Plan Review Details - Permit 15090984
Plan Review Stops For Permit 15090984
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-02-26 Cont ID  
Sent By rmcdouga Date 2016-02-26 Time 16:49 Rev Time 0.00
Received By rmcdouga Date 2016-02-25 Time 17:25 Sent To P
Notes
2016-02-26 16:44:17APPROVED WITH EXCEPTIONS.
 SUBMIT TWO SETS OF PRODUCT APPROVALS THAT HAVE BEEN
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD FOR THE ARCHED TOP WOOD FRONT DOOR. THE DOOR
 WILL ALSO REQUIRE HISTORIC APPROVAL. DCA RULE 9N-3 &
 FBC 107.3.4.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-01-19 Cont ID  
Sent By rmcdouga Date 2016-01-19 Time 15:13 Rev Time 0.00
Received By rmcdouga Date 2016-01-14 Time 18:41 Sent To  
Notes
2016-01-19 15:02:35PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO COPIES OF A SURVEY OF THE PROPERTY. FBC
 107.2.1
  
 2) SUBMIT TWO SETS OF ENERGY COMPLIANCE FORMS FOR THE
 ADDITION. SHOW COMPLIANCE WITH 2014 FBC ENERGY
 CONSERVATION SECT. R101.4.3 & R103.2 BY SUBMITTING THE
 PROPER CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING
 FORMS 402 OR 405. (THE FORMS ARE REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER/AGENT.)
  
 3) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE CONCRETE ROOF TILE AND RESIST THE
 REQUIRED OVERTURN MOMENT. THIS CAN BE ACCOMPLISHED BY
 CIRCLING THE APPROPRIATE METHOD ON THE PRODUCT
 APPROVAL. IF A ROOF TILE ADHESIVE WILL BE USED, SUBMIT
 TWO SETS OF THE PRODUCT APPROVALS FOR IT.
  
 4) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 WINDOWS, DOORS AND ROOFING MATERIALS THAT HAVE BEEN
 APPROVED BY THE HISTORIC PLANNER AND HAVE BEEN REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. DCA
 RULE 9N-3 AND FBC 107.3.4.1
  
 5) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE ARCHED
 TOP DOORS THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. DCA RULE 9N-3 AND
 FBC 107.3.4.1
  
 6) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE SINGLE
 HUNG WINDOWS THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. DCA RULE 9N-3 AND
 FBC 107.3.4.1
  
 7) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-30 Cont ID  
Sent By rmcdouga Date 2015-10-30 Time 16:48 Rev Time 0.00
Received By rmcdouga Date 2015-10-29 Time 18:39 Sent To  
Notes
2015-10-30 11:48:50PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHEET S-3 OF THE PLANS HAS SEVERAL REFERENCES TO THE
 2010 FBC. THE FBC FIFTH EDITION (2014) WENT INTO EFFECT
 ON JUNE 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR
 AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE FBC FIFTH EDITION. THE 2011 NEC IS THE
 CORRECT EDITION AND THE 2008 NEC IS SPECIFIED ON SHEET
 A-1.0.
  
 2) SUBMIT TWO COPIES OF A SURVEY OF THE PROPERTY. FBC
 107.2.1
  
 3) A SEPARATE PERMIT, APPLICATION AND REVIEW IS
 REQUIRED FOR THE WALL AND GATE RELOCATION.
  
 4) A SEPARATE PERMIT, APPLICATION AND REVIEW IS
 REQUIRED FOR THE CANVAS AWNINGS.
  
 5) SUBMIT TWO SETS OF ENERGY COMPLIANCE FORMS FOR THE
 ADDITION. SHOW COMPLIANCE WITH 2014 FBC ENERGY
 CONSERVATION SECT. R101.4.3 & R103.2 BY SUBMITTING THE
 PROPER CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING
 FORMS 402 OR 405.
  
 6) DETAIL 3 ON SHEET A4.1 APPEARS TO SHOW ROOF TILE ON
 FLAT ROOF AREAS, WHICH IS NOT ALLOWED BY THE BUILDING
 CODE. THE MINIMUM SLOPE FOR CONCRETE OR CLAY ROOF TILE
 IS 2:12 PER FBC-R905.3.2.
  
