Plan Review Details - Permit 15090929
Plan Review Stops For Permit 15090929
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-05-11 Cont ID  
Sent By skennedy Date 2016-05-11 Time 10:27 Rev Time 0.00
Received By skennedy Date 2016-05-11 Time 10:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-03-28 Cont ID  
Sent By jwitmer Date 2016-03-28 Time 08:53 Rev Time 0.00
Received By jwitmer Date 2016-03-28 Time 08:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-12-16 Cont ID  
Sent By jwitmer Date 2015-12-16 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2015-12-16 Time 07:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-05 Cont ID  
Sent By jwitmer Date 2015-10-05 Time 06:45 Rev Time  
Received By jwitmer Date 2015-10-05 Time 06:01 Sent To  
Notes
2015-10-05 06:33:41BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090929
 ADD: 1044 26TH ST.
 CONT: JOSEPH W. SCHUESSLER, INC.
 TEL: (561)635-6712
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT. 5/2015
 ACTION: DENIED
  
 1) SHEET 1SHOWS A BOILER WITHIN NEW 1 HOUR FIRE RATED
 WALLS. THE PLANS DO NOT PROVIDE AT WHAT PRESSURE AND
 THE HORSEPOWER OF THE MOTOR. IF THE BOILER IS OVER 15
 PSI AND 10 HORSEPOWER THEN IT WOULD REQUIRE EITHER A 1
 HOUR FIRE RATED ROOM OR AN AUTOMATIC FIRE SPRINKLER
 SYSTEM. 2014 FBC-B TABLE 509. THE PLANS DO INDICATE A 1
 HOUR FIRE RATED ROOM, IF THE BOILERS OPERATING PRESSURE
 IS OVER 15 PSI AND MOTOR IS OVER 10 HORSEPOWER THEN THE
 DOOR WILL NEED TO BE 3/4 HR RATING IN COMPLIANCE WITH
 TABLE 716.5.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-05-09 Cont ID  
Sent By vperez Date 2016-05-09 Time 16:02 Rev Time 0.00
Received By vperez Date 2016-05-09 Time 16:01 Sent To  
Notes
2016-05-09 16:06:36TO BIN C21- ITS ON JIMS LIST

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2016-04-05 Cont ID  
Sent By albarran Date 2016-04-05 Time 10:24 Rev Time 0.00
Received By albarran Date 2016-04-05 Time 09:21 Sent To I
Notes
2016-04-05 10:25:05NO ELECTRICAL DATA PROVIDED. I SPOKE WITH THE
 CONTRACTOR AND HE WILL SUBMIT AN ELECTRICAL SHEET AS
 REQUIRED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-01-14 Cont ID  
Sent By albarran Date 2016-01-14 Time 10:19 Rev Time 0.00
Received By albarran Date 2016-01-14 Time 10:06 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-10-02 Cont ID  
Sent By albarran Date 2015-10-02 Time 10:06 Rev Time 0.00
Received By albarran Date 2015-10-02 Time 09:55 Sent To M
Notes
2015-10-02 10:14:06PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE SECOND ELECTRICAL REVIEW OF
 THE ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE
 REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED
 SHALL BE RESUBMITTED FOR ANOTHER REVIEW.
 1. YOU SHALL SUBMIT ELECTRICAL DRAWINGS INDICATING THE
 SCOPE OF WORK.
 2. THE SPECS ON THE BOILER DO NOT INDICATE WHICH OF THE
 CHOICES FOR THE PUMPS ETC.
 3. YOU SHALL PROVIDE THE REQUIRED LIGHTING AND SERVICE
 OUTLET FOR THE NEW BOILER ROOM.
 4. YOU WILL SUBMIT A SIMPLE FEEDER SCHEDULE (RISER
 DIAGRAM) INDICATING THE WIRE SIZE, INSULATION AND ALL
 APPLICABLE COMPONENTS OF THE INSTALLATION.
 5.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2016-05-03 Cont ID  
Sent By J.Walker Date 2016-05-03 Time   Rev Time 0.00
Received By   Date 2016-05-02 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-03-16 Cont ID  
Sent By pleduc Date 2016-03-16 Time   Rev Time 0.00
Received By pleduc Date 2016-03-16 Time 15:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-12-17 Cont ID  
Sent By J.Walker Date 2015-12-17 Time   Rev Time 0.00
Received By   Date 2015-12-16 Time   Sent To  
Notes
2015-12-17 10:49:41WILL REQUIRE BALLARDS INSTALLED IF OCCUPANT PLANS ON
 PARKING VEHICLES WITHIN THE STRUCTURE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-09-24 Cont ID  
Sent By Walker Date 2015-09-24 Time   Rev Time 0.00
Received By   Date 2015-09-23 Time   Sent To E
Notes
2015-09-24 07:39:30WILL REQUIRE BALLARDS AROUND EQUIPMENT IF VEHICLES WILL
 BE PARKED IN THE STRUCTURE

