| Plan Review Stops For Permit 15090992 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2015-11-03 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-11-03 |
Time |
13:18 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-11-03 |
Time |
12:52 |
Sent To |
I |
|
| Notes |
| 2015-11-03 13:19:58 | THE ELECTRICAL SCOPE OF THIS PERMIT IS LIMITED TO | | | TAKING THE DESCRIBED ELECTRICAL FEED TO AN EXISTING | | | POINT OF CONNECTION OUTSIDE THE CLASSIFIED LOCATION AND | | | TO REWIRE THE EMERGENCY STOP BUTTON. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-10-22 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-10-22 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-10-22 |
Time |
15:30 |
Sent To |
I |
|
| Notes |
| 2015-10-22 15:40:51 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION | | | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION | | | OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION | | | OF THE FBC, (FLORIDA BUILDING CODE) 2014, AS APPLICABLE | | | AND BELOW ARE THE DEFICIENCIES NOTED. | | | 1. THERE IS NO ELECTRICAL INFORMATION ACCOMPANYING THIS | | | SUBMITTAL FOR A REVIEW. | | | 2. PLEASE PROVIDE DETAILED INFORMATION ON THE PROPOSED | | | WORK. | | | 3. I WILL NEED A COMPLETE SITE SPECIFIC RISER DIAGRAM | | | INCLUDING ALL GROUNDING AND CONDUCTOR SIZING. | | | 4. YOU SHALL SUBMIT A PANEL SCHEDULE WITH RESPECTIVE | | | LOAD CALCS. | | | 5. INDICATE THE LOCATION OF ALL MAIN DISCONNECTS. | | | 6. AL EQUIPMENT SHALL HAVE THE ARC-FLASH WARNING | | | LABELS. | | | THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN | | | MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED | | | FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED | | | TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG | | | WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE, | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY | | | APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2015-10-09 |
|
|
Cont ID |
|
| Sent By |
Walker |
Date |
2015-10-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-10-06 |
Time |
|
Sent To |
|
|
| Notes |
| 2015-10-09 08:39:38 | PLANS AS SUBMITTED PASSED. | | | WILL REQUIRE SLAB DETAIL AT TIME OF INSPECTION |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2015-11-03 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-11-03 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-11-03 |
Time |
11:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2015-09-26 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-09-26 |
Time |
05:54 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-09-26 |
Time |
05:23 |
Sent To |
|
|
| Notes |
| 2015-09-26 04:21:28 | 1) SUBMIT TWO COPIES OF THE FUEL DISPENSER | | | MANUFACTURER'S INSTALLATION INSTRUCTIONS PER NFPA 58, | | | 2011 EDITION, SEC. 6.24.3.1. | | | 2) NFPA 58 SEC. 6.24.3.6 - PIPING AND THE DISPENSING | | | HOSE SHALL BE PROVIDED WITH HYDROSTATIC RELIEF VALVES | | | IN ACCORDANCE WITH SECTION 6.13 OF NFPA 58. | | | 3) NFPA 58-2011 - SEC. 6.24.3.7 - PROTECTION AGAINST | | | TRESPASSING AND TAMPERING SHALL BE IN ACCORDANCE WITH | | | 6.18.4. SHOW ON THE PLAN HOW THE TANKS WILL BE | | | PROTECTED AGAINST UNAUTHORIZED ACCESS. | | | 4) NFPA 58-2011 - SEC. 6.24.3.12 - ALL DISPENSERS | | | EITHER SHALL BE INSTALLED ON A CONCRETE FOUNDATION OR | | | SHALL BE PART OF A COMPLETE STORAGE AND DISPENSING UNIT | | | MOUNTED ON A COMMON BASE AND INSTALLED IN ACCORDANCE | | | WITH 6.6.3.1 (G). SHOW COMPLIANCE WITH TABLE 6.6.3 (A). | | | 5) PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE PER | | | THE WPB AMEND. TO FBC SEC. 107.2.1.4. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-11-03 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-11-03 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-11-03 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2015-11-03 13:22:23 | 11/3/15 SUCCESSFULLY BEEN THROUGH ALL REVIEWS. | | | CONTRACTOR NOTIFIED VIA EMAIL. SENT TO SMALL READY BIN | | | "A". MA |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-10-22 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-10-22 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-09-23 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2015-10-22 15:44:11 | 10/22/15 FAILED ELECTRICAL REVIEW FOR LACK OF | | | SUPPORTING DOCUMENTATION. CONTRACTOR NOTIFIED VIA | | | EMAIL. SENT TO SMALL DENIED BIN "A".MA | | 2015-09-23 12:57:54 | B03 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2015-11-03 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-11-03 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-11-03 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2015-11-03 11:23:11 | REVIEW STOP ENTERED BY MISTAKE.TKL. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2015-10-02 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-10-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2015-10-02 |
Time |
|
Sent To |
|
|
| Notes |
| 2015-10-01 15:35:48 | 10/1/15 |
|
|