 7) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE ON
 SHEET S-3. FBC-R301.2.1
  
 8) THE ROOF AND WALL PRESSURES ON SHEET S-3 APPEAR TO
 BE INCORRECT FOR A STRUCTURE LOCATED IN EXPOSURE C WITH
 A 132 MPH VASD WIND SPEED. SPECIFY THE ROOF SLOPE FOR
 THE ROOF COMPONENT AND CLADDING PRESSURE TABLE ON THE
 PLANS. FBC-R301.2.1
  
 9) ON SHEET S-2 THE LOWER ROOF FRAMING PLAN THERE ARE
 TAGS WITH C/S3 AND D/S3. THERE ARE NO DETAILS ON SHEET
 S3 THAT ARE LABELED C OR D.
  
 10) THERE APPEARS TO BE SOME ERRORS IN THE TAGS ON THE
 PARTIAL UPPER ROOF FRAMING ON SHEET S-2. THERE IS ONE
 WITH 786 OVER A 1 RATHER THAN THE LETTER A. THERE IS
 ONE WITH A D OVER 270 AND AN 8 OVER 270. THESE LAST TWO
 APPEAR TO HAVE THE UPLIFT AND CONNECTOR REVERSED.
 PLEASE CLARIFY.
  
 11) SUBMIT TWO SETS OF MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR THE CARLISLE WATERPROOFING SYSTEM. FBC
 107.2.1.3
  
 12) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE CONCRETE ROOF TILE AND RESIST THE
 REQUIRED OVERTURN MOMENT. THIS CAN BE ACCOMPLISHED BY
 CIRCLING THE APPROPRIATE METHOD ON THE PRODUCT
 APPROVAL. IF A ROOF TILE ADHESIVE WILL BE USED, SUBMIT
 TWO SETS OF THE PRODUCT APPROVALS FOR IT.
  
 13) THE PVC - VINYL WIDOWS AND DOORS, WHOSE PRODUCT
 APPROVALS WERE SUBMITTED, ARE NOT APPROVED TO BE USED
 IN THIS PROJECT BY THE HISTORIC PLANNER. SUBMIT TWO
 SETS OF PRODUCT APPROVALS FOR THE WINDOWS AND DOORS
 THAT HAVE BEEN APPROVED BY THE HISTORIC PLANNER AND
 HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. FBC 107.3.4.1
  
 14) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE ARCHED
 TOP WOOD ENTRY DOOR THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. FBC
 107.3.4.1
  
