Plan Review Details - Permit 15091199
| Plan Review Stops For Permit 15091199 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2015-10-23 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-10-23 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-10-22 |
Time |
16:15 |
Sent To |
FIRE |
|
| Notes |
| 2015-10-23 10:11:47 | A PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN | | | SATISFACTORILY ADDRESSED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-10-14 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-10-14 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-10-13 |
Time |
14:29 |
Sent To |
I |
|
| Notes |
| 2015-10-14 11:07:09 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE | | | ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH | | | REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE | | | REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED | | | SHALL BE RESUBMITTED FOR ANOTHER REVIEW. | | | 1. NFPA 72, SECTION 17.14.6 REQUIRES THAT THE MANUAL | | | PULL STATION DEVICES BE LOCATION NO MORE THAN 5? FROM | | | THE EXITS IN THE PATH OF EGRESS. | | | 2. THE LOWER LOBBY AS INDICATED ON THE DRAWINGS IS | | | MISSING MANUAL INITIATION DEVICES, (PULL STATIONS). | | | 3. IF THE REASON FOR THE PLACEMENT OF THESE DEVICES SO | | | DISTANT FROM THE DOOR WAY IS DUE TO GLASS FACADE, | | | PLEASE NOTE THAT THE CODE DOES NOT MAKE AN EXCEPTION | | | FOR THIS. | | | 4. THOUGH THE ADDITION OF THE MISSING PULL STATIONS | | | WILL NOT ALTER THE CALCS, THEY WILL ALTER RISER | | | DIAGRAM. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2015-10-27 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2015-10-27 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2015-10-27 |
Time |
13:01 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2015-09-28 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2015-09-28 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2015-09-28 |
Time |
13:27 |
Sent To |
E |
|
| Notes |
| 2015-10-27 13:01:19 | PERMIT # 15091199 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | REPEAT COMMENTS | | | PERMIT APPROVED PROVISO: | | | | | | 1) ADDITIONAL DEVICES ARE NEEDED FOR THE DINING | | | TERRACE. | | | | | | SUE ELLEN CALDERON | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 644-7326 | | 2015-09-28 13:28:50 | PERMIT # 15091199 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PERMIT APPROVED PROVISO: | | | | | | 1) ADDITIONAL DEVICES ARE NEEDED FOR THE DINING | | | TERRACE. | | | | | | SUE ELLEN CALDERON | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 644-7326 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-10-27 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2015-10-27 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2015-10-21 |
Time |
10:02 |
Sent To |
|
|
| Notes |
| 2015-10-22 10:02:44 | ROUTED TO MALBARRAN |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-10-14 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-10-14 |
Time |
11:08 |
Rev Time |
|
| Received By |
albarran |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2015-10-14 11:09:55 | 10/14/15 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR | | | NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "A". MA |
|
|
|
Account Summary | Usage Policy | Privacy Policy