Plan Review Details - Permit 15090645
Plan Review Stops For Permit 15090645
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2015-10-21 Cont ID  
Sent By jwitmer Date 2015-10-21 Time 12:30 Rev Time 0.00
Received By jwitmer Date 2015-10-21 Time 11:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-22 Cont ID  
Sent By jwitmer Date 2015-09-22 Time 07:27 Rev Time 0.00
Received By jwitmer Date 2015-09-22 Time 06:29 Sent To  
Notes
2015-09-22 07:27:12BUILDING PLAN REVIEW
 W. P. B. REVISION: 15090645
 W. P. B. PERMIT: 14090659
 ADD: 500 BELVEDERE RD.
 CONT: OAK CONSTRUCTION
 TEL: (954)583-9949
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 22/ 2015
 ACTION: DENIED
  
 1) THE REVISION IS THE FRONT ENTRY DOORS DURA STORM
 ALUMINUM AUTOMATIC SLIDING GLASS DOORS, OPERABLE PANELS
 W/ FULL BREAKOUT PANELS-LMI.
 THE SUBMITTED LITEATURE A MIAMI-DADE NOA 13-0529.23.
 PLEASE PROVIDE COMPLIANCE FOR CODE SECTIONS;
 2010 FBC-B
  
 1008.1.4.2 POWER-OPERATED DOORS.
 WHERE MEANS OF EGRESS DOORS ARE OPERATED BY POWER, SUCH
 AS DOORS WITH A PHOTOELECTRIC-ACTUATED MECHANISM TO
 OPEN THE DOOR UPON THE APPROACH OF A PERSON, OR DOORS
 WITH POWER-ASSISTED MANUAL OPERATION, THE DESIGN SHALL
 BE SUCH THAT IN THE EVENT OF POWER FAILURE, THE DOOR IS
 CAPABLE OF BEING OPENED MANUALLY TO PERMIT MEANS OF
 EGRESS TRAVEL OR CLOSED WHERE NECESSARY TO SAFEGUARD
 MEANS OF EGRESS. THE FORCES REQUIRED TO OPEN THESE
 DOORS MANUALLY SHALL NOT EXCEED THOSE SPECIFIED IN
 SECTION 1008.1.3, EXCEPT THAT THE FORCE TO SET THE DOOR
 IN MOTION SHALL NOT EXCEED 50 POUNDS (220 N). THE DOOR
 SHALL BE CAPABLE OF SWINGING FROM ANY POSITION TO THE
 FULL WIDTH OF THE OPENING IN WHICH SUCH DOOR IS
 INSTALLED WHEN A FORCE IS APPLIED TO THE DOOR ON THE
 SIDE FROM WHICH EGRESS IS MADE. FULL-POWER-OPERATED
 DOORS SHALL COMPLY WITH BHMA A156.10. POWER-ASSISTED
 AND LOW-ENERGY DOORS SHALL COMPLY WITH BHMA A156.19.
  
 EXCEPTIONS: 2. HORIZONTAL SLIDING DOORS COMPLYING WITH
 SECTION 1008.1.4.3.
  
 3. FOR A BIPARTING DOOR IN THE EMERGENCY BREAKOUT MODE,
 A DOOR LEAF LOCATED WITHIN A MULTIPLE-LEAF OPENING
 SHALL BE EXEMPT FROM THE MINIMUM 32-INCH (813 MM)
 SINGLE-LEAF REQUIREMENT OF SECTION 1008.1.1, PROVIDED A
 MINIMUM 32-INCH (813 MM) CLEAR OPENING IS PROVIDED WHEN
 THE TWO BIPARTING LEAVES MEETING IN THE CENTER ARE
 BROKEN OUT.
  
 1008.1.4.3 HORIZONTAL SLIDING DOORS.
 IN OTHER THAN GROUP H OCCUPANCIES, HORIZONTAL SLIDING
 DOORS PERMITTED TO BE A COMPONENT OF A MEANS OF EGRESS
 IN ACCORDANCE WITH EXCEPTION 6 TO SECTION 1008.1.2
 SHALL COMPLY WITH ALL OF THE FOLLOWING CRITERIA:
  
 1. THE DOORS SHALL BE POWER OPERATED AND SHALL BE
 CAPABLE OF BEING OPERATED MANUALLY IN THE EVENT OF
 POWER FAILURE.
  
 2. THE DOORS SHALL BE OPENABLE BY A SIMPLE METHOD FROM
 BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT.
  
 3. THE FORCE REQUIRED TO OPERATE THE DOOR SHALL NOT
 EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND
 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE
 MINIMUM REQUIRED WIDTH.
  
 4. THE DOOR SHALL BE OPENABLE WITH A FORCE NOT TO
 EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS
 (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR ADJACENT
 TO THE OPERATING DEVICE.
  
 5. THE DOOR ASSEMBLY SHALL COMPLY WITH THE APPLICABLE
 FIRE PROTECTION RATING AND, WHERE RATED, SHALL BE
 SELF-CLOSING OR AUTOMATIC CLOSING BY SMOKE DETECTION IN
 ACCORDANCE WITH SECTION 716.5.9.3, SHALL BE INSTALLED
 IN ACCORDANCE WITH NFPA 80 AND SHALL COMPLY WITH
 SECTION 716.
  
 6. THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED STANDBY
 POWER SUPPLY.
  
 7. THE DOOR ASSEMBLY POWER SUPPLY SHALL BE ELECTRICALLY
 SUPERVISED.
  
 8. THE DOOR SHALL OPEN TO THE MINIMUM REQUIRED WIDTH
 WITHIN 10 SECONDS AFTER ACTIVATION OF THE OPERATING
 DEVICE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2015-10-21 Cont ID  
Sent By jwitmer Date 2015-10-21 Time 12:30 Rev Time 0.00
Received By jwitmer Date 2015-10-19 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-22 Cont ID  
Sent By jwitmer Date 2015-09-22 Time 07:27 Rev Time 0.00
Received By jwitmer Date 2015-09-15 Time 10:36 Sent To  
Notes
2015-09-16 10:36:30SUBMITTAL ROUTED TO JWITMER