 15) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-02-25 Cont ID  
Sent By rmcdouga Date 2016-02-25 Time 17:45 Rev Time 0.00
Received By rmcdouga Date 2016-02-25 Time 17:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-01-15 Cont ID  
Sent By rmcdouga Date 2016-01-15 Time 09:22 Rev Time 0.00
Received By rmcdouga Date 2016-01-15 Time 09:22 Sent To  
Notes
2016-01-15 09:37:332ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRIC
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PLAN SHEET E-1 HAS A NOTE THAT AHU-2 IS TO BE
 RELOCATED. SPECIFY THE NEW LOCATION ON THE PLANS. FBC
 107.2.1
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-10-29 Cont ID  
Sent By rmcdouga Date 2015-10-29 Time 18:36 Rev Time 0.00
Received By rmcdouga Date 2015-10-29 Time 18:36 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2016-02-27 Cont ID  
Sent By tklarge Date 2016-02-27 Time 07:56 Rev Time 0.00
Received By tklarge Date 2016-02-27 Time 07:27 Sent To HIST
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-01-07 Cont ID  
Sent By tklarge Date 2016-01-07 Time 09:35 Rev Time 0.00
Received By tklarge Date 2016-01-07 Time 06:46 Sent To  
Notes
2016-01-07 08:42:301) THE MINIMUM SIZE OF THE GAS LINE TO THE COOKTOP
 SHALL BE 3/4" PER 2014 FBCR TABLE G2413.4 (1). THE GAS
 RISER SHOWS THE DROP TO THE COOKTOP AS 3/4" BUT IT IS
 BEING SUPPLIED BY A 1/2" LINE. THE ENTIRE LINE TO THE
 COOKTOP HAS TO BE 3/4", NOT JUST A SECTION OF IT. 2ND
 REQUEST.
 2) SCH. 40 GALVANIZED CANNOT BE USED BELOW GROUND PER
 2014 FBCR SEC. G2415.11, G2415.11.1, G2415.11.2. THE
 NOTE IS STILL ON THE PLAN.INDICATE ON THE PLAN THE TYPE
 OF PIPE MATERIAL TO BE USED BELOW GROUND. WPB AMEND. TO
 FBC SEC. 107.2.1.2ND REQUEST.
 3) SHOW THE SIZES OF ALL OF THE EXISTING GAS PIPING.
 WITH THE ADDED TANKLESS WATER HEATER, THE EXISTING GAS
 PIPING MAY BE UNDERSIZED AND MAY HAVE TO BE INCREASED.
 THE MINIMUM SIZE GAS SUPPLY LINE SUPPLYING 248,000
 BTU'S AT PRESSURE BELOW 2 PSI PER TABLE G2413.4 (1) OF
 THE 2014 FBCR SHALL BE 1 1/4" FOR THE DISTANCE SHOWN ON
 THE PLANS.
 4) SOME CORRECTIONS WERE MADE TO ONLY ONE COPY OF THE
 PLANS. PLEASE MAKE CORRECTIONS TO BOTH SETS OF PLANS.
 5) VENTING SHALL BE IN ACCORDANCE WITH THE 2014 FUEL
 GAS CODE, NOT THE 2010. REVISE NOTE ON THE PLAN.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-10-04 Cont ID  
Sent By tklarge Date 2015-10-04 Time 08:35 Rev Time 0.00
Received By tklarge Date 2015-10-04 Time 08:27 Sent To  
Notes
2015-10-04 08:27:171) THE MINIMUM SIZE OF THE GAS LINE TO THE COOKTOP
 SHALL BE 3/4" PER 2014 FBCR TABLE G2413.4 (1).
 2) SCH. 40 GALVANIZED CANNOT BE USED BELOW GROUND PER
 2014 FBCR SEC. G2415.11, G2415.11.1, G2415.11.2.
 3) GAS APPLIANCES SHALL BE LISTED AND LABELED.2014 FBCR
 G2404.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2016-03-01 Cont ID  
Sent By fmittner Date 2016-03-01 Time 09:02 Rev Time 0.00
Received By fmittner Date 2016-03-01 Time 09:02 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2016-01-19 Cont ID  
Sent By rmcdouga Date 2016-01-19 Time 15:37 Rev Time 0.00
Received By rmcdouga Date 2016-01-19 Time 15:37 Sent To  
Notes
2016-01-19 15:40:10PRODUCT APPROVALS FOR SINGLE HUNG WINDOWS AND ARCHED
 TOP DOORS WERE NOT SUBMITTED.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2015-10-07 Cont ID  
Sent By fmittner Date 2015-10-07 Time 14:22 Rev Time 0.00
Received By fmittner Date 2015-10-07 Time 14:22 Sent To  
Notes
2015-10-14 09:38:43VINYL WINDOWS NOT PERMITTED IN HISTORIC DISTRICTS.
2015-09-25 14:09:129/25/15

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-01 Cont ID  
Sent By lmarchan Date 2016-03-01 Time 10:25 Rev Time 0.00
Received By lmarchan Date 2016-02-05 Time 15:16 Sent To  
Notes
2016-02-05 15:16:10R25

