Plan Review Details - Permit 15091208
Plan Review Stops For Permit 15091208
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-12-10 Cont ID  
Sent By jwitmer Date 2015-12-10 Time 12:30 Rev Time 0.00
Received By jwitmer Date 2015-12-10 Time 12:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-11-04 Cont ID  
Sent By jwitmer Date 2015-11-04 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2015-11-03 Time 17:10 Sent To E
Notes
2015-11-04 06:24:26BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15091208
 ADD: 427 NORTHWOOD AVE.
 CONT: OPEN SIGHTS CONSTRUCTION
 TEL: (786)246-7052
 E-MAIL: SACHAUZAN6GMAIL.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. NOV. 04/ 2015
 ACTION: DENIED
  
 1) COMPLIED. PLEASE SUBMIT A FLOOR PLAN OF THE INTERIOR
 OF THE BUILDING. IN THE YEAR 1998-99 IT LOOKS LIKE
 THERE WERE PERMITS TO CONVERT THIS SPACE TO HAVE A
 COMMERCIAL KITCHEN. THERE WAS A PERMIT FOR A UNDER
 COUNTER GREASE TRAP. IT WOULD APPEAR THROUGH THE
 OCCUPATIONAL LISENCE THAT THE USE AS A CATERING
 BUSINESS THAT WOULD HAVE BEEN NO CHANGE OF OCCUPANCY.
 THE NEW OCCUPATIONAL LICESNE FOR TABLE 427 IS FOR A 43
 SEAT RESTARAUNT. THIS MAY NOT BE A CHANGE OF OCCUPANCY
 BUT A CHANGE OF USE THAT WILL NEED TO BE REVIEWED BY
 ALL DISCIPLES FOR CODE COMPLIANCE. 2014 FBC-B 303.1.1.
 PLEASE NOTE THE OCCUPANT LOAD IS BASED ON THE SQUARE
 FOOTAGE OF THE BUILDING 15 SQ. FT PER OCCUPANT AND 200
 SQUARE FEET PER OCCUPANT FOR COMMERCIAL KITCHENS.
  
 PLEASE NOTE THAT WE WILL ALSO NEED A FLOOR PLAN FOR THE
 ADDTIONAL OUSIDE SEASONAL SEATING. ONCE THE COMBINED
 OCCUPANT LOAD IS 50 OR GREATER THIS BECOMES A CHANGE OF
 OCCUPANCY AS WELL AS A CHANGE IN USE. CHAPTER 10 OF THE
 2014 EXISISTNG BUILDING CODE WOULD BE ENACTED. PLEASE
 NOTE THE NEW CONCRETE SLAB DEPICTED ON SHEET 3 IS
 APPROXIMATELY 1364 SQUARE FEET/ 15= 91 OCCUPANTS.
  
 2) PROVISO: SHEET # 3 SHOWS THE NEW OPENING INTO THE
 EXISITNG BUILDING WITH NEW VERTICAL STEEL ON EACH SIDE
 OF THE DOORWAY. THE PLANS SHOW THE VERTICAL REBAR TO
 THE LINTEL HEIGHT BUT GOING TO THE BEAM ABOVE THAT WILL
 MAKE THE VERTICAL REBAR PART OF THE MWFRS (MAIN WIND
 FORCE RESISTING SYSTEM).
  
 3A) (1) 2ND REQUEST THE RESPONSE COMMENTS INDICATE THE
 OWNERS ARE RECYCLING AN EXISTING DOOR. THE ENGINEER OF
 RECORD WILL NEED TO COMPLETE AN ANALYSIS OF THE DOOR
 AND PROVIDE A REPORT THAT THE DOOR MEETS THE 2014 FBC-B
 FOR WIND PRESSURE DESIGN. HE WILL ALSO NEED TO PROVIDE
 A DOOR JAMB DETAIL AND ANCHORING OF THE DOOR JAMB TO
 THE MWFRS (MAIN WIND FORCE RESISTING SYSTEM) THE
 ENGINEER OF RECORD CAN USE AN APPROVED DOOR REPORT A
 MIAMI-DADE NOA OR FLORIDA APPROVAL TO DO THEIR RATIONAL
 ANALYSIS FROM.
 A SITE SPECIFIC FORM FOR THE OWNERS SUPPLIED DOOR WILL
 BE E-MAILED TO: [email protected]
 11/04/2015 06:53 AM
  
 COMMENT FROM 1ST REVIEW. NO PRODUCT APPROVAL WAS
 SUBMITTED FOR THE NEW DOOR OPENING. 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 3A)(2) NEW COMMENT. CORRECT WORDING ON SHEETS 1 & 3.
 THE PLANS NOW SAY NEW FRENCH DOORS. PLEASE REVISE TO
 RECYCLED DOORS. DISCEPANCY IN THE DESCRIPTION OF THE
 PRODUCT BEING INSTALLED. 107.2.4 EXTERIOR WALL
 ENVELOPE. THE CONSTRUCTION DOCUMENTS SHALL INCLUDE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS THAT PROVIDE
 SUPPORTING DOCUMENTATION THAT THE PROPOSED PENETRATION
 AND OPENING DETAILS DESCRIBED IN THE CONSTRUCTION
 DOCUMENTS MAINTAIN THE WEATHER RESISTANCE
 OF THE EXTERIOR WALL ENVELOPE. THE SUPPORTING
 DOCUMENTATION SHALL FULLY DESCRIBE THE EXTERIOR WALL
 SYSTEM WHICH WAS TESTED, WHERE APPLICABLE, AS WELL AS
 THE TEST PROCEDURE USED.
  
 3B) COMPLIED. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4) COMPLIED. THE PRODUCT APPROVAL SUBMITTED FOR THE
 ACCORDIAN STORM SHUTTER DOES NOT HAVE ANY OF THE
 DETAILS HIGHLIGHTED (CIRCLED) FOR THE TOP AND BOTTOM
 TRACKS, SPANS, TYPE OF FASTENERS ETC. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 5) 2ND REQUEST. I'VE SPOKEN WITH THE BUILDING OFFICIAL
 ABOUT THE INSWING GATES. THERE ARE (2) ISSUES WE WILL
 NEED TO SHOW EGRESS FRROM THE PROPOSED EXTERIOR
 ASSEMBLY SEATING WITH A OCCUPANT LOAD GREATER THAN 50.
  
 5A) THE DESIGNER OF RECORD ON THE COMMENT RESPONSE
 INDICATED WHILE THE RESTARAUNT IS OPEN THE GATES WILL
 BE HELD OPEN WITH HOLD OPEN DEVICES. THIS STATEMENT
 WILL NEED TO BE ADDED TO SHEETS 2,3 & 4.
  
 5B) THE DESIGNER OF RECORD ON THE COMMENT RESPONSE
 INDICATED THE 2ND MEANS OF EGRESS IS THE WHOLE BACK
 SIDE OF THE PROPOSED PATIO WILL BE OPEN SO THE
 DIRECTION OF TRAVEL CAN GO TOWARDS THE ALLEY AND TO THE
 PUBLIC WAY. SINCE THE 2014 FBC-B TABLE 1015.1 REQUIRES
 2 MEANS OF EGRESS WE WOULD ASK THAT THE DESIGNER OF
 RECORD
 PUT THE ABOVE STATEMENT ON SHEETS 2, 3 & 4 FOR
 COMPLIANCE OF THE SECOND MEANS OF EGRESS. ONCE OUTSIDE
 OF THE BUILDING FOR A MEANS OF EGRESS, YOU CAN NOT
 RE-ENTER THE BUILDING AS PART OF A MEANS OF EGRESS.
  
 COMMENT FROM 1ST REVIEW. SHEET 1 AND 3 BOTH SHOW THE
 NEW GATES THAT EXIT TO THE STREET SWING IN. WHEN
 OCCUPANT LOADS GREATER THAN 49 THEY NEED TO SWING IN
 THE DIRECTION OF TRAVEL. 2014 FBC-B 1008.1.2.
  
 THE OTHER ISSUE WITH THE NEW GATES, WITH OUTSWING GATES
 THEY WILL NEED TO BE SET BACK SO THE OUTSWING GATES DO
 NOT SWING OUT OVER THE PROPERTY LINE. 2014 FBC-B
 3202.2.
  
 6) PLEASE PROVIDE COMPLIANCE WITH THE NEW EXTERIOR BAR
 AREA. SHOW HOW COMPLIANCE WITH 2014 ACCESSIBILITY CODE
 226.2 DISPERSION,DINING SURFACES REQUIRED TO COMPLY
 WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE OR
 FACILITY CONTAINING DINING SURFACES.
 2014 FBC-ACCESSIBILITY CODE 902.3 HEIGHT, PLEASE SHOW
 HOW COMPLIANCE WITH THE HEIGHT OF THE BAR WILL BE
 ACHIEVED. THE TOP OF DINING SURFACES SHALL BE A MINIMUM
 OF 28 INCHES AND A MAXIMUM OF 34 INCHES ABOVE THE
 FINISH FLOOR.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-13 Cont ID  
Sent By jwitmer Date 2015-10-13 Time 14:16 Rev Time 0.00
Received By jwitmer Date 2015-10-13 Time 02:01 Sent To  
Notes
2015-10-13 13:14:37BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15091208
 ADD: 427 NORTHWOOD AVE.
 CONT: OPEN SIGHTS CONSTRUCTION
 TEL: (786)246-7052
 E-MAIL: SACHAUZAN6GMAIL.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. OCT. 13/ 2015
 ACTION: DENIED
  
 1) PLEASE SUBMIT A FLOOR PLAN OF THE INTERIOR OF THE
 BUILDING. IN THE YEAR 1998-99 IT LOOKS LIKE THERE WERE
 PERMITS TO CONVERT THIS SPACE TO HAVE A COMMERCIAL
 KITCHEN. THERE WAS A PERMIT FOR A UNDER COUNTER GREASE
 TRAP. IT WOULD APPEAR THROUGH THE OCCUPATIONAL LISENCE
 THAT THE USE AS A CATERING BUSINESS THAT WOULD HAVE
 BEEN NO CHANGE OF OCCUPANCY. THE NEW OCCUPATIONAL
 LICESNE FOR TABLE 427 IS FOR A 43 SEAT RESTARAUNT. THIS
 MAY NOT BE A CHANGE OF OCCUPANCY BUT A CHANGE OF USE
 THAT WILL NEED TO BE REVIEWED BY ALL DISCIPLES FOR CODE
 COMPLIANCE. 2014 FBC-B 303.1.1. PLEASE NOTE THE
 OCCUPANT LOAD IS BASED ON THE SQUARE FOOTAGE OF THE
 BUILDING 15 SQ. FT PER OCCUPANT AND 200 SQUARE FEET PER
 OCCUPANT FOR COMMERCIAL KITCHENS.
  
 PLEASE NOTE THAT WE WILL ALSO NEED A FLOOR PLAN FOR THE
 ADDTIONAL OUSIDE SEASONAL SEATING. ONCE THE COMBINED
 OCCUPANT LOAD IS 50 OR GREATER THIS BECOMES A CHANGE OF
 OCCUPANCY AS WELL AS A CHANGE IN USE. CHAPTER 10 OF THE
 2014 EXISISTNG BUILDING CODE WOULD BE ENACTED. PLEASE
 NOTE THE NEW CONCRETE SLAB DEPICTED ON SHEET 3 IS
 APPROXIMATELY 1364 SQUARE FEET/ 15= 91 OCCUPANTS.
  
 2) SHEET # 3 SHOWS THE NEW OPENING INTO THE EXISITNG
 BUILDING WITH NEW VERTICAL STEEL ON EACH SIDE OF THE
 DOORWAY. THE PLANS SHOW THE VERTICAL REBAR TO THE
 LINTEL HEIGHT BUT GOING TO THE BEAM ABOVE THAT WILL
 MAKE THE VERTICAL REBAR PART OF THE MWFRS (MAIN WIND
 FORCE RESISTING SYSTEM).
  
