Plan Review Details - Permit 15091201
Plan Review Stops For Permit 15091201
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-10-22 Cont ID  
Sent By jwitmer Date 2015-10-22 Time 14:53 Rev Time  
Received By jwitmer Date 2015-10-14 Time 14:14 Sent To  
Notes
2015-10-22 14:53:50BUILDING PLAN REVIEW
 W. P. B. REVISION: 15091201
 W. P. B. PERMIT: 14050111
 ADD: 600 OKEECHOBEE BLVD.
 CONT: COASTAL CONSTRUCTION
 TEL: (
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. OCT. 22/ 2015
  
 ACTION: BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
  
 1) SHEET 0243 THE FRONT ENTRY DOORS INDICATE THEY ARE
 SWING ENTRY DOORS WITH WHAT APPEARS TO BE SIDE LIGHTS.
 NR WINDOWS HAS A REVISION IN FOR DOOR OPENING 100A TO
 CREATE ELECTRIC HORIZONTAL SLIDDING DOORS. REVISION #
 14 DOES NOT DEPICT THIS CHANGE. PLEASE NOTE ON THIS
 SHEET AND THE DOOR SCHEDULE THESE DOORS BEING PART OF
 THE MEANS OF EGRESS WILL NEED TO COMPLY WITH 2010 FBC-B
 1008.1.10 DOORS SERVING ROOMS OR SPACES WITH AN
 OCCUPANT LOAD OF 50 OR MORE IN A GROUP A OCCUPANCY
 SHALL NOT BE PROVIDED WITH A LOCK OR LATCH UNLESS IT IS
 PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 THE EXEPTION # 1 DOES NOT WORK SINCE 1008.1.9.3(2) IS
 FOR GROUP A OCCUPANCIES WITH OCCUPANT LOADS OF 300 OR
 LESS FOR THE BUILDING.
  
  
 2) SHEET 0238-A3.13 STAIR TOWER # 2 THE WALL IS MISSING
 THAT SEPARATES THE STAIRWELL FROM THE ADJACENT
 MECHANICAL ROOM. STAIRWELL # 2 IS NOT ONLY A VERTICAL
 EXIT BUT THE STAIRWELL THAT IS ADJACENT TO THE FIRE
 SERVICE ACCESS ELEVATOR. THIS WILL BE THE STAIRWELL THE
 FIRE FIGHTERS WILL BE USING TO GAIN ACCESS TO THE ROOF
 TOP. 2010 FBC-B 403.6.1.
  
 THE 2010 FBC-B 1022.3 OPENINGS AND PENETRATIONS. THE
 ONLY ALLOWABLE OPENINGS ARE PERMITTED IN
 FIRE-RESISTANCE RATED EXIT STAIRWAY ENCLOSURESS ARE
 DOORS THAT LEAD FROM NORMALLY OCCUPIED SPACES INTO THE
 ENCLOSURE AND DOORS LEADING OUT OF THE ENCLOSURE TO THE
 OUTSIDE.
  
 THE MECHANICAL PLANS LABELED 1022-T4-19 LABEL THE
 ADJOINING ROOM, MECHANICAL ROOM 1502. PLEASE NOTE TO
 GAIN ACCESS TO THIS ROOM IT WILL NEED TO BE FROM THE
 EXTERIOR OF THE BUILDING, NOT THROUGH THE VERTICAL
 EXIT. THE VERTICAL EXIT CAN NOT BE USED FOR STORAGE
 AREAS OR IN THE FUTURE THE INSTALATION OF CELLUAR PHONE
 EQUIPMENT. THIS BEING A HIGH RISE BUILDING WILL
 PROBABLY END UP WITH CELLUAR PHONE TOWERS AND EQUIPMENT
 ROOMS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-10-28 Cont ID  
Sent By skennedy Date 2015-10-28 Time 15:51 Rev Time 0.00
Received By skennedy Date 2015-10-28 Time 15:51 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2016-01-15 Cont ID  
Sent By skennedy Date 2016-01-15 Time 15:12 Rev Time 0.00
Received By skennedy Date 2016-01-15 Time 15:12 Sent To  
Notes
2016-01-15 15:13:51CIVIL SHEETS REMOVED AND REVIEWED UNDER 15120207.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-12-03 Cont ID  
Sent By mGONZALE Date 2015-12-03 Time   Rev Time 1.00
Received By mgonzale Date 2015-12-03 Time   Sent To I
Notes
2015-12-03 14:49:38PLEASE ADDRESS PLANNING'S COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-10-22 Cont ID  
Sent By wjolin Date 2015-10-22 Time 16:12 Rev Time 0.00
Received By wjolin Date 2015-10-22 Time 16:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-03 Cont ID  
Sent By lmarchan Date 2015-12-03 Time 15:14 Rev Time 0.00
Received By lmarchan Date 2015-09-30 Time 08:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-12-23 Cont ID  
Sent By ccole Date 2015-12-23 Time 06:58 Rev Time 0.00
Received By ccole Date 2015-12-23 Time 06:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-10-23 Cont ID  
Sent By ccole Date 2015-10-23 Time 07:02 Rev Time 0.00
Received By ccole Date 2015-10-20 Time 15:02 Sent To  
Notes
2015-10-23 07:30:081ST REVIEW: FBC 2010 MECHANICAL
 REVISION PERMIT #15091201
 MASTER PERMIT # 14050111
  
