Plan Review Details - Permit 15090991
Plan Review Stops For Permit 15090991
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-10-21 Cont ID  
Sent By shill Date 2015-10-21 Time 09:13 Rev Time 0.00
Received By shill Date 2015-10-21 Time 09:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-24 Cont ID  
Sent By tklarge Date 2015-09-26 Time 05:20 Rev Time 0.00
Received By shill Date 2015-09-24 Time 13:42 Sent To P
Notes
2015-09-24 13:44:39****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 1507, PROVIDE INFORMATION AS TO HOW SIZING HAS
 BEEN DETERMINED.
  
 2. FBC 107, PROVIDE A PLAN WHICH SHOWS LOCATION OF
 GUTTERS, DOWNSPOUTS, AND SCUPPERS. INCLUDE LINEAR FOOT
 ON PLAN.
  
 3. FBC 109, PROVIDE A COPY OF THE CONTRACT FOR THIS
 JOB.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-21 Cont ID  
Sent By shill Date 2015-10-21 Time 09:13 Rev Time 0.00
Received By shill Date 2015-10-21 Time 08:44 Sent To  
Notes
2015-10-21 08:44:10TO TL DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-26 Cont ID  
Sent By tklarge Date 2015-09-26 Time 05:20 Rev Time 0.00
Received By tklarge Date 2015-09-23 Time 12:48 Sent To B
Notes
2015-09-24 13:45:069/24 TO PLUMBING BOX
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-10-21 Cont ID  
Sent By tklarge Date 2015-10-21 Time 09:12 Rev Time 0.00
Received By tklarge Date 2015-10-21 Time 09:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-09-26 Cont ID  
Sent By tklarge Date 2015-09-26 Time 05:20 Rev Time 0.00
Received By tklarge Date 2015-09-26 Time 05:03 Sent To  
Notes
2015-09-26 03:11:201) SUBMIT 2 COPIES OF A ROOF PLAN (CAN BE HAND DRAWN)
 THAT SHOWS THE LOCATION OF THE SCUPPERS, GUTTERS
 (INCLUDE GUTTER DIMENSIONS) AND DOWNSPOUTS. WPB AMEND.
 TO FBC SEC. 107.2.1.
 2) SUBMIT INFORMATION AS TO HOW THE SIZING OF THE
 SCUPPERS, DOWNSPOUTS AND GUTTERS WAS ATTAINED. SHOW THE
 SQUARE FOOTAGE AREA OF THE ROOF DRAINED BY THE GUTTERS,
 SCUPPERS AND DOWNSPOUTS.COMPLY WITH 2014 FBC-PLUMBING,
 SEC.1106.6, 1106.7.
 3) INDICATE ON THE PLAN WHERE THE DOWNSPOUTS TERMINATE.
 DOWNSPOUTS SHALL TERMINATE A MINIMUM OF 1 FOOT FROM THE
 BUILDING SIDEWALL PER 2014 FBC SEC.1503.7.
 4) THE SIZING SHALL BE DONE BASED ON A 5 INCH PER HOUR
 RAINFALL RATE PER FIGURE 1106.1 OF 2014 FBC-PLUMBING.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  