| 2015-10-22 08:57:31 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION |
| | OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION |
| | OF THE FBC, (FLORIDA BUILDING CODE) 2014, AS APPLICABLE |
| | AND BELOW ARE THE DEFICIENCIES NOTED. |
| | 1. NO ELECTRICAL DATA PROVIDED. |
| | 2. YOU SHALL SUBMIT AN ELECTRICAL WIRING DIAGRAM |
| | REFLECTING THE PROPOSED INSTALLATION, TAKING INTO |
| | CONSIDERATION ALL APPLICABLE MOTOR LOADS, VOLTAGE DROP |
| | AND DIRECT SUNLIGHT EXPOSURE OF YOUR CONDUCTORS. |
| | 3. YOU SHALL SUBMIT SPEC SHEETS ON THE PROPOSED LIFT |
| | INCLUDING MOTOR LOADS. |
| | 4. YOU SHALL INCLUDE THE LOCATION OF THE SERVICE, MAIN |
| | DISCONNECT AND ALL ASSOCIATED EQUIPMENT. ALL THIS SHALL |
| | BE LOCATED TAKING INTO CONSIDERATION ALL THE |
| | REQUIREMENTS OF NEC 682. (BE AWARE OF THE ELECTRICAL |
| | DATUM PLANE WHEN LOCATING THE EQUIPMENT) |
| | 5. IN ADDITION TO THE ELECTRIC FOR THE HOIST MOTORS, |
| | AND 15-20 AMP 120 V. GFCI PROTECTED OUTLET SHALL BE |
| | PROVIDED FOR SERVICE AND SHORE POWER. |
| | THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN |
| | MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED |
| | FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED |
| | TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG |
| | WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE, |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY |
| | APPRECIATED. |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | |