Plan Review Details - Permit 15090810
Plan Review Stops For Permit 15090810
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-03-10 Cont ID  
Sent By jwitmer Date 2016-03-10 Time 08:32 Rev Time 0.00
Received By jwitmer Date 2016-03-10 Time 07:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-01-20 Cont ID  
Sent By jwitmer Date 2016-01-20 Time 13:48 Rev Time 0.00
Received By jwitmer Date 2016-01-20 Time 11:57 Sent To  
Notes
2016-01-20 13:47:12BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090810
 ADD: 4385 45TH ST
 CONT: C. W. HAYES CONSTRUCTION CO.
 TEL: (407)366-1564
 E-MAIL: CWHAYESCONSTRUCTION.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JAN. 20/2016
  
 ACTION: BUILDING PROVISO
  
 1) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31) (B) WINDOWS
 (C) WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) SHEET S4.1 AND DETAIL # 4 INDICATES THE SLAT WALL
 SYSTEM BY SPECIALTY ENGINEER TO BE A DEFERRED
 SUBMITTAL.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-05 Cont ID  
Sent By jwitmer Date 2015-10-05 Time 0 Rev Time  
Received By jwitmer Date 2015-10-05 Time 06:46 Sent To  
Notes
2015-10-05 08:46:34BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090810
 ADD: 4385 45TH ST
 CONT: C. W. HAYES CONSTRUCTION CO.
 TEL: (407)366-1564
 E-MAIL: CWHAYESCONSTRUCTION.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT. 06/2015
 ACTION: DENIED
  
 1) SHEET S0-1 INDICATES THE CORRECT WIND DESIGN
 CRITERIA 170 MPH, EXPOSURE C BUT THE OPENING SIZE THE
 PRESSUES IS NOT GIVEN. ROOF PRESSURES ARE REVIEWED FOR
 10 SQ. FT. PRESSURES IN ROOF ZONES 1 & 2 ARE CORRECT
 PRESSURES IN ROOF ZONE 3 ARE PROVIDED AS ZONE # 2
 ASSUMED 3'-0" PARAPET. SHEET A4-0 SHOWS A DASH LINE
 ASSUMED TO BE THE ROOF WITH PARAPET AT 30 INCHES, NOT 3
 FEET. ASCE 7-10 REQUIRES A 3'-0" PARAPET NOT TO HAVE A
 ROOF ZONE 3.
  
 2) SHEET S0-1 INDICATES THE CORRECT WIND DESIGN
 CRITERIA 170 MPH, EXPOSURE C BUT THE OPENING SIZE THE
 PRESSUES IS NOT GIVEN. THE WINDOWS BEING REPLACED ARE
 IN A WALL ZONE 4, THE SIZE OF THE OPENING IN THE CHART
 IS NOT GIVEN. THEY ARE CLOSE TO 50 SQ. FT. PRESSURES IN
 WALL ZONE 4, EXPOSURE C @ 15 FEET MEAN ROOF HEIGHT ARE
 +33.9/ -37.1. PLEASE CORRECT. 2014 FBC-B 1603.1.4 WIND
 DESIGN DATA.
  
 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31) (B) WINDOWS
 (C) WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) SHEET S4.1 AND DETAIL # 4 INDICATES THE SLAT WALL
 SYSTEM BY SPECIALTY ENGINEER. SHEET A4.0 NOTE # 12
 INDICATES THE SLAT WALL SYSTEM IS TO BE A ALUMINUM
 PRODUCT. BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT
 PLEASE HAVE ENGINEER OF RECORD REVIEW AND APPROVE
 BEFORE BEING FORWARDED TO THE BUILDING DEPARTMENT.
  
 SHEET A5.1 NOTE ON SHEET: DESIGN INTENT IS TO SPAN SLAT
 WALL BETWEEN TOWERS. SLAT WALL VENDOR TO DESIGN
 STRUCTURE REQUIRED FOR SPAN.
  
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 6) SHEET S4.2 DETAILS 1 & 3. THE PLANS ARE NOT CLEAR
 THE HOLES TO BE DRILLED INTO THE EXISTING FOUNDATION,
 HOW DEEP ARE THE HOLES TO BE DRILLED INTO THE
 FOUNDATION AND AT WHAT CENTERS? THE OTHER ISSUE, THERE
 THE REBAR PINS TO BE EPOXIED INTO PLACE? 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED. NOTE THE FOUNDATION
 EXTENSION IS PART OF THE MWFRS MAIN WIND FORCE
 RESISTING SYSTEM.
  