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-19 Cont ID  
Sent By rmcdouga Date 2016-01-19 Time 15:38 Rev Time 0.00
Received By rmcdouga Date 2016-01-06 Time 10:38 Sent To  
Notes
2016-01-06 10:38:50TLARGE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-30 Cont ID  
Sent By rmcdouga Date 2015-10-30 Time 16:48 Rev Time 0.00
Received By rmcdouga Date 2015-09-22 Time 11:01 Sent To  
Notes
2015-09-23 11:02:47R20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2016-03-07 Cont ID  
Sent By rmcdouga Date 2016-03-07 Time 13:39 Rev Time 0.00
Received By rmcdouga Date 2016-03-07 Time 13:39 Sent To  
Notes
2016-03-07 13:41:05MU2016-5197, NO IMPACT FEES WERE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2016-02-25 Cont ID  
Sent By rmcdouga Date 2016-02-25 Time 18:25 Rev Time 0.00
Received By rmcdouga Date 2016-02-25 Time 18:25 Sent To  
Notes
2016-02-25 18:25:16BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-01-14 Cont ID  
Sent By rmcdouga Date 2016-01-14 Time 18:46 Rev Time 0.00
Received By rmcdouga Date 2016-01-14 Time 18:41 Sent To  
Notes
2016-01-14 18:46:25BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-10-30 Cont ID  
Sent By rmcdouga Date 2015-10-30 Time 13:34 Rev Time 0.00
Received By rmcdouga Date 2015-10-30 Time 13:34 Sent To  
Notes
2015-10-30 13:35:38BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-02-25 Cont ID  
Sent By rmcdouga Date 2016-02-25 Time 18:56 Rev Time 0.00
Received By rmcdouga Date 2016-02-25 Time 18:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-01-15 Cont ID  
Sent By rmcdouga Date 2016-01-15 Time 10:01 Rev Time 0.00
Received By rmcdouga Date 2016-01-15 Time 10:01 Sent To  
Notes
2016-01-15 10:12:58 
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) THE ENERGY CALCULATIONS ARE REQUIRED TO BE SIGNED BY
 THE OWNER/AGENT. FBC R101.5.1.1.1
  
 3) THE ELECTRICAL PLAN INDICATES THAT AHU-2 IS TO BE
 RELOCATED BUT DOES NOT SPECIFY THE NEW LOCATION. FBC
 107.2.1
  
 4) A COPY OF AN APPLICATION WAS ATTACHED TO THE
 MECHANICAL. THE MECHANICAL SUB-PERMIT APPLICATION IS
 REQUIRED TO HAVE THE ORIGINAL SIGNATURES AND BE
 SUBMITTED TO THE PERMIT CLERKS AT THE FRONT COUNTER SO
 THAT THE CONTRACTOR'S INFORMATION CAN BE VERIFIED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-10-30 Cont ID  
Sent By rmcdouga Date 2015-10-29 Time 18:37 Rev Time 0.00
Received By rmcdouga Date 2015-10-29 Time 18:37 Sent To  
Notes
2015-10-29 18:38:53NO MECHANICAL WORK IS INDICATED ON THE PLANS. HOWEVER,
 AN EQUIPMENT SIZING SUMMARY WAS SUBMITTED FOR THE 2ND
 FLOOR MASTER AHU-2 AND THE SECOND FLOOR ELECTRICAL PLAN
 SHOWS AHU-3 AS EXISTING IN THE ATTIC. PLEASE CLARIFY.
 FBC107.2.1

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-10-04 Cont ID  
Sent By tklarge Date 2015-10-04 Time 08:27 Rev Time 0.00
Received By tklarge Date 2015-10-04 Time 08:06 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2015-10-30 Cont ID  
Sent By rmcdouga Date 2015-10-30 Time 13:36 Rev Time 0.00
Received By rmcdouga Date 2015-10-30 Time 13:36 Sent To  
Notes
2015-10-30 13:38:03ROOFING MATERIALS
  
 1) ENTEGRA, GALENA SPANISH "S" CONCRETE ROOF TILE

Review Stop Z ZONING
Rev No 1 Status P Date 2015-10-07 Cont ID  
Sent By fmittner Date 2015-10-07 Time 14:23 Rev Time 0.00
Received By fmittner Date 2015-10-07 Time 14:23 Sent To  
Notes
***NONE***