THAT IN ACCORDANCE WITH RESOLUTION | | | NO. 206-15, PRIOR TO THE ISSUANCE OF THE C.O., THE | | | FOLLOWING SHALL OCCUR: | | | | | | A. RECORD A PUBLIC ACCESS EASEMENT FOR ANY PUBLIC | | | SIDEWALKS OR UTILITIES ON THE SITE. THE EASEMENT | | | LANGUAGE SHALL BE APPROVED BY THE CITY ATTORNEY'S | | | OFFICE. | | | B. ABANDON THE UNUSED FPL EASEMENT ON THE NORTH | | | PROPERTY LINE. | | | C. CONSTRUCT THE PEDESTRIAN CROSSING OF WESTBOUND | | | OKEECHOBEE BOULEVARD FROM THE CITYPLACE OFFICE PARCEL | | | TO THE RESTORATION HARDWARE PARCEL IN ACCORDANCE WITH A | | | FLORIDA DEPARTMENT OF TRANSPORTATION RIGHT-OF-WAY | | | PERMIT APPROVAL AND TIE IT INTO THE SIDEWALK NETWORK ON | | | THE EAST SIDE OF THE RESTORATION HARDWARE SITE. A COPY | | | OF THE FLORIDA DEPARTMENT OF TRANSPORTATION | | | RIGHT-OF-WAY PERMIT SHALL BE PROVIDED TO THE PLANNING | | | DIVISION. | | | D. CONSTRUCT THE MODIFICATIONS TO THE PEDESTRIAN | | | CROSSING OF OKEECHOBEE BOULEVARD AT ROSEMARY AVENUE | | | (EAST SIDE) TO BE IN COMPLIANCE WITH PLANS APPROVED BY | | | THE FLORIDA DEPARTMENT OF TRANSPORTATION AND THE CITY. | | | A COPY OF THE FLORIDA DEPARTMENT OF TRANSPORTATION | | | RIGHT-OF-WAY PERMIT SHALL BE PROVIDED TO THE PLANNING | | | DIVISION. | | | | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | | | 2015-10-15 11:38:29 | 10/15/15 |
|
|
|