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2016-05-02 Cont ID  
Sent By tklarge Date 2016-05-02 Time 07:33 Rev Time 0.00
Received By tklarge Date 2016-05-02 Time 04:56 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2016-03-18 Cont ID  
Sent By tklarge Date 2016-03-18 Time 12:46 Rev Time 0.00
Received By tklarge Date 2016-03-18 Time 12:35 Sent To  
Notes
2016-03-18 13:02:241) SHT. M-100 INDICATES A TYPE "B" VENT FOR THE
 BOILER.THE GAS CODE REFERS TO CATEGORY I APPLIANCES
 BEING USED WITH A TYPE B VENT AND THESE TYPE OF
 APPLIANCES OPERATE UNDER A NONPOSITIVE VENT STATIC
 PRESURE. THE REPORT FROM VAN-PACKER INDICATES THAT THE
 BOILER IS A FORCED DRAFT SYSTEM AND THEREFORE CANNOT BE
 USED WITH A TYPE B VENT.
 2) PLEASE COMPILE THE PLANS INTO TWO COMPLETE SETS OF
 PLANS FOR REVIEW.
 3) THE 12" VENT IS UNDERSIZED FOR THE BOILER IN
 ACCORDANCE WITH TABLE 504.2 (1) OF 2014 FUEL GAS CODE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-02-05 Cont ID  
Sent By tklarge Date 2016-02-05 Time 12:33 Rev Time 0.00
Received By tklarge Date 2016-02-05 Time 10:45 Sent To  
Notes
2016-02-05 10:46:451) SHT. P100 - PROPANE TANK HOLDOWN AREA - THE 2014 FBC
 HAS ADOPTED ASCE-10, NOT ASCE-98. REVISE.
 2) THE WIND LOAD IS 170 MPH, ULT DESIGN PER 2014 FBC
 SEC. 1609.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-12-20 Cont ID  
Sent By tklarge Date 2015-12-20 Time 10:07 Rev Time 0.00
Received By tklarge Date 2015-12-20 Time 08:33 Sent To  
Notes
2015-12-20 09:01:421) INDICATE ON THE PLAN THE VENTING CATEGORY OF THE
 BOILER IN ACCORDANCE WITH THE 2014 FBC-FUEL GAS SEC.
 202 (DEFINITIONS - VENTED APPLIANCE CATEGORIES).
 2) SHOW THE SIZE OF THE GAS VENT FOR THE BOILER. THE
 VENT SIZE SHALL COMPLY WITH SEC. 503.6.9 & TABLE
 504.2(2) IF THIS IS A CATEGORY I VENTED APPLIANCE. IF
 NOT A CATEGORY I APPLIANCE, SUBMIT MANUF. SPECS FOR THE
 REQUIRED VENT SIZING.
 3) SHT.P-200 - INDICATE THE TYPE OF MATERIAL, LOCATION
 AND DISTANCE ABOVE THE ROOF OF THE VENTS FOR THE
 BLOWDOWN TANKS FOR THE BOILER, FEEDWATER TANK AND THE
 AUTOCLAVE.SUBMIT MANUFACTURER'S SPECS FOR THE VENT
 INSTALLATION FOR THIS EQUIPMENT. WPB AMEND. TO FBC SEC.
 107.2.1.
 4) A TYPE B GAS VENT SHALL TERMINATE AT LEAST 5 FEET IN
 VERTICAL HEIGHT ABOVE THE APPLIANCE DRAFT HOOD OR FLUE
 COLLAR PER 2014 FGC SEC.503.6.5. SHOW ON THE THE PLANS.
 SHOW THE TOTAL HEIGHT OF THE GAS VENT.
 5) INDICATE ON THE PLAN IF THE BOILER IS A NATURAL
 DRAFT OR FAN ASSISTED VENT APPLIANCE. THIS WILL
 DETERMINE VENT SIZE IF A CATEGORY I VENTED APPLIANCE
 PER TABLE 504.2 (2).
 6) SUBMIT DETAILS FOR SUPPORT OF THE GAS VENT. 2014 FGC
 SEC.503.6.1.
 7) SHOW THE SIZE OF THE LP TANKS ON THE PLAN.WPB AMEND.
 TO FBC SEC. 107.2.1.
 8) SUBMIT ANCHORING DETAILS FOR THE LP TANKS.ANCHORING
 SHALL BE DDESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 BUILDING SEC.1609.
 9) SHT. P-100 - THE SIZE OF THE PIPING FROM THE LP
 TANKS IS SHOWN AS 3/4 INCH BUT THE BOILER SYSTEM DETAIL
 SHOWS 1 1/4 INCHES. CLARIFY.
 10) SUBMIT DETAILS FOR THE SEALING OF THE GAS PIPE
 PENETRATION THROUGH THE EXTERIOR WALL. WPB AMEND. TO
 FBC SEC. 107.2.1.
 11) SHOW THE LOCATION OF THE STEP DOWN GAS REGULATOR ON
 THE GAS DRAWING.WPB AMEND. TO FBC SEC. 107.2.1.
 12) SHOW THE DISTANCE FROM THE STEP DOWN REGULATOR TO
 THE MOST REMOTE OUTLET ON THE SYSTEM.WPB AMEND. TO FBC
 SEC. 107.2.1.
 13) SHOW THE PIPE SIZE FROM THE STEP DOWN REGULATOR TO
 THE EQUIPMENT.WPB AMEND. TO FBC SEC. 107.2.1.
 14) SHOW THE SIZE OF THE GAS PIPING FROM THE LP
 TANKS.WPB AMEND. TO FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-05-11 Cont ID  
Sent By skennedy Date 2016-05-11 Time 10:27 Rev Time 0.00
Received By skennedy Date 2016-04-25 Time 13:13 Sent To  
Notes
2016-04-25 13:13:15C21

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-04-05 Cont ID  
Sent By albarran Date 2016-04-05 Time 10:25 Rev Time 0.00
Received By albarran Date 2016-03-11 Time 15:42 Sent To  
Notes
2016-04-05 10:27:144/5/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA PHONE AND EMAIL. SENT FILE TO LARGE DENIED
 "J" DRAWER. MA
2016-03-11 15:42:36C03

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-11 Cont ID  
Sent By cpuell Date 2016-03-11 Time 15:40 Rev Time 0.00
Received By cpuell Date 2016-02-01 Time 12:42 Sent To  
Notes
2016-02-02 12:42:53RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-14 Cont ID  
Sent By albarran Date 2016-01-14 Time 10:21 Rev Time 0.00
Received By albarran Date 2015-12-11 Time 14:15 Sent To  
Notes
2016-01-14 10:40:081/14/16 PASSED ELECTRICAL BUT FAILED OTHER TRADE
 REVIEWS. CONTRACTOR NOTIFIED VIA EMAIL. SENT TO SMALL
 DENIED BIN "J". MA
  
2015-12-11 14:15:31B34

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-07 Cont ID  
Sent By ccole Date 2015-10-07 Time 08:27 Rev Time 0.00
Received By ccole Date 2015-09-22 Time 12:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2016-04-27 Cont ID  
Sent By ccole Date 2016-04-27 Time 12:24 Rev Time 0.00
Received By ccole Date 2016-04-27 Time 07:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2016-03-17 Cont ID  
Sent By ccole Date 2016-03-17 Time 13:47 Rev Time 0.00
Received By ccole Date 2016-03-17 Time 13:47 Sent To  
Notes
2016-03-17 14:13:174TH REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090929
 3/17/16
  
 1) THE RE-SUBMITTED M100 PLAN FROM GM CONSULTING
 ENGINEERS IS INDICATING THE BOILER FLUE IS A B-VENT
 TYPE FOR A CATEGORY 1 APPLIANCE, HOWEVER THE NEWLY
 SUBMITTED MANUFACTURER'S SPECIFCATIONS FROM VAN PACKER
 FOR THE BOILER SPECIFI A FORCED DRAFT VENTING SYSTEM .
 PLEASE SEE THE DEFINITIONS OF CATEGORY-1, TYPE B VENT,
 AND FORCED DRAFT IN SECTION 202 FBC-14 FUEL GAS:
  