 3A) NO PRODUCT APPROVAL WAS SUBMITTED FOR THE NEW DOOR
 OPENING. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 3B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 4) THE PRODUCT APPROVAL SUBMITTED FOR THE ACCORDIAN
 STORM SHUTTER DOES NOT HAVE ANY OF THE DETAILS
 HIGHLIGHTED (CIRCLED) FOR THE TOP AND BOTTOM TRACKS,
 SPANS, TYPE OF FASTENERS ETC. CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
  
 5) SHEET 1 AND 3 BOTH SHOW THE NEW GATES THAT EXIT TO
 THE STREET SWING IN. WHEN OCCUPANT LOADS GREATER THAN
 49 THEY NEED TO SWING IN THE DIRECTION OF TRAVEL. 2014
 FBC-B 1008.1.2.
  
 THE OTHER ISSUE WITH THE NEW GATES, WITH OUTSWING GATES
 THEY WILL NEED TO BE SET BACK SO THE OUTSWING GATES DO
 NOT SWING OUT OVER THE PROPERTY LINE. 2014 FBC-B
 3202.2.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-12-15 Cont ID  
Sent By albarran Date 2015-12-15 Time 18:54 Rev Time 0.00
Received By albarran Date 2015-12-15 Time 18:40 Sent To I
Notes
2015-12-15 18:54:41MISSING SIGN OUTLET HAS BEEN ADDED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-11-24 Cont ID  
Sent By albarran Date 2015-11-24 Time 18:00 Rev Time 0.00
Received By albarran Date 2015-11-18 Time 10:31 Sent To I
Notes
2015-11-24 18:06:28I HAD THIS FILE ON MY DESK WAITING FOR A RESPONSE TO MY
 EMAIL OF 11/8/15 TO MR. CARL FORBES. BEING THAT A
 RESPONSE WAS NEVER RECEIVED, I HAD TO NEGATIVELY
 PROCESS THIS PERMIT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-10-21 Cont ID  
Sent By albarran Date 2015-10-21 Time 20:32 Rev Time 0.00
Received By albarran Date 2015-10-21 Time 19:45 Sent To I
Notes
2015-10-21 20:32:40THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION
 OF THE FBC, (FLORIDA BUILDING CODE) 2014, AS APPLICABLE
 AND BELOW ARE THE DEFICIENCIES NOTED.
  
 1. YOU SHALL PROVIDE A DEDICATED SIGN OUTLET ADJACENT
 TO THE ?NEW IRON GATE?. NEC 600.5 REQUIRES THAT EVERY
 PEDESTRIAN ENTRY IN EVERY COMMERCIAL ESTABLISHMENT BE
 PROVIDED WITH PROVISIONS FOR SIGNAGE.
 2. YOU SHALL PROVIDE PROPER ILLUMINATION FOR THE AREA.
 3. YOU SHALL PROVIDE AN EMERGENCY/EXIT COMBINATION
 FIXTURE ABOVE THE NEW EXIT. THIS FIXTURE SHALL BE
 CONNECTED AHEAD OF ANY SWITCHING, ON THE SAME CIRCUIT
 PROVIDING THE REQUIRED LIGHTING FOR THE AREA IN
 QUESTION.
 4. PER NEC 310.15, YOU SHALL USE 3 # 3/0 CU CONDUCTORS
 FOR YOUR SERVICE FEEDERS.
 5. PER NEC 250.66, YOUR GROUNDING ELECTRODE CONDUCTOR
 SHALL BE NO LESS THAN A #4 CU.
 6. PER NEC 250.122, YOUR EQUIPMENT GROUND CONDUCTOR
 SHALL BE NO LESS THAN A #6 CU.
  
