Plan Review Details - Permit 15090967
Plan Review Stops For Permit 15090967
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-12-21 Cont ID  
Sent By cthroop Date 2015-12-21 Time 08:57 Rev Time 0.00
Received By cthroop Date 2015-12-21 Time 08:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-11-17 Cont ID  
Sent By cthroop Date 2015-11-17 Time 11:32 Rev Time 0.00
Received By cthroop Date 2015-11-17 Time 11:32 Sent To  
Notes
2015-11-17 11:37:47CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 SUBMITTAL MUST BE SIGNED BY DESIGNER. PROVIDE 2 COPIES.
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
2015-11-13 07:26:55LIGHT POLE SUBMITTAL RECEIVED TO BE ASSOCIATED WITH
 APPLICATION TO ALLOW FOR SECOND REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-03 Cont ID  
Sent By cthroop Date 2015-11-03 Time 11:46 Rev Time 0.00
Received By cthroop Date 2015-11-03 Time 11:46 Sent To FIRE
Notes
2015-11-03 11:58:34CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER PX3169
 (561) 805-6718
 [email protected]
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION FOR THE
 PROPOSED LIGHT POLES: A) WIND SPEED DESIGN; B)
 FOUNDATION & ANCHORAGE.
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 1801.1 SCOPE.
 THE PROVISIONS OF THIS CHAPTER SHALL APPLY TO BUILDING
 AND FOUNDATION SYSTEMS.
 1801.2 DESIGN BASIS.
 ALLOWABLE BEARING PRESSURES, ALLOWABLE STRESSES AND
 DESIGN FORMULAS PROVIDED IN THIS CHAPTER SHALL BE USED
 WITH THE ALLOWABLE STRESS DESIGN LOAD COMBINATIONS
 SPECIFIED IN SECTION 1605.3. THE QUALITY AND DESIGN OF
 MATERIALS USED STRUCTURALLY IN EXCAVATIONS AND
 FOUNDATIONS SHALL COMPLY WITH THE REQUIREMENTS
 SPECIFIED IN CHAPTERS 16, 19, 21, 22 AND 23 OF THIS
 CODE. EXCAVATIONS AND FILLS SHALL ALSO COMPLY WITH
 CHAPTER 33.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-02-02 Cont ID  
Sent By albarran Date 2016-02-02 Time 15:11 Rev Time 0.00
Received By albarran Date 2016-02-02 Time 14:25 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2016-01-22 Cont ID  
Sent By albarran Date 2016-01-22 Time 10:06 Rev Time 0.00
Received By albarran Date 2016-01-22 Time 09:10 Sent To I
Notes
2016-01-22 10:22:29YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED
 DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL
 REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED
 BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO
 SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE
 REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION
 OF ANY PREVIOUS COMMENTS. THESE PLANS HAVE BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE) AND THE FBC, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS IN EFFECT AT THE TIME OF SUBMITTAL.
  
 1. ALL EXTERIOR LIGHTING SHALL COMPLY WITH FBC?E
 SECTIONS C405.6.1 & C405.6.2
  
 TO THIS COMMENT YOU PROVIDED A PHOTOMETRIC PLAN, BUT
 FAIL TO INCLUDE THE POWER DENSITY ALLOWANCE CHART
 SHOWING COMPLIANCE.
  
 2. PROVIDE WIRING DETAIL OR CALCULATIONS INDICATING
 COMPLIANCE WITH FBC?E405.7.3
  
 YOU DID PROVIDE A RISER DIAGRAM AS REQUIRED, BUT DO NOT
 INDICATE ON THE RISER DIAGRAM DETAIL OR ON THE
 ELECTRICAL PLAN ANY PROTECTION FOR THIS EQUIPMENT. NEC
 110.27(B) REQUIRES THAT THERE BE PROTECTION FROM
 PHYSICAL DAMAGE FOR THIS EQUIPMENT. FURTHERMORE, YOUR
 RISER DIAGRAM CONFLICTS WITH ?ELECTRICAL GENERAL NOTES?
 #2 WHICH PROHIBIT THE USE OF ALUMINUM CONDUCTORS.
  
 3. YOU SHALL PROVIDE A FIXTURE SCHEDULE AND AN
 ABBREVIATION AND SYMBOLS LEGEND
  
 THE FIXTURE SCHEDULE SAID TO BE ON SHEET GE1 IS
 MISSING. THE FIXTURE SCHEDULE SHALL BE ON THE PLAN SET.
  
 4. UNLESS PRIOR ARRANGEMENTS ARE MADE WITH THE
 ELECTRICAL INSPECTOR, ALL TRENCHING SHALL REMAIN OPEN
 FOR INSPECTION. NO SITE TUBES ARE ALLOWED.
  
 FOR FULL COMPLIANCE WITH THIS, PLEASE INCLUDE A NOTE ON
 THE PLANS STATING THAT TRENCHES WILL REMAIN OPEN UNTIL
 INSPECTED.
  
  
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE
 NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-12-17 Cont ID  
Sent By albarran Date 2015-12-17 Time 16:57 Rev Time 0.00
Received By albarran Date 2015-12-17 Time 14:57 Sent To B
Notes
2015-12-17 16:57:11THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. ALL EXTERIOR LIGHTING SHALL COMPLY WITH FBC-E
 SECTIONS C405.6.1 & C405.6.2
 2. PROVIDE WIRING DETAIL OR CALCULATIONS INDICATING
 COMPLIANCE WITH FBC-E405.7.3
 3. YOU SHALL PROVIDE A FIXTURE SCHEDULE AND AN
 ABBREVIATION AND SYMBOLS LEGEND
 4. UNLESS PRIOR ARRANGEMENTS ARE MADE WITH THE
 ELECTRICAL INSPECTOR, ALL TRENCHING SHALL REMAIN OPEN
 FOR INSPECTION. NO SITE TUBES ARE ALLOWED.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-10-08 Cont ID  
Sent By albarran Date 2015-10-08 Time 12:26 Rev Time 0.00
Received By albarran Date 2015-10-08 Time 12:18 Sent To Z
Notes
2015-10-08 12:32:14I INITIALLY STAMPED THE DRAWINGS FOR THE SITE LIGHTING
 ELECTRIC, BUT HAD TO FAIL THE APPLICATION DUE TO
 INCOMPLETE SUBMITTAL. YOU SHALL PROVIDE SPECS ON THE
 PROPOSED LUMINARIES AND SUPPORTING POLES AS WELL AS FOR
 THE GATE OPENERS AND READERS. YOU SHALL ALSO INCLUDE A
 DETAIL ON THE MOUNTING AND GROUNDING OF THE POLES. THE
 APPLICATION ALSO MENTIONED CAR CHARGERS AND NO MENTION
 OF CAR CHARGERS APPEARS ON THE PANELS NOR IS THE
 REQUIRED LITERATURE FOR THE CHARGERS INCLUDED. A BLDG
 STOP WILL BE ADDED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2015-11-18 Cont ID  
Sent By wjolin Date 2015-11-18 Time 13:31 Rev Time 0.00
Received By wjolin Date 2015-11-18 Time 13:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-02-02 Cont ID  
Sent By albarran Date 2016-02-02 Time 15:13 Rev Time 0.00
Received By albarran Date 2016-01-26 Time 10:03 Sent To Z
Notes
2016-02-02 15:14:472/2/16 PERMIT READY FOR ISSUANCE. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT FILE TO SMALL READY BIN F. MA
2016-01-27 10:04:09SENT TO ESCHNEIDER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-01-22 Cont ID  
Sent By albarran Date 2016-01-22 Time 10:25 Rev Time 0.00
Received By albarran Date 2016-01-05 Time 13:07 Sent To  
Notes
2016-01-22 10:25:091/22/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. FILE SENT TO LARGE DENIED DRAWER
 "F". MA
2016-01-05 13:09:12RESUB ROUTED TO ESCHNEIDER VIA SGRAHAM'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-21 Cont ID  
Sent By cthroop Date 2015-12-21 Time 08:56 Rev Time 0.00
Received By cthroop Date 2015-12-14 Time 10:08 Sent To  
Notes
2015-12-14 10:08:56RESUB ROUTED TO ESCHNEIDER VIA SGRAHAM'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-19 Cont ID  
Sent By albarran Date 2015-11-17 Time 12:33 Rev Time 0.00
Received By cpuell Date 2015-09-23 Time 14:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2016-01-29 Cont ID  
Sent By albarran Date 2016-02-02 Time 15:14 Rev Time 0.00
Received By eschneid Date 2016-01-29 Time 09:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2016-01-05 Cont ID  
Sent By eschneid Date 2016-01-05 Time 17:06 Rev Time 0.50
Received By eschneid Date 2016-01-05 Time 17:06 Sent To E
Notes
2016-01-05 17:40:02PASSED W/PROVISO
  
 1) PRIOR TO THE 104 FINAL INSPECTION, PROVIDE REVISED
 PHOTOMETRIC DRAWING BASED ON ACTUAL POLE LOCATIONS.
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2015-12-16 Cont ID  
Sent By eschneid Date 2015-12-16 Time 11:16 Rev Time 0.25
Received By eschneid Date 2015-12-16 Time 11:16 Sent To E
Notes
2015-12-16 11:33:38FAILED
  
 1) THE BASE PARKING LOT LAYOUT IS NOT THE ONE APPROVED
 THROUGH THE PPRC REVIEW. THE PARKING LOT HAS SHIFTED
 WEST APPROXIMATELY 3.5 FEET; THEREFORE THE LIGHT POLE
 LOCATIONS ARE NOT SHOWN IN THE CORRECT LOCATIONS.
  
 2) ZONING STAFF IS UNCLEAR AS TO THE LOCATION OF THE
 CAR CHARGING STATIONS. PLEASE CLEARLY ANNOTATE THEM ON
 THE PLAN.
  
 3) HOW TALL ARE THE CHARGING STATIONS?
  
 4) NO LIGHT POLE OR FIXTURE DETAILS PROVIDED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2015-10-23 Cont ID  
Sent By eschneid Date 2015-10-23 Time 10:28 Rev Time 0.25
Received By eschneid Date 2015-10-23 Time 10:27 Sent To  
Notes
2015-10-23 12:05:35FAILED
  
 1) THE MINOR AMENDMENT TO CONVERT THE GARAGE TO A
 SURFACE PARKING LOT HAS NOT BEEN APPROVED. THE LIGHT
 POLE AND ENTRY GATE LOCATIONS MAY CHANGE BASED ON HOW
 THE COMMENTS FROM THE MINOR AMENDMENT ARE ADDRESSED, SO
 ZONING WILL NOT APPROVE THIS PERMIT UNTIL THE MINOR
 AMENDMENT PLANS ARE APPROVED.
  
 2) PROVIDE THE LIGHT POLE AND FIXTURE DETAILS. THESE
 WERE INCLUDED AS PART OF THE MINOR AMENDMENT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.