 A) CATEGORY I. AN APPLIANCE THAT OPERATES WITH A
 NONPOSITIVE VENT STATIC PRESSURE AND WITH A VENT GAS
 TEMPERATURE THAT AVOIDS EXCESSIVE CONDENSATE PRODUCTION
 IN THE VENT.
 B) TYPE B VENT. A VENT LISTED AND LABELED FOR USE WITH
 APPLIANCES WITH DRAFT HOODS AND OTHER CATEGORY I
 APPLIANCES THAT ARE LISTED FOR USE WITH TYPE B VENTS.
 C) FORCED-DRAFT VENTING SYSTEM. A PORTION OF A VENTING
 SYSTEM USING A FAN OR OTHER MECHANICAL MEANS TO CAUSE
 THE REMOVAL OF FLUE OR VENT GASES UNDER POSITIVE STATIC
 VENT PRESSURE.
 IT WOULD APPEAR THAT THE M100 PLAN INDICATING A
 CATEGORY 1 APPLIANCE WITH A TYPE B VENT IS NOT
 CONSISTENT WITH THE MANUFACTURER'S SPECIFICATIONS FROM
 VAN-PACKER.
 2) PLEASE PROVIDE AN UPDATED WIND LOAD ENGINEERING
 SUBMITTAL FOR INSTALLATION OF THE FLUE ABOVE THE ROOF.
 THE PLAN IN THE FILE HAS BEEN MARKED VOID BY EITHER THE
 CONTRACTOR OR DESIGN PROFESSIONAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-02-03 Cont ID  
Sent By ccole Date 2016-02-03 Time 07:23 Rev Time 0.00
Received By ccole Date 2016-02-03 Time 07:23 Sent To  
Notes
2016-02-03 07:30:533RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090929
 2/3/15
  
 1) AFTER TWO PREVIOUS REVIEW REQUESTS, THE REVISED M100
 BOILER FLUE INSTALLATION DETAIL IS STILL NOT SHOWING A
 TOTAL RUN LENGTH OF THE VENT WHICH IS REQUIRED TO
 VERIFY CORRECT SIZING DAIMETER OF THE VENT. THE DRAWING
 IS "NTS" BUT BY APPEARANCES THE 12" DIAMETER VENT MAY
 BE UNDERSIZED FOR THE TOTAL LENGTH OF THE RUN. REFER TO
 TABLE 504.2(1) FBC-14 FUEL GAS AND REVISE THE PLAN TO
 SHOW THE TOTAL RUN LENGTH AND CORRECT VENT SIZING PER
 THE TABLE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-12-18 Cont ID  
Sent By ccole Date 2015-12-18 Time 16:00 Rev Time 0.00
Received By ccole Date 2015-12-18 Time 16:00 Sent To  
Notes
2015-12-18 16:03:021ST REVIEW 2014 MECHANICAL
 PERMIT #15090929
 12/18/15
  
 THE1ST REVIEW COMMENTS # 1 & 2 WERE NOT ADDRESSED. I AM
 NOT SEEING ANY DIMENSIONS INDICATING THE DIAMETER OF
 THE DUCT AND THE LENGTH OF THE DUCT RUN- SEE TABLE
 504.2(1) FBC-14 FUEL GAS. I HAVE COPIED COMMENTS #1 & 2
 BELOW: PLEASE REVISE THE PLANS TO INDICATE COMPLIANCE.
 1) WORKING CLEARANCE- REFER TO SECTION 1004.3 FBC-014
 MECHANICAL: "PASSAGEWAYS AROUND ALL SIDES OF BOILERS
 SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 18"
 UNLESS OTHERWISE APPROVED". THE SUBMITTED FLOOR PLAN
 DRAWING INDICATES NON-COMPLIANCE- PLEASE REVISE.
 2) PROVIDE DETAILS FOR EXHAUST VENTING OF THE BOILER:
 SHOW THE TYPE AND SIZE OF EXHAUST VENT, EXHAUST VENT
 RUN AND TERMINATION LOCATION, AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS.
 3) PLEASE PROVIDE A TIE-DOWN DETAIL FOR ANCHORING THE
 EXHAUST VENT ASSEMBLY ABOVE THE ROOF TO THE ROOF
 STRUCTURE.
 4) SUBMIT TWO COPIES OF THE MIAMI-DADE NOA FOR THE
 COMBUSTION AIR LOUVERS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-10-07 Cont ID  
Sent By ccole Date 2015-10-07 Time 07:32 Rev Time 0.00
Received By ccole Date 2015-10-07 Time 06:52 Sent To  
Notes
2015-10-07 08:26:591ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090929
 10/7/15
  
 1) WORKING CLEARANCE- REFER TO SECTION 1004.3 FBC-014
 MECHANICAL: "PASSAGEWAYS AROUND ALL SIDES OF BOILERS
 SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 18"
 UNLESS OTHERWISE APPROVED". THE SUBMITTED FLOOR PLAN
 DRAWING INDICATES NON-COMPLIANCE- PLEASE REVISE.
 2) PROVIDE DETAILS FOR EXHAUST VENTING OF THE BOILER:
 SHOW THE TYPE AND SIZE OF EXHAUST VENT, EXHAUST VENT
 RUN AND TERMINATION LOCATION, AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS.
 3) REFER TO SECTION 1006.6- SAFETY AND RELIEF VALVE
 DISCHARGE: "HIGH PRESSURE-STEAM SAFETY VALVES SHALL BE
 VENTED TO THE OUTSIDE OF THE STRUCTURE" PLEASE PROVIDE
 DETAILS.
 4) REFER TO SECTION 1008.1 AND INDICATE COMPLIANCE FOR
 THE REQUIRED BLOWOFF VALVE AND BLOWOFF VALVE DISCHARGE
 LOCATION.
 5) PROVIDE PIPING DIAGRAMS OR SCHEMATICS FOR THE BOILER
 AND OTHER EQUIPMENT ASSOCIATED WITH THE SYSTEM.
 INDICATE THE TYPES AND SIZES OF ALL PIPING, VALVE TYPES
 AND LOCATIONS ETC.
 6) PROVIDE UL TESTED AND APPROVED FIRESTOPPING DETAILS
 FOR ALL PIPES AND DUCTS PENETRATING THE FIRE-RATED
 BOILER ENCLOSURE AND THE ROOF STRUCTURE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-03-18 Cont ID  
Sent By tklarge Date 2016-03-18 Time 13:22 Rev Time 0.00
Received By tklarge Date 2016-03-18 Time 12:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-02-05 Cont ID  
Sent By tklarge Date 2016-02-05 Time 10:45 Rev Time 0.00
Received By tklarge Date 2016-02-05 Time 10:45 Sent To  
Notes
2016-02-05 10:45:131) ALL THE PLANS AND SUPPORTING DOCUMENTS SHALL BE
 COMPILED INTO TWO COMPLETE SETS OF PLANS FOR
 SUBMITTAL.2014 FBC SEC. 107.2.1.
 2) THE PLANS FROM GM CONSULTING ENGINEERS SHOWS THE
 BOILER EXHAUST BEING VENTED WITH 2- 45 DEGREE OFFSETS
 BUT THE PLANS FROM RIZA ALTAN SHOWS THE SAME VENT WITH
 2- 90 DEGREE FITTINGS. CLARIFY.
 3) THE PLUMBING RISER FROM TURQUOISE ENGINEERING SHOWS
 3-FLOOR SINKS, A VENT AND A FLOOR DRAIN FOR THIS
 INSTALLATION. ONLY 2 FLOOR SINKS ARE SHOWN ON THE PLAN
 BY GM CONSULTING ENGINEERS. A TRAP PRIMER IS REQUIRED
 ON THE FLOOR DRAIN.CLARIFY.2014 FPC SEC.1002.4
 4) THE 8 1/2" X 11 SHEET FROM BONDTECH IS ILLEGIBLE.
 SUBMIT A CLEAR AND LEGIBLE SHEET FOR REVIEW.FBC SEC.
 107.2.1.
 5) A BACKFLOW PREVENTER (RPZ) IS REQUIRED ON THE WATER
 FEED TO THE BOILER. 2014 FPC SEC. 608.3.
 6)

