| Plan Review Stops For Permit 15090984 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2016-02-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-02-26 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-02-25 |
Time |
17:25 |
Sent To |
P |
|
| Notes |
| 2016-02-26 16:44:17 | APPROVED WITH EXCEPTIONS. | | | SUBMIT TWO SETS OF PRODUCT APPROVALS THAT HAVE BEEN | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD FOR THE ARCHED TOP WOOD FRONT DOOR. THE DOOR | | | WILL ALSO REQUIRE HISTORIC APPROVAL. DCA RULE 9N-3 & | | | FBC 107.3.4.1 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2016-01-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-01-19 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-01-14 |
Time |
18:41 |
Sent To |
|
|
| Notes |
| 2016-01-19 15:02:35 | PLAN REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO COPIES OF A SURVEY OF THE PROPERTY. FBC | | | 107.2.1 | | | | | | 2) SUBMIT TWO SETS OF ENERGY COMPLIANCE FORMS FOR THE | | | ADDITION. SHOW COMPLIANCE WITH 2014 FBC ENERGY | | | CONSERVATION SECT. R101.4.3 & R103.2 BY SUBMITTING THE | | | PROPER CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING | | | FORMS 402 OR 405. (THE FORMS ARE REQUIRED TO BE SIGNED | | | AND DATED BY THE OWNER/AGENT.) | | | | | | 3) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED | | | TO INSTALL THE CONCRETE ROOF TILE AND RESIST THE | | | REQUIRED OVERTURN MOMENT. THIS CAN BE ACCOMPLISHED BY | | | CIRCLING THE APPROPRIATE METHOD ON THE PRODUCT | | | APPROVAL. IF A ROOF TILE ADHESIVE WILL BE USED, SUBMIT | | | TWO SETS OF THE PRODUCT APPROVALS FOR IT. | | | | | | 4) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE | | | WINDOWS, DOORS AND ROOFING MATERIALS THAT HAVE BEEN | | | APPROVED BY THE HISTORIC PLANNER AND HAVE BEEN REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. DCA | | | RULE 9N-3 AND FBC 107.3.4.1 | | | | | | 5) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE ARCHED | | | TOP DOORS THAT HAVE BEEN REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD. DCA RULE 9N-3 AND | | | FBC 107.3.4.1 | | | | | | 6) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE SINGLE | | | HUNG WINDOWS THAT HAVE BEEN REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD. DCA RULE 9N-3 AND | | | FBC 107.3.4.1 | | | | | | 7) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A | | | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW | | | COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-10-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-10-30 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-10-29 |
Time |
18:39 |
Sent To |
|
|
| Notes |
| 2015-10-30 11:48:50 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SHEET S-3 OF THE PLANS HAS SEVERAL REFERENCES TO THE | | | 2010 FBC. THE FBC FIFTH EDITION (2014) WENT INTO EFFECT | | | ON JUNE 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR | | | AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND | | | REFERENCE THE FBC FIFTH EDITION. THE 2011 NEC IS THE | | | CORRECT EDITION AND THE 2008 NEC IS SPECIFIED ON SHEET | | | A-1.0. | | | | | | 2) SUBMIT TWO COPIES OF A SURVEY OF THE PROPERTY. FBC | | | 107.2.1 | | | | | | 3) A SEPARATE PERMIT, APPLICATION AND REVIEW IS | | | REQUIRED FOR THE WALL AND GATE RELOCATION. | | | | | | 4) A SEPARATE PERMIT, APPLICATION AND REVIEW IS | | | REQUIRED FOR THE CANVAS AWNINGS. | | | | | | 5) SUBMIT TWO SETS OF ENERGY COMPLIANCE FORMS FOR THE | | | ADDITION. SHOW COMPLIANCE WITH 2014 FBC ENERGY | | | CONSERVATION SECT. R101.4.3 & R103.2 BY SUBMITTING THE | | | PROPER CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING | | | FORMS 402 OR 405. | | | | | | 6) DETAIL 3 ON SHEET A4.1 APPEARS TO SHOW ROOF TILE ON | | | FLAT ROOF AREAS, WHICH IS NOT ALLOWED BY THE BUILDING | | | CODE. THE MINIMUM SLOPE FOR CONCRETE OR CLAY ROOF TILE | | | IS 2:12 PER FBC-R905.3.2. | | | | | | 7) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE ON | | | SHEET S-3. FBC-R301.2.1 | | | | | | 8) THE ROOF AND WALL PRESSURES ON SHEET S-3 APPEAR TO | | | BE INCORRECT FOR A STRUCTURE LOCATED IN EXPOSURE C WITH | | | A 132 MPH VASD WIND SPEED. SPECIFY THE ROOF SLOPE FOR | | | THE ROOF COMPONENT AND CLADDING PRESSURE TABLE ON THE | | | PLANS. FBC-R301.2.1 | | | | | | 9) ON SHEET S-2 THE LOWER ROOF FRAMING PLAN THERE ARE | | | TAGS WITH C/S3 AND D/S3. THERE ARE NO DETAILS ON SHEET | | | S3 THAT ARE LABELED C OR D. | | | | | | 10) THERE APPEARS TO BE SOME ERRORS IN THE TAGS ON THE | | | PARTIAL UPPER ROOF FRAMING ON SHEET S-2. THERE IS ONE | | | WITH 786 OVER A 1 RATHER THAN THE LETTER A. THERE IS | | | ONE WITH A D OVER 270 AND AN 8 OVER 270. THESE LAST TWO | | | APPEAR TO HAVE