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE,
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-12-03 Cont ID  
Sent By J.Walker Date 2015-12-03 Time   Rev Time 0.25
Received By   Date 2015-12-02 Time   Sent To Z
Notes
2015-12-03 08:51:07OCCUPANT LOAD SINGAGE, ABC FIRE EXTINGUISHERS WILL BE
 REQUIRED FOR FIRE FINAL #131
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-10-09 Cont ID  
Sent By Walker Date 2015-10-09 Time   Rev Time  
Received By   Date 2015-10-06 Time   Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-16 Cont ID  
Sent By lmarchan Date 2015-12-16 Time 14:39 Rev Time 0.00
Received By lmarchan Date 2015-11-30 Time 10:10 Sent To  
Notes
2015-12-01 10:10:46C06

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-24 Cont ID  
Sent By albarran Date 2015-11-24 Time 18:06 Rev Time 0.00
Received By albarran Date 2015-10-27 Time 09:33 Sent To  
Notes
2015-11-24 18:07:2011/24/15 FAILED TRADE REVIEWS. ON 11/8/15 I SENT AN
 EMAIL TO MR. CARL FORBES WITH REGARDS TO THIS
 ELECTRICAL REVIEW. I NEVER RECEIVED A RESPONSE AND WAS
 FORCED TO FAIL THE ELECTRICAL REVIEW.CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "O". MA
2015-10-28 09:33:59C01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-21 Cont ID  
Sent By albarran Date 2015-10-21 Time 20:33 Rev Time 0.00
Received By albarran Date 2015-09-28 Time 10:34 Sent To  
Notes
2015-10-21 20:33:5610/21/15 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "O". MA

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-12-10 Cont ID  
Sent By jwitmer Date 2015-12-10 Time 12:04 Rev Time 0.00
Received By jwitmer Date 2015-12-10 Time 12:04 Sent To  
Notes
2015-12-10 12:05:07IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-10-13 Cont ID  
Sent By jwitmer Date 2015-10-13 Time 14:17 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2015-10-13 14:17:06BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-12-04 Cont ID  
Sent By gjohnson Date 2015-12-04 Time 12:56 Rev Time 0.00
Received By gjohnson Date 2015-12-04 Time 12:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-11-02 Cont ID  
Sent By gjohnson Date 2015-11-02 Time 14:55 Rev Time 0.00
Received By gjohnson Date 2015-11-02 Time 14:55 Sent To  
Notes
2015-11-02 15:12:222ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1.DRAIN LINE FROM BAR SINKS SHALL NO DRAIN INTO GREASE
 TRAP.PER FBC P SEC 1003.3.1 GREASE INTERCEPTORS AND
 AUTOMATIC GREASE REMOVAL DEVICES SHALL RECEIVE WASTE
 ONLY FROM FIXTURES AND EQUIPMENT THAT ALLOW FATS, OILS
 OR GREASE TO BE DISCHARGED.
 2.PROVIDE MANUFACTURE SPECS FOR WATER HEATER. PER WPB
 AMEND TO FBC SEC107.2.1
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-10-05 Cont ID  
Sent By tklarge Date 2015-10-05 Time 05:40 Rev Time 0.00
Received By tklarge Date 2015-10-05 Time 05:10 Sent To  
Notes
2015-10-05 05:24:431) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. WPB AMEND.
 TO FBC SEC. 107.3.5.1.3.
 2) SUBMIT A SEATING PLAN FOR THE NEW OUTSIDE PATIO AREA
 AND PLACE THE OCCUPANT LOAD ON THE PLANS AND THE TOTAL
 OCCUPANT LOAD FOR THE INTERIOR AND EXTERIOR AREAS. THE
 NEW EXTERIOR AREA WILL CONTRIBUTE TO THE THE OVERALL
 OCCUPANT LOAD.WPB 107.2.1.
 3) SUBMIT AN INTERIOR FLOOR PLAN SHOWING THE CURRENT
 EXISTING SANITARY FACILITIES. THE INCREASE IN THE
 OCCUPANT LOAD FROM THE EXTERIOR PATIO MAY TRIGGER
 ADDITIONAL SANITARY FACILITIES. 2014 FBC-EXISTING
 BUILDING CODE SEC.1103.1 & 2014 FBC-PLUMBING TABLE
 403.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-12-04 Cont ID  
Sent By sgraham Date 2015-12-04 Time 15:53 Rev Time 0.00
Received By sgraham Date 2015-12-04 Time 15:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-10-02 Cont ID  
Sent By SGRAHAM Date 2015-10-02 Time 14:59 Rev Time 0.00
Received By sgraham Date 2015-10-02 Time 14:59 Sent To E
Notes