 7) SHEET A3.0 NOTE # 11 WHICH DEALS WITH ROOF TOP RTU'S
 OR ROOF TOP A/C STANDS. REPLACE OR RE-COMMISION TO
 CURRENT DESIGN LOADS. PLEASE PROVIDE WHAT THE INTENT OF
 THIS STATEMENT IS? THERE IS NO INFORMATION ON THE
 MECHANICAL SHEETS OF THE REPLACEMENT OF EQUIPMENT,
 CURBS AND OR ROOF TOP A/C STANDS. HOW WILL CURRENT
 DESIGN LOADS BE DETERMINED? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 7.2. RISK CATEGORY.
  
 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-03-10 Cont ID  
Sent By albarran Date 2016-03-10 Time 09:55 Rev Time 0.00
Received By albarran Date 2016-03-10 Time 09:04 Sent To I
Notes
2016-03-10 10:25:35ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFCTORILLY ADDRESSED. I PLACED A CALL TO RYAN GRAY,
 PE AT DIVITA TO DISCUSS FEEDER DERATION FOR PANEL "C".

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-02-18 Cont ID  
Sent By albarran Date 2016-02-18 Time 14:32 Rev Time 0.00
Received By albarran Date 2016-02-17 Time 09:34 Sent To I
Notes
2016-02-18 14:33:212ND ELECTRICAL REVIEW NOTES:
 REVIEWED FOR COMPLIANCE WITH:
 FBC 5TH EDITION 2014
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 1. ACCEPTED RESPONSE WITH NOTE.
 2. ACCEPTED RESPONSE. OUTLETS ARE INDICATED AND NOTE
 ALLOWING ADJUSTMENT DUE TO CONDITIONS.
 3. THE RISER DIAGRAM REFLECTS A PANEL ?C? AS EXISTING,
 AND THE MDP CIRCUIT DIRECTORY REFERS TO FOOD PREP LINE,
 IS THAT THE SAME AS PANEL ?C?? IF SO, CORRECT THE
 LABELS TO MATCH.
 4. PANEL ?C? SHOWN ON THE RISER DIAGRAM OR FOOD PREP
 LINE SHOWN ON THE MDP SCHEDULE DO NOT HAVE LOAD CALCS
 SHOWN ON PLAN.
 5. THERE IS A CIRCUIT DIRECTORY FOR PANELS A & B, BUT
 NOT FOR C OR THE FOOD PREP LINE.
 6. THERE IS NO INDICATION ON THE NOTES AREA NOR
 MARKINGS ON THE PANELS TO SHOW COMPLIANCE WITH THIS
 REQUIREMENT. PANELS SHALL BE MARKED TO INDICATE THE
 LOCATION OF THEIR SOURCE OF POWER.
 7. ACCEPTED THAT THE RECESSED LIGHTS ARE NOT WITHIN THE
 THERMAL ENVELOPE.
 8. THE EXISTING LIGHTING DESIGN MAY HAVE BEEN MADE TO
 AN EARLIER CODE WHICH HAD LESSER REQUIREMENTS. CURRENT
 CODES TAKE INTO ACCOUNT DAYLIGHT ENTERING THE PREMISES
 ALONG WITH DIMMING REQUIREMENTS.
 9. THE FLACOM REPORT SUBMITTED IS OUTDATED. IT SHALL BE
 TO THE STANDARDS OF THE 2014 FBC.
 10. ACCEPTED NEW SEPARATED SHEETS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-09 Cont ID  
Sent By albarran Date 2015-11-09 Time 13:00 Rev Time 0.00
Received By albarran Date 2015-11-09 Time 12:08 Sent To I
Notes
2015-11-09 13:00:55THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION
 OF THE 2014 FBC, (FLORIDA BUILDING CODE) AS APPLICABLE
 AND BELOW ARE THE DEFICIENCIES NOTED.
  
 1. NEC 110.16. PROVIDE ARC-FLASH HAZARD WARNING LABELS
 ON ALL PANELBOARDS.
 2. NEC 210.62. YOU SHALL PROVIDE A 15 -20 AMP SHOW
 OUTLET FOR EVERY 12 FT. OF WINDOW OR MAJOR PORTION
 THEREOF.
 3. NEC 215.5. YOU SHALL SUBMIT ACCURATE & SITE SPECIFIC
 FEEDER DIAGRAM SHOWING DETAILS OF CONDUCTOR SIZING AND
 LOADS.
 4. NEC 220.16. YOU SHALL PROVIDE ACCURATE LOADS CALCS.
 AS MENTIONED.
 5. NEC 408.4(A) YOU SHALL SUBMIT AN ACCURATE SITE
 SPECIFIC CIRCUIT DIRECTORY FOR EVERY ELECTRICAL PANEL.
 6. NEC 408.4(B). ALL PANEL BOARDS SHALL BE MARKED TO
 INDICATE THE LOCATION OF THEIR POWER SOURCE.
 7. FBC-ENERGY CONSERVATION CODE AKA FBC-E SECTION
 C402.4.8. RECESSED LIGHTING INSTALLED WITHIN THE BLDG.
 THERMAL ENVELOPE SHALL BE IC RATED AND SEALED TO LIMIT
 AIR LEAKAGE BETWEEN CONDITIONED & UNCONDITIONED SPACE.
 8. FBC-E SECTION C405 HAS SPECIFIC MANDATORY LIGHTING
 CONTROL REQUIREMENTS THAT I DO NOT SEE COMPLIANCE WITH
 ON THE LIGHTING PLANS.
 9. FBC-E C405.5.2 PROVIDE AN INTERIOR LIGHTING
 ALLOWANCE CHART TO SHOW COMPLIANCE.
 10. YOU SHALL SUBMIT A POWER PLAN IN ADDITION TO THE
 SUBMITTED LIGHTING PLANS.
 11. YOU SHALL PROVIDE A ROOF PLANS INDICATING THE
 LOCATION OF ALL ELECTRICAL APPARATUS ON THE ROOF.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER
 (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-03-04 Cont ID  
Sent By pleduc Date 2016-03-04 Time   Rev Time 0.00
Received By pleduc Date 2016-03-04 Time 09:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-01-11 Cont ID  
Sent By scaldero Date 2016-01-11 Time 13:58 Rev Time 0.00
Received By scaldero Date 2016-01-11 Time 13:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-09-24 Cont ID  
Sent By   Date 2015-09-24 Time   Rev Time 0.00
Received By pleduc Date 2015-09-24 Time   Sent To  
Notes
2015-09-24 13:14:119/24/15 - PASS WITH PROVISO.
 1. ADD ADDITIONAL E/M LIGHTS AS NOTED ON PAGE E1.0 OF
 PLAN.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-10 Cont ID  
Sent By albarran Date 2016-03-10 Time 10:25 Rev Time 0.00
Received By albarran Date 2016-03-01 Time 09:13 Sent To  
Notes
2016-03-10 10:30:023/10/16 PASSED ELECTRICAL REVIEW. ROXY NOTIFIED VIA
 TELEPHONE CALL. FILE ROUTED TO LARGE READY BIN "C:. MA
2016-03-02 09:13:27C32

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-18 Cont ID  
Sent By albarran Date 2016-02-18 Time 14:41 Rev Time 0.00
Received By albarran Date 2016-01-08 Time 12:41 Sent To  
Notes
2016-02-18 14:43:292/18/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL AND SPOKE W/ROXIE. FILE SENT TO
 LARGE DENIED BIN "C". MA
2016-01-08 12:42:07C32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-09 Cont ID  
Sent By albarran Date 2015-11-09 Time 13:04 Rev Time 0.00
Received By albarran Date 2015-09-18 Time 14:02 Sent To  
Notes
2015-11-09 13:05:1711/9/15 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN "C". MA
2015-09-18 14:02:54C38

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-09-30 Cont ID  
Sent By ccole Date 2015-09-30 Time 13:56 Rev Time 0.00
Received By ccole Date 2015-09-30 Time 13:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-10-03 Cont ID  
Sent By tklarge Date 2015-10-03 Time 04:02 Rev Time 0.00
Received By tklarge Date 2015-10-03 Time 03:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2016-03-04 Cont ID  
Sent By dkittred Date 2016-03-04 Time 16:40 Rev Time 0.00
Received By dkittred Date 2016-03-04 Time 15:42 Sent To  
Notes
2016-03-04 16:39:51PLANNING AND ZONING COMMENTS:
  
