| 2016-03-01 11:11:12 | 03/01/2016 AN E-MAIL WAS RECEIVED TODAY FROM THE | | | CONTRACTOR COASTAL FOR THE VERIFICATION OF THE | | | ELECTRONIC SIGNATURE FOR L.DAVID RICE OF RICE | | | ENGINEERING FOR THE ENGINEERING SHEETS AND CALCULATION | | | SHEE OF THE HANDRAIL AND PROTECTIVE BARRIER AROUND THE | | | FIRE PIT. FORWARDED THE E-MAIL WITH SIGNATURES TO | | | CARLOINE PUELL FOR RECORD RETENTION. JW. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-10-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-10-06 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-10-06 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2015-10-06 16:38:59 | BUILDING PLAN REVIEW | | | W. P. B. REVISION: 15090823 | | | W. P. B. PERMIT: 14050111 | | | ADD: 600 OKEECHOBEE BLVD. | | | CONT: COASTAL | | | TEL: ( 561)429-2302 | | | E-MAIL: ???????? | | | | | | 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 1ST REVIEW | | | DATE: TUES. OCT. 06/ 2015 | | | ACTION: DENIED | | | | | | 1) SHEET LS511H. INDICATES A FIRE PIT WITH THE USE OF | | | GAS AND AND A GLASS GUARDRAIL AROUND THE UNIT. PLEASE | | | PROVIDE COMPLIANCE THE GUARDRAIL WILL MEET COMPLIANCE | | | WITH 2010 FBC-B 1607.7.1 AND 1607.7.1.1. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2016-03-24 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2016-03-24 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2016-03-24 |
Time |
08:47 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2015-09-30 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2015-09-30 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2015-09-30 |
Time |
13:57 |
Sent To |
P |
|
| Notes |
| 2015-09-30 14:52:56 | 600 OKEECHOBEE BOULEVARD | | | PERMIT #15090823 | | | MASTER #14050111 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | WHAT ARE THE DAYS/HOURS OF OPERATION OF THE FIRE PIT? | | | WHO HAS ACCESS/TRAINING/AUTHORITY TO OPERATE THE GAS | | | IGNITER? WHO WILL BE SUPERVISING THE OPEN FLAME FIRE | | | PIT? | | | | | | PROVIDE A POOL DECK SITE PLAN SHOWING FIRE PIT LOCATION | | | IN RELATION TO THE SWIMMING POOL, HOTEL STRUCTURE AND | | | ANY OVERHANG/ROOF. | | | | | | ELIMINATE THE 6-INCH PERIMETER "CLIMBING LEDGE" CREATED | | | AT THE INTERSECTION OF THE CMU WALL, CAP AND TEMPERED | | | GLASS WALL BARRIER. | | | | | | PROIVIDE A NOTE ON THE PLANS INDICATING: PER THE | | | FLORIDA FIRE PREVENTION CODE - SECTION 10.11.10: THE | | | AHJ SHALL BE AUTHORIZED TO REQUIRE ANY FIRE TO BE | | | IMMEDIATELY DISCONTINUED IF THE FIRE IS DETERMINED TO | | | CONSTITUTE A HAZARDOUS CONDITION. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2016-04-18 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-04-18 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-04-18 |
Time |
04:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2016-03-28 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-03-28 |
Time |
07:15 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-03-28 |
Time |
05:04 |
Sent To |
|
|
| Notes |
| 2016-03-28 07:15:18 | IT APPEARS AS THOUGH NONE OF THE PREVIOUS PLAN REVIEW | | | COMMENTS FROM THE REVIEW DONE ON 10/3/15 HAVE BEEN | | | ADDRESSED. COMPLY WITH ALL PREVIOUS PLAN REVIEW | | | COMMENTS. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2015-10-03 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-10-03 |
Time |
07:24 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-10-03 |
Time |
06:58 |
Sent To |
|
|
| Notes |
| 2015-10-03 07:04:49 | 1) ALL GAS APPLIANCES SHALL BE LISTED & LABELED PER THE | | | 2014 FBC-FUEL GAS SEC. 301.3. SUBMIT VERIFICATION OF | | | LISTING/LABELING. | | | 2) NOTE #3 ON PLAN REFERS TO SHT. LS 101H. THERE IS NO | | | SUCH SHEET IN THIS SUBMITTAL. SUBMIT THE SHEET FOR | | | REVIEW. WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) SUBMIT COMPLETE MANUF. SPECIFICATION SHEETS FOR THE | | | FIRE PIT. WPB AMEND. TO FBC SEC. 107.2.1. | | | 4) SUBMIT A SITE PLAN SHOWING THE LOCATION OF THE FIRE | | | PIT.WPB AMEND. TO FBC SEC. 107.2.1. | | | 5) INDICATE ON THE PLAN IF THE GAS IS LP OR NATURAL.WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 6) SUBMIT A GAS PIPING DIAGRAM SHOWING THE LOCATION OF | | | THE GAS METER/LP TANK, THE DISTANCE FROM THE THE | | | METER/TANK TO THE FIRE PIT, THE DISTANCE FROM THE METER | | | / TANK TO THE MOST REMOTE OUTLET ON THE SYSTEM, TYPE OF | | | PIPE, BTU LOAD OF APPLIANCE, ETC. SEE GAS PERMITTING | | | CHECKLIST IN PERMIT FOLDER. | | | 7) EXPLAIN THE REASON FOR THE VENTS LOCATED ON THE WALL | | | OF THE FIREPIT.WPB AMEND. TO FBC SEC. 107.2.1. | | | 8) EXPLAIN THE INSTALLATION OF THE TWO 9" CATCH BASINS | | | THAT APPEAR TO BE LOCATED IN THE PIT AND WHAT | | | DISCHARGES TO THESE DRAINS AND WWHERE DOES THE EFFLUENT | | | GO? | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-04-18 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-04-18 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-04-13 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2016-04-13 15:35:15 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-03-28 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-03-28 |
Time |
07:18 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-02-25 |
Time |
13:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-10-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-10-06 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-09-18 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2015-09-18 13:42:40 | SUBMITTAL ROUTED TO FIRE |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2016-03-08 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2016-03-08 |
Time |
08:40 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2016-03-08 |
Time |
08:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2015-10-05 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2015-10-05 |
Time |
11:13 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2015-10-05 |
Time |
11:13 |
Sent To |
B |
|
| Notes |
|
|