| Plan Review Stops For Permit 15090603 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2015-11-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2015-11-19 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-11-19 |
Time |
16:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2015-10-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2015-10-14 |
Time |
18:50 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-10-14 |
Time |
18:50 |
Sent To |
|
|
| Notes |
| 2015-10-14 18:55:19 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. OK | | | | | | 2. PROVIDE INFORMATION REGARDING EXISTING CONDITIONS, | | | FBC 107 (IN THE FORM OF A PLAN) AND PROPOSED. NO | | | INFORMATION REGARDING THE TENANT SPACE HAS BEEN | | | PROPOSED. | | | | | | 3. PROVIDE INFORMATION AS TO HOW THE PROPOSED | | | IMPROVEMENT WILL AFFECT EXITING AND ACCESSIBILITY. SPEC | | | SHEET STATES THAT THE DOOR WILL BE INSTALLED WITHIN A | | | 3/4" RECESS. PROVIDE A PLAN/DETAIL WHICH SHOWS THAT | | | THIS RECESS COMPLIES WITH MEANS OF EGRESS AND | | | ACCESSIBILITY REQUIREMENTS. WON'T THIS CREATE A 3/4" | | | TRENCH? SEE FBC 5TH EDITION ACCESSIBILITY 303. IS THIS | | | AREA RQUIRED TO BE ACCESSIBLE? SHOW COMPLIANCE WITH FBC | | | 1008.1, 1008.1.4.3. NOT ENOUGH INFORMATION PROVIDED TO | | | PERFORM A COMPLETE PLAN REVIEW, FBC 107. | | | | | | 2ND REVIEW, PROVIDE A DETAIL WHICH SHOWS THE AFFECT ON | | | ACCESSIBILITY AND EXITING. A PLAN WAS PROVIDED WHICH | | | STATES THAT THIS WILL BE INSTALLED IN A TRENCH, BUT THE | | | SPEC SHEET PROVIDED STATES THAT THIS SLIDING GLASS DOOR | | | HAS A 2 1/4" RISER FOR THE TRACK. | | | | | | SEE FBC 107 REGARDING THE QUALITY OF DETAIL. PLANS TO | | | BE ARCHITECTURAL QUALITY, TO SCALE. A STATEMENT THAT | | | THIS IS WHEELCHAIR ACCESSIBLE IS NOT ADEQUATE TO | | | DEMONSTRATE HOW THIS TRACK AND SILL WILL AFFECT | | | EXITING. | | | | | | DETAILS ARE TO SHOW HEIGHT OF SILL, WIDTH, DEPTH, PLAN | | | VIEW AND SECTION, WITH DIMENSIONS. DIMENSIONS ARE TO BE | | | CONSISTENT WITH THE MANUFACTURER'S INFORMATION. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-09-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2015-09-17 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-09-17 |
Time |
09:12 |
Sent To |
Z |
|
| Notes |
| 2015-09-17 09:45:58 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, | | | FAC9N-3, FBC 1609. A MULLION PRODUCT APPROVAL WAS | | | PROVIDED. A SLIDING GLASS DOOR PROPOSED. | | | | | | 2. PROVIDE INFORMATION REGARDING EXISTING CONDITIONS, | | | FBC 107 (IN THE FORM OF A PLAN) AND PROPOSED. NO | | | INFORMATION REGARDING THE TENANT SPACE HAS BEEN | | | PROPOSED. | | | | | | 3. PROVIDE INFORMATION AS TO HOW THE PROPOSED | | | IMPROVEMENT WILL AFFECT EXITING AND ACCESSIBILITY. SPEC | | | SHEET STATES THAT THE DOOR WILL BE INSTALLED WITHIN A | | | 3/4" RECESS. PROVIDE A PLAN/DETAIL WHICH SHOWS THAT | | | THIS RECESS COMPLIES WITH MEANS OF EGRESS AND | | | ACCESSIBILITY REQUIREMENTS. WON'T THIS CREATE A 3/4" | | | TRENCH? SEE FBC 5TH EDITION ACCESSIBILITY 303. IS THIS | | | AREA RQUIRED TO BE ACCESSIBLE? SHOW COMPLIANCE WITH FBC | | | 1008.1, 1008.1.4.3. NOT ENOUGH INFORMATION PROVIDED TO | | | PERFORM A COMPLETE PLAN REVIEW, FBC 107. | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2015-11-16 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-11-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-11-16 |
Time |
11:07 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2015-10-06 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-10-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-10-06 |
Time |
16:20 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2015-09-30 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-09-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-09-30 |
Time |
13:37 |
Sent To |
PC |
|
| Notes |
| 2015-09-30 13:43:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THERE IS INSUFFICIENT DETAIL TO COMPLETE OR APPROVE THE | | | PROPOSED PROJECT. | | | | | | 1) PROVIDE A VERIFYING DETAILED FLOOR PLAN SHOWING | | | EXISTING AND PROPOSED | | | | | | 2) ADDRESS BUILDING COMMENTS | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-11-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2015-11-19 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-10-23 |
Time |
12:47 |
Sent To |
|
|
| Notes |
| 2015-10-26 12:47:51 | RESUB ROUTED TO ESCHNEIDER VIA SGRAHAM'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-10-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2015-10-14 |
Time |
18:55 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-10-05 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2015-10-09 10:51:36 | 10/9 TO SH DESK | | | | | | | | 2015-10-05 11:20:36 | RESUB ROUTED TO FIRE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-09-30 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-09-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-09-15 |
Time |
13:31 |
Sent To |
|
|
| Notes |
| 2015-09-17 09:46:30 | 9/17 TO SG DESK W/STICKY "ES" | | | PER ESCHNEIDER REQUEST | | | | | 2015-09-15 13:31:19 | BLDG MISC 1 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2015-11-10 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2015-11-10 |
Time |
13:56 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2015-11-10 |
Time |
13:56 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2015-09-29 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2015-09-29 |
Time |
09:50 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2015-09-29 |
Time |
09:50 |
Sent To |
FIRE |
|
| Notes |
|
|