| 2015-10-07 17:29:03 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15090952 |
| | ADD: 5300 EAST AVE. / 2ND FLOOR ALTERATIONS |
| | CONT: TRILLIUM CONSTRUCTION |
| | TEL: (561)371-6825 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. OCT. 07/2015 |
| | ACTION: DENIED |
| | |
| | 1) THE 1ST FLOOR LIFE SAFETY SHEET SUBMITTED FOR |
| | REFERENCE ONLY INDICATES THE 1ST FLOOR IS A I-2 |
| | OCCUPANCY WITH 120 SLEEPING COMPARTMENTS. SHEET S0.1 |
| | THE WIND DESIGN CRITERIA LIST THE WIND AT 169 VULT, |
| | BUILDING RISK CATEGORY AS II AND EXPOSURE AS B. |
| | PLEASE SEE THE 2014 FBC-B TABLE 1604.5. I-2 OCCUPANCIES |
| | WITH AN OCCUPANT LOAD OF 120 SLEEPING COMPARTMENTS. |
| | THIS CLASSIFIES THE BUILDING RISK CATEGORY AS A III, |
| | WITH 180 MPH WIND VULT, AND THE EXPOSURE IS A C |
| | EXPOSURE OPEN AREAS TO THE WEST 150 FEET WIDE AND 600 |
| | FEET LONG FBC-B 1609.4.3. PLEASE UPDATE WIND DESIGN |
| | CRITERIA AND ASSOCIATED PRESURES. |
| | |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 1.2. RISK CATEGORY. |
| | |
| | 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. |
| | |
| | 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| | M2). |
| | |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | |
| | 2) THE WINDOW PRODUCT APPROVAL SUBMITTED NOA |
| | 14-0203.01. 2014 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 3) SHEET D1 NOTE # 11 INDICATES THE REMOVAL OF EXISITNG |
| | RELIEF VENT AND RELOCATING IN A NEW POSITION. M1.3 |
| | INDICATES THE REMOVAL AND NEW LOCATION TO THE 2ND |
| | FLOOR. SHEET M2.1 NOTR # 8 INDICATES THERE TO BE A FIRE |
| | DAMPER ACCESS DOOR ON THE ADJACENT WALL OF THE |
| | CORRIDOR. THE DUCT THAT COMES UP FROM THE FIRST FLOOR |
| | IS WITHIN A CHASED WALL OF THE BREAKROOM THAT BACKS UP |
| | TO THE COMMON COORIDOR. |
| | THE ARCHITECTURAL PLANS DO NOT INDICATE THAT ANY OF |
| | THESE WALLS ARE GOING TO REQUIRE A FIRE DAMPER ACCESS |
| | DOOR. |
| | |
| | 2014 FBC-B 717.4 ACCESS AND IDENTIFICATION. FIRE AND |
| | SMOKE DAMPERS SHALL BE PROVIDED WITH AN APPROVED MEANS |
| | OF ACCESS, WHICH IS LARGE ENOUGH TO PERMIT INSPECTION |
| | AND MAINTENANCE OF THE DAMPER AND ITS OPERATING PARTS. |
| | THE ACCESS SHALL NOT AFFECT THE INTEGRITY OF |
| | FIRE-RESISTANCE-RATED ASSEMBLIES. THE ACCESS OPENINGS |
| | SHALL NOT REDUCE THE FIRE-RESISTANCE RATING OF THE |
| | ASSEMBLY. ACCESS POINTS SHALL BE PERMANENTLY IDENTIFIED |
| | ON THE EXTERIOR BY A LABEL HAVING LETTERS NOT LESS THAN |
| | 1/2 INCH (12.7 MM) IN HEIGHT READING: FIRE/SMOKE |
| | DAMPER, SMOKE DAMPER OR FIRE DAMPER. ACCESS DOORS IN |
| | DUCTS SHALL BE TIGHT FITTING AND SUITABLE FOR THE |
| | REQUIRED DUCT CONSTRUCTION. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |