Plan Review Details - Permit 15091221
Plan Review Stops For Permit 15091221
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-11-30 Cont ID  
Sent By lmarchan Date 2015-12-03 Time 13:53 Rev Time 0.00
Received By shill Date 2015-11-30 Time 17:25 Sent To  
Notes
2015-11-30 17:32:01****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLAN STATES THAT NON IMPACT WINDOWS WERE INSTALLED
 (AND OUR RECORDS INDICATE THAT THE WINDOWS ARE NON
 IMPACT), AND PLAN ACKNOWLEDGES THAT IMPACT PROTECTION
 IS REQUIRED. HOWEVER, IMPACT WINDOW PRODUCT APPROVALS
 WERE SUBMITTED. THIS DOES NOT APPEAR CONSISTENT WITH
 THE WORK DONE. DO YOU PROPOSE TO REMOVE THE NON IMPACT
 WINDOWS AND INSTALL IMPACT?
  
 IF WINDOWS ARE NON IMPACT AND ARE TO REMAIN, PROVIDE
 PRODUCT APPROVALS, FAC9N-3. ALSO PROVIDE PRODUCT
 APPROVALS FOR THE SHUTTERS REFERRED TO ON THE PLAN.
  
 2. FOR THE SHUTTERS, COMPLETE THE SAMPLE INSTALLATION
 SCHEDULE OR PROVIDE ALL INFORMATION TO SHOW CODE
 COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC R301,
 FBC1609. TWO SETS REQUIRED. THIS FORM IS AVAILABLE IN
 THE LOBBY OR ON THE INTERNET AT
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
 3. IT IS NOT CLEAR WHAT AFFECT, IF ANY, ENCLOSING THE
 PORCH HAS ON EMERGENCY EGRESS FOR SLEEPING ROOMS.
 REVISE THE PLAN TO SHOW ROOM DESIGNATION(S) FOR THE
 ROOM(S) ADJACENT TO THE FRONT PORCH, FBC R310.
 ADDITIONAL INFORMATION MAY BE REQUIRED.
  
 4. PLAN SHOWS TWO COLUMNS AN NO WALL WHERE THE FORMER
 EXTERIOR WALL WAS LOCATED. REVISE PLAN TO CLARIFY; IS
 THE WALL IN PLACE OR HAS IT BEEN REMOVED? FBC 107
  
 5. PLAN IS NOT CLEAR. A NOTE STATES THAT STRAPS ARE NOT
 REQUIRED AS THE WALL IS INFILL ONLY, BUT THE DETAIL
 SHOWS STRAPS. CORRELATE AND PROVIDE CALCULATIONS TO
 SHOW THAT THE INFILL WALL WILL RESIST WIND LOADS, FBC
 5TH ED. 301. IF STRAPS ARE NOT UTILIZED, DETAIL SHOULD
 SHOW WHAT IS TO HOLD THE WALL IN PLACE TO RESIST
 POSITIVE AND NEGATIVE WIND PRESSURES. DETAIL SHOWS
 STRAPS, LANGUAGE STATES THEY ARE NOT TO BE INSTALLED,
 PROPOSED DESIGN NOT CLEAR.
  
 6. PLAN IS NOT CLEAR; GROUND FLOOR PLAN GRAPHICALLY
 SHOWS SUPPORTS LARGER THAN THE WALL, AND IT APPEARS
 THAT THE SUPPORTS MAY BE NEW, REVISE PLAN TO CLARIFY,
 FBC 107.
  
 7. A NEW DOOR WAS INSTALLED WITHOUT PERMIT, SEE
 PREVIOUS LIST, REVISE PLAN TO INCLUDE ALL WORK DONE AS
 WELL AS ALL WORK REQUIRED TO BRING INTO COMPLIANCE.
 PROVIDE TWO SETS OF PRODUCT APPROVAL FOR THE DOOR,
 FAC9N-3, FBC 107, FBC 5TH. ED RESIDENTIAL 301.
  
 8. PLAN STATES THAT SCOPE IS REMOVAL OF PLEXIGLASS
 WINDOWS, INSTALLATION OF NEW WINDOWS. THE PORCH WAS
 REBUILT, ELECTRICAL ADDED. REVISE PLAN TO BE CONSISTENT
 WITH WORK DONE WITHOUT PERMIT.
  
 9. VALUE IS TO INCLUDE ALL WORK DONE WITHOUT PERMIT,
 FBC 109. PROVIDE A COST BREAKDOWN OF WORK TO BE
 INCLUDED IN THIS PERMIT.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-10-27 Cont ID  
Sent By shill Date 2015-10-27 Time 07:24 Rev Time 0.00
Received By shill Date 2015-10-27 Time 07:24 Sent To  
Notes
2015-10-27 07:55:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 1. THIS PERMIT IS TO ADDRESS A CODE VIOLATION.
  
 REVISE PLAN TO CLARIFY THE NATURE OF VIOLATION, PROVIDE
 INFORMATION ABOUT THE WORK DONE WITHOUT PERMIT, AND
 REVISE PLAN TO SHOW WHAT IS PROPOSED TO DEAL WITH THIS
 VIOLATION, FBC 107.
  
 PRIOR TO PERMIT ISSUANCE, WORK SHOWN ON THE PLAN WILL
 BE CONFIRMED WITH THE INSPECTOR WHO ISSUED THE
 VIOLATION.
  