THE UPLIFT AND CONNECTOR REVERSED. | | | PLEASE CLARIFY. | | | | | | 11) SUBMIT TWO SETS OF MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS FOR THE CARLISLE WATERPROOFING SYSTEM. FBC | | | 107.2.1.3 | | | | | | 12) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED | | | TO INSTALL THE CONCRETE ROOF TILE AND RESIST THE | | | REQUIRED OVERTURN MOMENT. THIS CAN BE ACCOMPLISHED BY | | | CIRCLING THE APPROPRIATE METHOD ON THE PRODUCT | | | APPROVAL. IF A ROOF TILE ADHESIVE WILL BE USED, SUBMIT | | | TWO SETS OF THE PRODUCT APPROVALS FOR IT. | | | | | | 13) THE PVC - VINYL WIDOWS AND DOORS, WHOSE PRODUCT | | | APPROVALS WERE SUBMITTED, ARE NOT APPROVED TO BE USED | | | IN THIS PROJECT BY THE HISTORIC PLANNER. SUBMIT TWO | | | SETS OF PRODUCT APPROVALS FOR THE WINDOWS AND DOORS | | | THAT HAVE BEEN APPROVED BY THE HISTORIC PLANNER AND | | | HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. FBC 107.3.4.1 | | | | | | 14) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE ARCHED | | | TOP WOOD ENTRY DOOR THAT HAVE BEEN REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD. FBC | | | 107.3.4.1 | | | | | | 15) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT | | | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW | | | COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2016-02-25 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-02-25 |
Time |
17:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-02-25 |
Time |
17:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2016-01-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-01-15 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-01-15 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2016-01-15 09:37:33 | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRIC | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PLAN SHEET E-1 HAS A NOTE THAT AHU-2 IS TO BE | | | RELOCATED. SPECIFY THE NEW LOCATION ON THE PLANS. FBC | | | 107.2.1 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2015-10-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-10-29 |
Time |
18:36 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-10-29 |
Time |
18:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2016-02-27 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-02-27 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-02-27 |
Time |
07:27 |
Sent To |
HIST |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2016-01-07 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-01-07 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-01-07 |
Time |
06:46 |
Sent To |
|
|
| Notes |
| 2016-01-07 08:42:30 | 1) THE MINIMUM SIZE OF THE GAS LINE TO THE COOKTOP | | | SHALL BE 3/4" PER 2014 FBCR TABLE G2413.4 (1). THE GAS | | | RISER SHOWS THE DROP TO THE COOKTOP AS 3/4" BUT IT IS | | | BEING SUPPLIED BY A 1/2" LINE. THE ENTIRE LINE TO THE | | | COOKTOP HAS TO BE 3/4", NOT JUST A SECTION OF IT. 2ND | | | REQUEST. | | | 2) SCH. 40 GALVANIZED CANNOT BE USED BELOW GROUND PER | | | 2014 FBCR SEC. G2415.11, G2415.11.1, G2415.11.2. THE | | | NOTE IS STILL ON THE PLAN.INDICATE ON THE PLAN THE TYPE | | | OF PIPE MATERIAL TO BE USED BELOW GROUND. WPB AMEND. TO | | | FBC SEC. 107.2.1.2ND REQUEST. | | | 3) SHOW THE SIZES OF ALL OF THE EXISTING GAS PIPING. | | | WITH THE ADDED TANKLESS WATER HEATER, THE EXISTING GAS | | | PIPING MAY BE UNDERSIZED AND MAY HAVE TO BE INCREASED. | | | THE MINIMUM SIZE GAS SUPPLY LINE SUPPLYING 248,000 | | | BTU'S AT PRESSURE BELOW 2 PSI PER TABLE G2413.4 (1) OF | | | THE 2014 FBCR SHALL BE 1 1/4" FOR THE DISTANCE SHOWN ON | | | THE PLANS. | | | 4) SOME CORRECTIONS WERE MADE TO ONLY ONE COPY OF THE | | | PLANS. PLEASE MAKE CORRECTIONS TO BOTH SETS OF PLANS. | | | 5) VENTING SHALL BE IN ACCORDANCE WITH THE 2014 FUEL | | | GAS CODE, NOT THE 2010. REVISE NOTE ON THE PLAN. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2015-10-04 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-10-04 |
Time |
08:35 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-10-04 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2015-10-04 08:27:17 | 1) THE MINIMUM SIZE OF THE GAS LINE TO THE COOKTOP | | | SHALL BE 3/4" PER 2014 FBCR TABLE G2413.4 (1). | | | 2) SCH. 40 GALVANIZED CANNOT BE USED BELOW GROUND PER | | | 2014 FBCR SEC. G2415.11, G2415.11.1, G2415.11.2. | | | 3) GAS APPLIANCES SHALL BE LISTED AND LABELED.2014 FBCR | | | G2404.3. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
3 |
Status |
P |
Date |
2016-03-01 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2016-03-01 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2016-03-01 |
Time |
09:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
F |
Date |
