Plan Review Details - Permit 15091217
Plan Review Stops For Permit 15091217
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-12-29 Cont ID  
Sent By albarran Date 2015-12-29 Time 15:50 Rev Time 0.00
Received By albarran Date 2015-12-29 Time 15:40 Sent To I
Notes
2015-12-29 15:53:2012/29/15 STAMPED NEW SHEETS AS REQUIRED AND MADE
 REFERENCE TO ELECTRICAL PROVISO FOR GFI OUTLETS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-12-17 Cont ID  
Sent By albarran Date 2015-12-17 Time 11:19 Rev Time 0.00
Received By albarran Date 2015-12-17 Time 08:38 Sent To I
Notes
2015-12-17 11:21:03APPROVED WITH EXCEPTION AS FOLLOWS: IF THE SCOPE OF
 THIS JOB INCLUDES ANY WORK WITHIN THE KITCHEN OUTLETS,
 NEC 210.8(B)2, REQUIRES THAT ALL KITCHEN OUTLETS BE
 GFCI PROTECTED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-10-19 Cont ID  
Sent By albarran Date 2015-10-19 Time 19:56 Rev Time 0.00
Received By albarran Date 2015-10-19 Time 18:26 Sent To I
Notes
2015-10-19 19:57:28NO ELECTRICAL DATA PROVIDED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-12-09 Cont ID  
Sent By albarran Date 2015-12-17 Time 11:24 Rev Time 0.00
Received By pleduc Date 2015-12-09 Time 11:18 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-10-06 Cont ID  
Sent By pleduc Date 2015-10-06 Time   Rev Time 0.00
Received By pleduc Date 2015-10-06 Time 15:56 Sent To E
Notes
2015-10-06 16:01:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 ADDRESS COMMENTS OF OTHER DIVISIONS AND RESUBMITT.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-29 Cont ID  
Sent By albarran Date 2015-12-29 Time 15:53 Rev Time 0.00
Received By albarran Date 2015-12-18 Time 14:31 Sent To  
Notes
2015-12-29 15:54:3312/29/15 READY FOR ISSUANCE. CONTRACTOR NOTIFIED VIA
 PHONE CALL AS NO EMAIL ADDRESS IS PROVIDED. SENT TO
 SMALL READY BIN "G". MA
2015-12-18 14:31:36RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-17 Cont ID  
Sent By albarran Date 2015-12-17 Time 11:21 Rev Time 0.00
Received By albarran Date 2015-12-07 Time 09:54 Sent To FIRE
Notes
2015-12-17 11:24:4112/17/15 PASSED ELECTRICAL REVIEW BUT FAILED
 MECHANICAL. CONTRACTOR NOTIFIED VIA PHONE CALL TO
 NUMBER ON REV FORM. SENT TO SMALL DENIED BIN "G". MA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-19 Cont ID  
Sent By albarran Date 2015-10-19 Time 19:59 Rev Time 0.00
Received By albarran Date 2015-09-28 Time 08:45 Sent To M
Notes
2015-10-19 20:00:1410/19/15 FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO SMALL DENIED BIN "G". MA

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-12-21 Cont ID  
Sent By ccole Date 2015-12-21 Time 08:09 Rev Time 0.00
Received By ccole Date 2015-12-21 Time 08:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-12-16 Cont ID  
Sent By ccole Date 2015-12-16 Time 07:08 Rev Time 0.00
Received By ccole Date 2015-12-16 Time 07:08 Sent To  
Notes
2015-12-16 07:34:462ND REVIEW 2010 MECHANICAL
 PERMIT REVISION #15091217
 12/16/15
  
 1) IN RESPONSE TO THE MOST RECENT LETTER FROM TRANE
 DATED NOVEMBER 5, 2015, PLEASE SEE SECTION 301.4 FBC-10
 MECHANICAL: 301.7 LISTED AND LABELED.
 APPLIANCES REGULATED BY THIS CODE SHALL BE LISTED AND
 LABELED FOR THE APPLICATION IN WHICH THEY ARE INSTALLED
 AND USED, UNLESS OTHERWISE APPROVED IN ACCORDANCE WITH
 SECTION 301.4.1.
 EXCEPTION: LISTING AND LABELING OF EQUIPMENT AND
 APPLIANCES USED FOR REFRIGERATION SHALL BE IN
 ACCORDANCE WITH SECTION 1101.2.
 ALTHOUGH THE LETTER STATES "DISCONNECTING AND REMOVING
 THE HEATERS .....IS ACCEPTABLE TO TRANE", THE LETTER
 ALSO STATES THE "FACTORY NAMEPLATE WILL NOT REFLECT
 THIS CHANGE". DUE TO THE FACT THAT THE PRODUCT WAS
 TESTED, APPROVED, AND LISTED WITH THE HEATERS IN TACT
 AS PART OF THE PRODUCT ASSEMBLY, THE NAMEPLATE OR LABEL
 IS NO LONGER VALID SINCE THE HEATERS HAVE BEEN REMOVED
 IN THE FIELD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-10-06 Cont ID  
Sent By albarran Date 2015-10-19 Time 20:00 Rev Time 0.00
Received By ccole Date 2015-10-06 Time 08:31 Sent To  
Notes
2015-10-06 08:40:531ST REVIEW: FBC 2010 MECHANICAL
 REVISION #15091217, MASTER #15050778
 10/6/15
  
 1) THE LETTER FROM MR. NERI OF TRANE SOUTH FLORIDA
 ASSOCIATED WITH THIS PLAN REVISION WAS SUBMITTED
 WITHOUT SIGNATURE. IN ADDITION, THE LETTER IS
 REQUESTING THAT AN INSPECTOR APPROVE MECHANICAL
 EQUIPMENT (VAV BOXES) THAT WILL BE ALTERED IN THE FIELD
 WITHOUT CERTIFICATION BY THE MANUFACTURER OR THE
 LISTING AND LABELING AGENCY- SECTION 301.4 FBC-10
 MECHANICAL.
 2) PLEASE NOTE THAT INSTALLATION OF THE NEW DUCT
 HEATERS WILL REQUIRE A REVISION TO THE APPROVED
 ELECTRICAL PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  