 2ND REVIEW, PLAN SUBMITTED INCLUDES AN ENGINEER'S TITLE
 BLOCK AND SEAL BUT NO SIGNATURE, SEE FS471.
  
 SCOPE IS STATED AS WINDOW REPLACEMENT. OUR RECORDS SHOW
 THAT THIS WAS AN UNENCLOSED PORCH WITH SOME SIDING,
 FOUR SCREEN OPENINGS AND A DOOR. THIS WAS ENTIRELY
 RE-FRAMED, OPENINGS RE-CONFIGURED, NEW DOOR AND
 WINDOWS, STUCCO, ELECTRICAL, HANDRAIL REMOVED.
  
 PROVIDE PLANS WHICH ADDRESS THE REFRAMING AND
 CONVERSION OF AN OPEN PORCH TO A HABITABLE ROOM. PLANS
 PROVIDED STATE THAT SCOPE IS TO "REMOVE EXISTING
 PLEXIGLASS WINDOW COVERINGS & INSTALL NEW WINDOWS." IT
 ALSO DEPICTS THIS AREA AS A "COVERED PORCH" BUT IT
 APPEARS THAT THIS IS NOW HABITABLE SPACE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-08 Cont ID  
Sent By shill Date 2015-10-08 Time 12:37 Rev Time 0.00
Received By shill Date 2015-10-08 Time 12:37 Sent To  
Notes
2015-10-08 12:39:00****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THIS PERMIT IS TO ADDRESS A CODE VIOLATION.
  
 REVISE PLAN TO CLARIFY THE NATURE OF VIOLATION, PROVIDE
 INFORMATION ABOUT THE WORK DONE WITHOUT PERMIT, AND
 REVISE PLAN TO SHOW WHAT IS PROPOSED TO DEAL WITH THIS
 VIOLATION, FBC 107.
  
 PRIOR TO PERMIT ISSUANCE, WORK SHOWN ON THE PLAN WILL
 BE CONFIRMED WITH THE INSPECTOR WHO ISSUED THE
 VIOLATION.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-12-03 Cont ID  
Sent By mvaldes Date 2015-12-03 Time 09:22 Rev Time 0.00
Received By mvaldes Date 2015-12-03 Time 09:19 Sent To  
Notes
2015-12-03 09:33:541ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
  
  
 (A) GENERAL PROVISIONS. IN EVERY KITCHEN, FAMILY ROOM,
 DINING ROOM, LIVING ROOM, PARLOR, LIBRARY, DEN,
 SUNROOM,
 BEDROOM, RECREATION ROOM, OR SIMILAR ROOM OR AREA OF
 DWELLING UNITS, RECEPTACLE OUTLETS SHALL BE INSTALLED
 IN ACCORDANCE
 WITH THE GENERAL PROVISIONS SPECIFIED IN 210.52(A)(1)
 THROUGH (A)(3).
  
 (3) BALCONIES, DECKS, AND PORCHES. BALCONIES, DECKS,
 AND
 PORCHES THAT ARE ACCESSIBLE FROM INSIDE THE DWELLING
 UNIT
 SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET INSTALLED
 WITHIN THE
 PERIMETER OF THE BALCONY, DECK, OR PORCH. THE
 RECEPTACLE
 SHALL NOT BE LOCATED MORE THAN 2.0 M (61?2 FT) ABOVE
 THE
 BALCONY, DECK, OR PORCH SURFACE.
  
 210.70 LIGHTING OUTLETS REQUIRED. LIGHTING OUTLETS
 SHALL
 BE INSTALLED WHERE SPECIFIED IN 210.70(A), (B), AND
 (C).
 (A) DWELLING UNITS. IN DWELLING UNITS, LIGHTING OUTLETS
 SHALL BE INSTALLED IN ACCORDANCE WITH 210.70(A)(1),
 (A)(2),
 AND (A)(3).
 (1) HABITABLE ROOMS. AT LEAST ONE WALL
 SWITCH?CONTROLLED
 LIGHTING OUTLET SHALL BE INSTALLED IN EVERY HABITABLE
 ROOM
 AND BATHROOM.
  
 (B) FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL SWITCH?
 CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED TO
 PROVIDE ILLUMINATION
 ON THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS
 WITH GRADE LEVEL ACCESS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-03 Cont ID  
Sent By shill Date 2015-12-03 Time 13:53 Rev Time  
Received By lmarchan Date 2015-11-24 Time 16:46 Sent To B
Notes
2015-11-30 18:00:03TO MARIO'S DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-27 Cont ID  
Sent By shill Date 2015-10-27 Time 08:05 Rev Time 0.00
Received By shill Date 2015-10-23 Time 12:57 Sent To  
Notes
2015-10-23 12:57:25RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-08 Cont ID  
Sent By shill Date 2015-10-08 Time 12:39 Rev Time 0.00
Received By shill Date 2015-09-28 Time 10:37 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2015-10-08 Cont ID  
Sent By shill Date 2015-10-08 Time 12:39 Rev Time 0.00
Received By shill Date 2015-10-08 Time 12:39 Sent To  
Notes
2015-10-08 12:39:35AS SCOPE IS NOT CLEAR, I CANNOT DETERMINE WHETHER
 ZONING REVIEW IS REQUIRED.
  
  