2016-01-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-01-19 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-01-19 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2016-01-19 15:40:10 | PRODUCT APPROVALS FOR SINGLE HUNG WINDOWS AND ARCHED | | | TOP DOORS WERE NOT SUBMITTED. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-10-07 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2015-10-07 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2015-10-07 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2015-10-14 09:38:43 | VINYL WINDOWS NOT PERMITTED IN HISTORIC DISTRICTS. | | 2015-09-25 14:09:12 | 9/25/15 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-03-01 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2016-03-01 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2016-02-05 |
Time |
15:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-01-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-01-19 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-01-06 |
Time |
10:38 |
Sent To |
|
|
| Notes |
| 2016-01-06 10:38:50 | TLARGE'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-10-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-10-30 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-09-22 |
Time |
11:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
4 |
Status |
P |
Date |
2016-03-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-03-07 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-03-07 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2016-03-07 13:41:05 | MU2016-5197, NO IMPACT FEES WERE DUE. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
F |
Date |
2016-02-25 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-02-25 |
Time |
18:25 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-02-25 |
Time |
18:25 |
Sent To |
|
|
| Notes |
| 2016-02-25 18:25:16 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2016-01-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-01-14 |
Time |
18:46 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-01-14 |
Time |
18:41 |
Sent To |
|
|
| Notes |
| 2016-01-14 18:46:25 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2015-10-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-10-30 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-10-30 |
Time |
13:34 |
Sent To |
|
|
| Notes |
| 2015-10-30 13:35:38 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2016-02-25 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-02-25 |
Time |
18:56 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-02-25 |
Time |
18:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2016-01-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-01-15 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-01-15 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2016-01-15 10:12:58 | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 2) THE ENERGY CALCULATIONS ARE REQUIRED TO BE SIGNED BY | | | THE OWNER/AGENT. FBC R101.5.1.1.1 | | | | | | 3) THE ELECTRICAL PLAN INDICATES THAT AHU-2 IS TO BE | | | RELOCATED BUT DOES NOT SPECIFY THE NEW LOCATION. FBC | | | 107.2.1 | | | | | | 4) A COPY OF AN APPLICATION WAS ATTACHED TO THE | | | MECHANICAL. THE MECHANICAL SUB-PERMIT APPLICATION IS | | | REQUIRED TO HAVE THE ORIGINAL SIGNATURES AND BE | | | SUBMITTED TO THE PERMIT CLERKS AT THE FRONT COUNTER SO | | | THAT THE CONTRACTOR'S INFORMATION CAN BE VERIFIED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-10-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-10-29 |
Time |
18:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-10-29 |
Time |
18:37 |
Sent To |
|
|
| Notes |
| 2015-10-29 18:38:53 | NO MECHANICAL WORK IS INDICATED ON THE PLANS. HOWEVER, | | | AN EQUIPMENT SIZING SUMMARY WAS SUBMITTED FOR THE 2ND | | | FLOOR MASTER AHU-2 AND THE SECOND FLOOR ELECTRICAL PLAN | | | SHOWS AHU-3 AS EXISTING IN THE ATTIC. PLEASE CLARIFY. | | | FBC107.2.1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2015-10-04 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-10-04 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-10-04 |
Time |
08:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2015-10-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-10-30 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-10-30 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2015-10-30 13:38:03 | ROOFING MATERIALS | | | | | | 1) ENTEGRA, GALENA SPANISH "S" CONCRETE ROOF TILE |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2015-10-07 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2015-10-07 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2015-10-07 |
Time |
14:23 |
Sent To |
|
|
| Notes |
|
|