Plan Review Details - Permit 15090773
Plan Review Stops For Permit 15090773
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-22 Cont ID  
Sent By ccole Date 2015-09-22 Time 08:12 Rev Time 0.00
Received By ccole Date 2015-09-17 Time 08:56 Sent To  
Notes
2015-09-18 08:56:37ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-10-07 Cont ID  
Sent By ccole Date 2015-10-07 Time 14:40 Rev Time 0.00
Received By ccole Date 2015-10-07 Time 14:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-09-22 Cont ID  
Sent By ccole Date 2015-09-22 Time 07:46 Rev Time 0.00
Received By ccole Date 2015-09-22 Time 07:46 Sent To  
Notes
2015-09-22 07:57:441ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090773
 09/22/15
  
 1) FOR EACH EXACT SAME SIZE, SAME LOCATION AC
 CHANGEOUT, PLEASE SUBMIT TWO COPIES OF THE CITY OF WEST
 PALM BEACH AC CHANGEOUT COMPLIANCE FORM.
 2) NEW HEAT PUMP REQUIREMENTS- PLEASE PROVIDE:
 A) A PLAN INDICATING THE LOCATIONS OF THE AIR HANDLER
 AND CONDENSER. B) AC COOLING AND HEATING CALCULATIONS
 PER SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. C)
 AHRI CERTIFICATE. D) AC EQUIPMENT SCHEDULE. E)
 CONDENSATE DISPOSAL PLAN. F) ELECTRICAL PLAN. G)
 STRUCTURAL DETAILS FOR THE CONSTRUCTION OF THE
 CONDENSER SLAB, AND ATTACHMENT OF THE CONDENSER TO THE
 SLAB.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  