 3/4/16
  
 1. BUILDING WORK APPROVED, SEPARATE PERMITS REQUIRED
 FOR SITE WORK AND SIGNAGE.
  
 2. WHEN SUBMITTING FOR SITE WORK AN ADDITIONAL DETAIL
 FOR THE BICYCLE RACK SPACING WILL BE REQUIRED AND MUST
 INCLUDE A MINIMUM OF 36 INCHES BETWEEN RACKS AND A
 MINIMUM OF 24 INCHES BETWEEN RACK AND EDGE OF CONCRETE
 PAD. THE LENGTH OF THE PAD SHALL BE A MINIMUM OF 6
 FEET. ADJUST SITE PLAN ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-01-12 Cont ID  
Sent By dkittred Date 2016-01-12 Time 09:10 Rev Time 0.00
Received By dkittred Date 2016-01-12 Time 08:59 Sent To  
Notes
2016-01-12 09:10:00PLANNING AND ZONING COMMENTS: ***FAILED***
  
 1/12/16
  
 ZONING COMMENTS WERE NOT ADDRESED IN THE RESUBMITTAL.
 PLEASE COMPLY WITH THE FOLLOWING:
  
 [PREVIOUS COMMENT #1.] THE SUBJECT PROPERTY IS LOCATED
 WITHIN THE NORTH TRAIL PLAZA COMMERCIAL PLANNED
 DEVELOPMENT (CPD). CHANGES PROPOSED TO THE SITE WILL
 REQUIRE A MINOR PD AMENDMENT APPLICATION SUBMITTAL AND
 APPROVAL THROUGHT THE PLANNING DIVISION PRIOR ZONING
 APPROVAL OF THE BUILDING PERMIT. THE APPLICATION CAN BE
 ACCESSED THROUGH THE FOLLOWING LINK: HTTP://WPB.ORG/WP-
 CONTENT/UPLOADS/2015/12/2016-DEVELOPMENT-APPLICATION-RE
 VISED-2015-12-03.PDF (SUBMITTAL SHOULD INCLUDE CHANGES
 TO THE BUILDING, SITE, SIGNAGE, LANDSCAPING, ETC.)
  
 [PREVIOUS COMMENT #2.] THE VALUE OF THE CONSTRUCTION
 ($190,000) EXCEEDS 50% OF THE STRUCTURE'S VALUE
 ($162,136) ACCORDING TO THE P.B.C. PROPERTY APPRAISER'S
 OFFICE; THEREFORE, PURSUANT TO SECTION 94-441(C)(2) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), THE
 LANDSCAPE ON THE SITE SHALL BE IN COMPLIANCE WITH ALL
 APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF THE
 ZLDR. IF THE SITE CONFORMS TO ARTICLE XIV, THEN TWO (2)
 COPIES OF A LANDSCAPE PLAN DEMONSTRATING COMPLIANCE
 SHALL BE INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE
 SITE DOES NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE
 ZONING APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE
 PERMIT AND IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING
 MATERIAL TO BRING THE SITE INTO CONFORMITY.
  
 [PREVIOUS COMMENT #3.] SEPARATE PERMIT AND REVIEW
 REQUIRED FOR SIGNAGE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-09-28 Cont ID  
Sent By dkittred Date 2015-09-28 Time 11:53 Rev Time 0.00
Received By dkittred Date 2015-09-28 Time 10:35 Sent To  
Notes
2015-09-28 11:53:41PLANNING AND ZONING COMMENTS: ***FAILED***
  
 9/28/15
  
 1. THE SUBJECT PROPERTY IS LOCATED WITHIN THE NORTH
 TRAIL PLAZA COMMERCIAL PLANNED DEVELOPMENT (CPD).
 CHANGES PROPOSED TO THE SITE WILL REQUIRE A MINOR PD
 AMENDMENT APPLICATION SUBMITTAL AND APPROVAL THROUGHT
 THE PLANNING DIVISION PRIOR ZONING APPROVAL OF THE
 BUILDING PERMIT. THE APPLICATION CAN BE ACCESSED
 THROUGH THE FOLLOWING LINK: HTTP://WPB.ORG/PLANNING/WP-
 CONTENT/UPLOADS/SITES/37/2013/04/2015-DEVELOPMENT-APPLI
 CATION-REVISED-06.17.2015.PDF (SUBMITTAL SHOULD INCLUDE
 CHANGES TO THE BUILDING, SITE, SIGNAGE, LANDSCAPING,
 ETC.)
  
 2. THE VALUE OF THE CONSTRUCTION ($190,000) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($162,136) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
 3. SEPARATE PERMIT AND REVIEW REQUIRED FOR SIGNAGE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2015-09-25 13:46:239/25/15