 1) THE SUBMITTED NARRATIVE FROM STEVEN FELLER P.E. DOES
 NOT LIST ALL THE CHANGES THAT ARE INDICATED ON THE
 PLANS. IF THE CHANGES WERE MADE UNDER PREVIOUS
 REVISIONS, PLEASE PLACE CLOUDS AND SYMBOLS ON THE PLANS
 FOR CLARIFICATION. PLEASE EXPAND THE NARRATIVE TO
 BRIEFLY EXPLAIN WHY SOME OF THESE CHANGES ARE BEING
 MADE. THE FOLLOWING LIST ARE "SOME" OF THE CHANGES I AM
 SEEING ON THE PLANS THAT ARE NOT IN THE NARRATIVE.
 A) SHEET M1.01: NEW VAV BOXES, VAV BOX RELOCATIONS,
 DUCTWORK CHANGES TO AC-3, AC-4, AC-5, DUCTWORK RUNS TO
 THE BALLROOM, MOTORIZED DAMPERS ADDED, LOUVER SIZE
 INCREASES, CHANGE TO RETURN AIR PLENUM, ETC.
 B) M1.02: RELOCATION OF AC-6 & AC-7, NEW INSTALLATION
 OF FIRE-RATED SUPPLY AND RETURN GRILLS AT THE DOCK
 OFFICE, AND RECONFIGURING OF DUCTWORK FOR ALL AC
 SYSTEMS, ETC. PROVIDE SUBMITTALS FOR THE FIRE-RATED
 GRILLS.
 C) M1.03: RELOCATION OF AC-13, VAV BOX RELOCATIONS,
 DUCTWORKWORK CHANGES, ETC.
 D) M1.04: RELOCATION OF AC-15, CHANGES TO THE RETURN
 AIR SYSTEMS IN THE MEETING ROOMS, ETC.
 E) M1.05: CHANGE IN RETURN AIR PLENUM, CHANGES TO RETUN
 AIR DUCTING TO AC-4, ETC.
 F) M1.09- M1.12: PLEASE CLARIFY WHY THE FIRE DAMPERS AT
 THE ELEVATOR LOBBIES WERE CHANGED TO FIRE/SMOKE
 DAMPERS.
 G) M2.0: CLARIFY WHY THE HP WAS EXCLUDED FROM THE EXEC.
 LOUNGE.
 H) M4.1: CLARIFY WHY HP-6, 7, & 8 WERE ADDED TO THE
 SCHEDULE AND WHERE ARE THEY LOCATED ON THE PLANS.
 PROVIDED SIZING CALCULATIONS FOR THE UNITS PER SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION.
 I) M4.2: CLARIFY WHY THE STAIR PRESSURIZATION FANS WERE
 CHANGED AND REDUCED IN CFM CAPACITY, AND WHY SPF-1 WAS
 CHANGED FROM "UTILITY" TO "MIXED FLOW". PROVIDE
 SUBMITTALS FOR THE NEW FANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-10-08 Cont ID  
Sent By tklarge Date 2015-10-08 Time 15:02 Rev Time 0.00
Received By tklarge Date 2015-10-08 Time 12:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-01-15 Cont ID  
Sent By skennedy Date 2016-01-15 Time 16:47 Rev Time 0.00
Received By skennedy Date 2016-01-15 Time 16:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-01-15 Cont ID  
Sent By eschneid Date 2016-01-15 Time 17:05 Rev Time 0.25
Received By eschneid Date 2016-01-15 Time 17:05 Sent To  
Notes
2016-01-15 17:06:59THE REFERENCED SHEETS HAVE BEEN REMOVED FROM THE
 APPROVED PLANS. THE UPDATED SHEETS SHALL BE SUBMITTED
 AS PART OF A REVISION PRIOR TO THE C.O. OF THE HOTEL.
2016-01-15 15:12:02ES TO ADD A PASS RESULT AS DENIED SHEETS HAVE BEEN
 REMOVED..

Review Stop Z ZONING
Rev No 1 Status F Date 2015-11-12 Cont ID  
Sent By eschneid Date 2015-11-12 Time 19:06 Rev Time 8.00
Received By eschneid Date 2015-11-12 Time 19:06 Sent To  
Notes
2015-11-12 19:07:23FAILED
  
 1) SHEETS C4.01 AND C4.01A SHALL BE REVISED IN
 ACCORDANCE WITH THE PLANS APPROVED AS PART OF THE
 PENDING MINOR PD AMENDMENT FOR THE LOADING AREA.
  
 2) SHEET A0.03 SHALL BE REVISED IN ACCORDANCE WITH THE
 PLANS APPROVED AS PART OF THE PENDING MINOR PD
 AMENDMENT FOR THE SURFACE PARKING LOT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2015-10-01 15:21:2610/1/15