| 2015-09-22 08:25:04 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. PLANS PREPARED BY A DESIGN PROFESSIONAL REQUIRED, |
| | FS471 DUE TO THE MODIFICATION (ELIMINATION OF A DOOR) |
| | TO A PUBLIC BUILDING. |
| | |
| | 2. THE DETAIL PROVIDED DOES NOT SHOW HOW THE BLOCK |
| | INFILL WILL RESIST LOADS, FBC 1601. NO STEEL EMBEDMENT |
| | INTO EXISTING SUBSTRATE IS PROPOSED. |
| | |
| | 3. PLAN PROPOSES TO CLOSE IN A ROOM, CREATING A SPACE |
| | WHICH HAS NO INGRESS AND EGRESS. REVISE PLAN TO INCLUDE |
| | ROOM DESIGNATION, FBC 107. SCOPE NOT CLEAR; WHY IS IT |
| | NECESSARY TO CLOSE IN THIS SPACE, CREATING A CONCEALED |
| | SPACE? REVISE PLAN TO CLARIFY SCOPE. |
| | |
| | 4. PRODUCT APPROVAL FL 14237 IS EXPIRED; CODE CHANGED |
| | ON 6/31/15. PROVIDE A CURRENT (FBC 2014) PRODUCT |
| | APPROVAL, FBC 1609, FAC9N-3. |
| | |
| | 5. PRODUCT APPROVAL FL 16356 HAS AN APPLICATION STATUS |
| | OF "VALIDATED"; THIS SHOULD BE "APPROVED." PLEASE PRINT |
| | THE FLORIDA STATE PRODUCT APPROVAL COVER SHEET WHICH |
| | SHOWS AN "APPROVED" STATUS, FBC 1609, FAC9N-3. |
| | |
| | PLEASE NOTE THAT IT APPEARS THAT THE PRODUCT APPROVAL |
| | WAS PRINTED ON 7/8/2015, BUT THE APPLICATION WAS |
| | SUBMITTED ON 9/17/15. AS MANUFACTURERS OFTEN UPDATE |
| | THEIR PRODUCTS, PRIOR TO SUBMITTING PERMIT APPLICATION, |
| | CONFIRM THAT THE VERSION PROVIDED IS THE MOST CURRENT |
| | VERSION. |
| | |
| | 6. WHEN RESUBMITTING, PROVIDE TWO COMPLETE IDENTICAL |
| | COLLATED SETS OF PLANS FOR PERMIT ISSUANCE. THE OLD |
| | SHEETS SHOULD BE REMOVED AND MARKED "VOID" AND RETAINED |
| | IN THE PERMIT PACKAGE. |
| | |
| | |
| | |
| | |