| Plan Review Stops For Permit 15091145 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2015-11-09 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2015-11-09 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2015-11-09 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2015-11-09 13:44:10 | CHRISTOPHER S. THROOP, C.B.O. | | | BLDG. PLANS EXAMINER ? PX3169 | | | (561) 805-6718 | | | [email protected] | | | | | | PLEASE PROVIDE FLORIDA PRODUCT APPROVALS FOR WINDOWS | | | AND DOORS | | | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS. | | | | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-10-21 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-10-21 |
Time |
18:22 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-10-21 |
Time |
18:22 |
Sent To |
|
|
| Notes |
| 2015-10-21 18:24:14 | 1ST REVIEW: FBC 2014 5TH ED. | | | | | | DISCUSSION WITH THE APPLICANT INDICATES NEW OR | | | ADDITIONAL DESIGN DOCUMENTS WILL BE PROVIDED. THIS IS | | | AN INCOMPLETE REVIEW BASED ON AN INADEQUATE SUBMITTAL. | | | | | | PROVIDE MINIMUM PLAN REVIEW CRITERIA PER FBC 107. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2015-11-13 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-11-13 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-11-13 |
Time |
17:25 |
Sent To |
|
|
| Notes |
| 2015-11-13 17:37:39 | 2ND REVIEW: FBC 2014 5TH ED. RESIDENTIAL | | | | | | THE PLAN HAS CONFLICTS IN THAT IT CITES THE 2008 NEC | | | AND THE 2011 NEC. NEITHER APPLY AS THE CODE IN EFFECT | | | IS REFERENCED ABOVE AND ELECTRICAL REQUIREMENTS ARE | | | CONTAINED THEREIN IN PART VIII - ELECTRICAL. | | | | | | PROVIDE THE FOLLOWING MINIMUM PLAN REVIEW INFORMATION: | | | | | | FBC- 107.3.5.3 ELECTRIC SERVICE RISER WITH WIRE SIZES, | | | CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE LOAD | | | CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON | | | FLOOR PLAN. | | | | | | THIS IS AN INCOMPLETE REVIEW BASED UPON AN INADEQUATE | | | SUBMITTAL. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-10-21 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-10-21 |
Time |
18:20 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-10-21 |
Time |
18:20 |
Sent To |
|
|
| Notes |
| 2015-10-21 18:22:20 | 1ST REVIEW: FBC 2014 5TH ED. | | | | | | FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE | | | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE | | | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON | | | FLOOR PLAN. | | | | | | THIS IS AN INCOMPLETE REVIEW BASED UPON AN INADEQUATE | | | SUBMITTAL. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-11-13 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-11-13 |
Time |
17:28 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-11-05 |
Time |
09:36 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-10-21 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-10-21 |
Time |
18:22 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-09-24 |
Time |
16:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2015-11-13 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-11-13 |
Time |
17:22 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-11-13 |
Time |
17:22 |
Sent To |
|
|
| Notes |
| 2015-11-13 17:25:38 | 2ND REVIEW: FBC 2014 5TH ED. RESIDENTIAL, EXISTING | | | BUILDINGS | | | | | | SECOND REVIEW IS A REPEAT OF THE FIRST REVIEW AS THERE | | | IS NO CHANGE IN THE APPLICATION OR RE-SUBMITTED PLANS | | | ADDRESSING THE FIRST REVIEW COMMENTS. | | | | | | THIS PROJECT IS A RENOVATION AS DEFINED IN THE FBC | | | ENERGY VOLUME THEREFORE PROVIDE THE FOLLOWING: | | | | | | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 | | | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO | | | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. | | | | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW | | | SUPPLY DUCTS PER FBC-R M16 & BATH EXHAUST PER FBC-R | | | M15. | | | FBC-ER403.6.1 PROVIDE AN EQUIPMENT SIZING CALCULATION | | | | | | THIS IS AN INCOMPLETE REVIEW BASED ON INSUFFICIENT | | | DETAIL PROVIDED. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-10-21 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-10-21 |
Time |
18:16 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-10-21 |
Time |
18:16 |
Sent To |
|
|
| Notes |
| 2015-10-21 18:16:50 | 1ST REVIEW: FBC 2014 5TH ED. | | | | | | THIS PROJECT IS A RENOVATION AS DEFINED IN THE FBC | | | ENERGY VOLUME THEREFORE PROVIDE THE FOLLOWING: | | | | | | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 | | | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO | | | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. | | | | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW | | | SUPPLY DUCTS PER FBC-R M16 & BATH EXHAUST PER FBC-R | | | M15. | | | FBC-ER403.6.1 PROVIDE AN EQUIPMENT SIZING CALCULATION | | | | | | THIS IS AN INCOMPLETE REVIEW BASED ON INSUFFICIENT | | | DETAIL PROVIDED. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2015-11-07 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-11-13 |
Time |
17:28 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-11-07 |
Time |
07:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2015-10-03 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-10-03 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-10-03 |
Time |
10:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2015-11-09 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2015-11-09 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2015-11-09 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2015-11-09 13:47:09 | CHRISTOPHER S. THROOP, C.B.O. | | | BLDG. PLANS EXAMINER ? PX3169 | | | (561) 805-6718 | | | [email protected] | | | | | | PLEASE PROVIDE FLORIDA PRODUCT APPROVAL FOR ROOF | | | SYSTEM. | | | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2015-10-21 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-10-21 |
Time |
18:13 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-10-21 |
Time |
18:13 |
Sent To |
|
|
| Notes |
| 2015-10-21 18:16:19 | 1ST REVIEW: FBC 2014 5TH ED. | | | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY | | | FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING | | | SUBMITTALS. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | | | | |
|
|