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-12-20 Cont ID  
Sent By tklarge Date 2015-12-20 Time 08:33 Rev Time 0.00
Received By tklarge Date 2015-12-20 Time 06:35 Sent To  
Notes
2015-12-20 07:41:211) WATER ABOVE 140 DEGRESS SHALL NOT BE DISCHARGED INTO
 ANY PART OF A DRAINAGE SYSTEM PER 2014 FBC-PLUMBING
 SEC. 803.1.
 2) SHT. P100 - IDENTIFY AND SIZE THE DRAIN FROM THE
 FEEDWATER TANK TO THE FLOOR SINK. WPB AMEND. TO FBC
 SEC. 107.2.1.
 3) SHT. P-200 - THE MINIMUM AIR GAP REQD. FOR THE
 INDIRECT WASTE PIPES SHALL BE NOT LESS THE TWICE THE
 EFFECTIVE OPENING OF THE INDIRECT WASTE PIPE. 2014 FBC
 PLUMBING SEC.802.2.1.
 4) SHT. P-200 - SHOW THE WATER SUPPLY TO THE AUTOCLAVE
 BLOWDOWN TANK ON THE AUTOCLAVE INSTALLATION DETAIL
 DRAWING.WPB AMEND. TO FBC SEC. 107.2.1.
 5) SHT. P-200 - THE PTR VALVE FOR THE AUTOCLAVE SHALL
 DISCHARGE BY GRAVITY PER 2014 FMC SEC.1006.5.
 6) SUBMIT AN INSTALLATION DETAIL FOR THE AUTOCLAVE
 BLOWDOWN TANK TO THE AUTOCLAVE. WPB AMEND. TO FBC SEC.
 107.2.1.
 7) SHT. P-200 SHOWS THE FLOOR SINKS AS EXISTING BUT
 SHT. 1 DOES NOT. ARE THEY NEW OR EXISTING? CLARIFY.
 8) THE FLOOR DRAINS ARE NOT VENTED. SHOW THE PROPER
 VENTING FOR THE FLOOR FRAINS. FBC-PLUMBING SEC.901.2,
 901.2.1. THE DISTANCE OF THE TRAP TO A VENT SHALL
 COMPLY WITH TABLE 909.1.
 9) TRAP PRIMERS ARE REQD. ON THE FLOOR DRAINS PER
 FBC-PLUMBING SEC.1002.4.
 10) THE 8 1/2 X 11 SHEET FROM BONDTECH IS ILLEGIBLE.
 SUBMIT A CLEAR AND LEGIBLE SHEET FOR REVIEW. WPB AMEND.
 TO FBC SEC.107.2.1.
 11) THE BOILER SHALL BE LISTED IN ACCORDANCE WITH THE
 2014 FL. MECHANICAL CODE SEC.1004.1.
 12) SUBMIT COMPLETE SPCIFICATIONS FOR THE FEEDWATER
 TANK AND THE BOILER. WPB AMEND. TO FBC SEC.107.2.1.
 130 INDICATE ON THE PLAN THE TYPE OF PIPING TO BE USED
 FOR THE STEAM SYSTEM. WPB AMEND. TO FBC SEC.107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-10-04 Cont ID  
Sent By tklarge Date 2015-10-04 Time 07:38 Rev Time 0.00
Received By tklarge Date 2015-10-04 Time 07:07 Sent To  
Notes
2015-10-04 07:05:001) THE FLOOR DRAINS ARE NOT VENTED. SHOW THE PROPER
 VENTING FOR THE FLOOR FRAINS. FBC-PLUMBING SEC.901.2,
 901.2.1. THE DISTANCE OF THE TRAP TO A VENT SHALL
 COMPLY WITH TABLE 909.1.
 2) TRAP PRIMERS ARE REQD. ON THE FLOOR DRAINS PER
 FBC-PLUMBING SEC.1002.4.
 3) THE 8 1/2 X 11 SHEET FROM BONDTECH IS ILLEGIBLE.
 SUBMIT A CLEAR AND LEGIBLE SHEET FOR REVIEW. WPB AMEND.
 TO FBC SEC.107.2.1.
 4) THE BOILER SHALL BE LISTED IN ACCORDANCE WITH THE
 2014 FL. MECHANICAL CODE SEC.1004.1.
 5) SPECIFICATIONS HAVE BEEN SUBMITTED FOR THE BOILER
 BUT NO PIPING DIAGRAM HAS BEEN SUBMITTED. INDICATE ON
 THE PLAN THAT THE BOILER INSTALLATION WILL BE DONE
 UNDER A SEPARATE PERMIT IF NOT BEING DONE AT THIS
 TIME.IF IT IS, SUBMIT COMPLETE PIPING DIAGRAM FOR
 REVIEW. WPB AMEND. TO FBC SEC.107.2.1.
 6) SUBMIT COMPLETE SPCIFICATIONS FOR THE FEEDWATER TANK
 AND SUBMIT THE COVER SHEET FOR THE BOILER. WPB AMEND.
 TO FBC SEC.107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  