Plan Review Details - Permit 15091145
Plan Review Stops For Permit 15091145
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-11-09 Cont ID  
Sent By cthroop Date 2015-11-09 Time 13:40 Rev Time 0.00
Received By cthroop Date 2015-11-09 Time 13:40 Sent To  
Notes
2015-11-09 13:44:10CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PLEASE PROVIDE FLORIDA PRODUCT APPROVALS FOR WINDOWS
 AND DOORS
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-21 Cont ID  
Sent By skennedy Date 2015-10-21 Time 18:22 Rev Time 0.00
Received By skennedy Date 2015-10-21 Time 18:22 Sent To  
Notes
2015-10-21 18:24:141ST REVIEW: FBC 2014 5TH ED.
  
 DISCUSSION WITH THE APPLICANT INDICATES NEW OR
 ADDITIONAL DESIGN DOCUMENTS WILL BE PROVIDED. THIS IS
 AN INCOMPLETE REVIEW BASED ON AN INADEQUATE SUBMITTAL.
  
 PROVIDE MINIMUM PLAN REVIEW CRITERIA PER FBC 107.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-11-13 Cont ID  
Sent By skennedy Date 2015-11-13 Time 17:27 Rev Time 0.00
Received By skennedy Date 2015-11-13 Time 17:25 Sent To  
Notes
2015-11-13 17:37:392ND REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 THE PLAN HAS CONFLICTS IN THAT IT CITES THE 2008 NEC
 AND THE 2011 NEC. NEITHER APPLY AS THE CODE IN EFFECT
 IS REFERENCED ABOVE AND ELECTRICAL REQUIREMENTS ARE
 CONTAINED THEREIN IN PART VIII - ELECTRICAL.
  
 PROVIDE THE FOLLOWING MINIMUM PLAN REVIEW INFORMATION:
  
 FBC- 107.3.5.3 ELECTRIC SERVICE RISER WITH WIRE SIZES,
 CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE LOAD
 CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
  
 THIS IS AN INCOMPLETE REVIEW BASED UPON AN INADEQUATE
 SUBMITTAL.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-10-21 Cont ID  
Sent By skennedy Date 2015-10-21 Time 18:20 Rev Time 0.00
Received By skennedy Date 2015-10-21 Time 18:20 Sent To  
Notes
2015-10-21 18:22:201ST REVIEW: FBC 2014 5TH ED.
  
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
  
 THIS IS AN INCOMPLETE REVIEW BASED UPON AN INADEQUATE
 SUBMITTAL.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-13 Cont ID  
Sent By skennedy Date 2015-11-13 Time 17:28 Rev Time 0.00
Received By skennedy Date 2015-11-05 Time 09:36 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-21 Cont ID  
Sent By skennedy Date 2015-10-21 Time 18:22 Rev Time 0.00
Received By skennedy Date 2015-09-24 Time 16:02 Sent To  
Notes
2015-09-24 16:02:53R01

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-11-13 Cont ID  
Sent By skennedy Date 2015-11-13 Time 17:22 Rev Time 0.00
Received By skennedy Date 2015-11-13 Time 17:22 Sent To  
Notes
2015-11-13 17:25:382ND REVIEW: FBC 2014 5TH ED. RESIDENTIAL, EXISTING
 BUILDINGS
  
 SECOND REVIEW IS A REPEAT OF THE FIRST REVIEW AS THERE
 IS NO CHANGE IN THE APPLICATION OR RE-SUBMITTED PLANS
 ADDRESSING THE FIRST REVIEW COMMENTS.
  
 THIS PROJECT IS A RENOVATION AS DEFINED IN THE FBC
 ENERGY VOLUME THEREFORE PROVIDE THE FOLLOWING:
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW
 SUPPLY DUCTS PER FBC-R M16 & BATH EXHAUST PER FBC-R
 M15.
 FBC-ER403.6.1 PROVIDE AN EQUIPMENT SIZING CALCULATION
  
 THIS IS AN INCOMPLETE REVIEW BASED ON INSUFFICIENT
 DETAIL PROVIDED.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-10-21 Cont ID  
Sent By skennedy Date 2015-10-21 Time 18:16 Rev Time 0.00
Received By skennedy Date 2015-10-21 Time 18:16 Sent To  
Notes
2015-10-21 18:16:501ST REVIEW: FBC 2014 5TH ED.
  
 THIS PROJECT IS A RENOVATION AS DEFINED IN THE FBC
 ENERGY VOLUME THEREFORE PROVIDE THE FOLLOWING:
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW
 SUPPLY DUCTS PER FBC-R M16 & BATH EXHAUST PER FBC-R
 M15.
 FBC-ER403.6.1 PROVIDE AN EQUIPMENT SIZING CALCULATION
  
 THIS IS AN INCOMPLETE REVIEW BASED ON INSUFFICIENT
 DETAIL PROVIDED.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-11-07 Cont ID  
Sent By skennedy Date 2015-11-13 Time 17:28 Rev Time 0.00
Received By tklarge Date 2015-11-07 Time 07:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-10-03 Cont ID  
Sent By tklarge Date 2015-10-03 Time 10:15 Rev Time 0.00
Received By tklarge Date 2015-10-03 Time 10:03 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2015-11-09 Cont ID  
Sent By cthroop Date 2015-11-09 Time 13:44 Rev Time 0.00
Received By cthroop Date 2015-11-09 Time 13:44 Sent To  
Notes
2015-11-09 13:47:09CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PLEASE PROVIDE FLORIDA PRODUCT APPROVAL FOR ROOF
 SYSTEM.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-10-21 Cont ID  
Sent By skennedy Date 2015-10-21 Time 18:13 Rev Time 0.00
Received By skennedy Date 2015-10-21 Time 18:13 Sent To  
Notes
2015-10-21 18:16:191ST REVIEW: FBC 2014 5TH ED.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING
 SUBMITTALS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  