Plan Review Details - Permit 15090594
Plan Review Stops For Permit 15090594
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-11-14 Cont ID  
Sent By jwitmer Date 2015-11-14 Time   Rev Time 0.00
Received By jwitmer Date 2015-11-14 Time 08:00 Sent To  
Notes
2015-11-14 08:38:23BUILDING PLAN REVIEW
 W. P. B. REVISION: 15090594
 W. P. B. PERMIT: 14120130
 ADD: 1901 S. DIXIE HWY.
 CONT: SISCA
 TEL: (
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT.NOV. /2015
  
 ACTION: BUILDING PROVISO
  
  
  
 1) COMPLIED. SHEET A1.2 THE NEW LAYOUT OF FURNATURE AND
 EGRESS PLAN.
  
 2) BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 OF THE PERMITED SET OF DRAWINGS SHEET A4.0 ONLY SHOWS
 THE LOCATION OF THE ROOFTOP RTU UNITS. BOTH S3 & M1.3
 BOTH SHOW A ROOF TOP VEIW OF THE PROJECT THE 3 RTU'S
 AND INTAKE AND ROOF TOP EXHAUST FANS. THERE IS A NOTE
 THE WALKIN CONDENSING UNIT TO BE REMOTE. FINAL LOCATIN
 SHALL BE DETERMINED BY OWNER/ ARCHITECT. REVISION #
 15090594 DOES NOT SHOW A REVISION TO THE ROOF PLAN NOR
 WAS SHEET S3 UPDATED TO SHOW NEW LOCATIONS, SHEET M1.3
 DOES SHOW ON THE MECHANICAL ROOF TOP SHEET A REVISION
 SHOWING THE LOCATION FOR 3 NEWLY LOCATED, (NOT
 HIGHLIGHTED SHOWING A REVISION), ROOF TOP CU UNITS, NO
 DETAILS UNDER MECHANICAL NOR STRUCTURAL SHEETS!!!!!
 PLEASE UPDATE ALL RELEVENT SHEETS TO THE NEW LOCATION
 OF THE 3 NEWLY LOCATED ROOF TOP A/C SPLIT SYSTEMS. WITH
 3 CU SPLIT SYSTEMS IF A ROOF TOP A/C STAND IS TO BE
 INSTALLED. PLEASE PROVIDE THE ATTACHMENT OF THE STAND
 TO THIS SITE SPECIFIC CONDITION. ALSO PROVIDE
 ENGINEERING FOR HOW THE C/U UNIT WILL BE ATTACHED TO
 THE STAND, BY THE ENGINEER OF RECORD.
  
 THE STRUCTURAL ENGINEER HAS NOT INDICATED ON ANY PLANS
 HOW THIS UNIT WILL ATTACH TO THE MWFRS. THE ENGINEER
 HAS PROVIDED (PERMIT SET OF DRAWINGS) DETAILS ON SHEET
 S6 FOR THE ATTACHMENT OF THE RTU'S CURB TO THE MWFRS
 AND THE CLIP SYSTEM FOR MOUNTING THE RTU TO THE CURB.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-07 Cont ID  
Sent By jwitmer Date 2015-10-07 Time 11:38 Rev Time  
Received By jwitmer Date 2015-10-07 Time 09:30 Sent To  
Notes
2015-10-07 11:05:38BUILDING PLAN REVIEW
 W. P. B. REVISION: 15090594
 W. P. B. PERMIT: 14120130
 ADD: 1901 S. DIXIE HWY.
 CONT: SISCA
 TEL: (
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. OCT. 07/2015
 ACTION: DENIED
  
 1) SHEET A1.2 THE NEW LAYOUT OF FURNATURE AND EGRESS
 PLAN APPEARS TO HAVE (2) PINCH POINTS OR MINIMUM
 REQUIRED EGRESS WIDTH. 2010 FBC-B 1005.1. THERE IS A
 GREAT DIFFERENCE BETWEEN THE ACCESS AILES AND AISLES.
 FOR ACCESS AILSES SECTION 1028.9 REFERS YOU BACK TO
 1017.4 FOR TABLES AND CHAIRS. THE 2010 FBC-B 1028.9
 ASSEMBLY AISLES. SEE 1028.9.1.1 THE MINIMUM WIDTH OF
 AISLES SERVING SEATING AT TABLES SHALL BE 44 INCHES.
 PLEASE REVISE SHOWING THE AISLES AT 44 INCHES. THE
 EXCEPTION IS 36 INCHES WHEN SERVING AN OCCUPANT LOAD OF
 NOT MORE THAN 50.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-11-30 Cont ID  
Sent By albarran Date 2015-11-30 Time 19:25 Rev Time 0.00
Received By albarran Date 2015-11-30 Time 18:07 Sent To  
Notes
2015-11-30 19:26:35ALL OF THE PREVIOUSLY MENTIONED COMMENTS WERE ADDRESSED
 AS DELTA 8 REVISION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-10-15 Cont ID  
Sent By albarran Date 2015-10-15 Time 18:49 Rev Time 0.00
Received By albarran Date 2015-10-15 Time 15:40 Sent To  
Notes
2015-10-15 18:49:23PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE
 ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE
 REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED
 SHALL BE RESUBMITTED FOR ANOTHER REVIEW.
 1. IN ADDITION TO THE IN-USE TYPE COVER, THE NEC
 REQUIRES THAT ALL RECEPTACLES IN WET LOCATIONS BE
 LISTED/RATED WEATHER RESISTANT.
 2. APPLICABLE CODES ARE AS FOLLOWS: FFPC-2012, NFPA
 1-2012, NFPA 70 (NEC)-2011, NFPA 72-2010, NFPA 101-2012
 AND FBC 5TH EDITION 2014.
 3. THE QUOTED FBC SECTION HAS NOTHING TO DO WITH THE
 RESPECTIVE NOTE OR COMMENT.
 4. NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN
 OUT ADJACENT TO EVERY PEDESTRIAN ENTRY WAY NOT JUST THE
 MAIN FRONT DOOR. SIGN OUTLET REQ?D BY KANUGA DR. EXIT.
 5. DOOR TO ALLEY WAY IS EXCLUDED FROM THE SIGN OUTLET
 REQUIREMENT.
 6. REVISE THE PANEL SCHEDULES AND SUBSEQUENT LOAD CALCS
 FOR BOTH PANELS A & B.
 7. REVISE THE ELECTRICAL RISER DIAGRAM TO MATCH THE
 PROPOSED SERVICE DISTRIBUTION AND PANEL SCHEDULE.
 8. LOCATION OF LIGHTING CONTROL PANEL DIFFERS BETWEEN
 SHEETS E-1.1 & E-2.1. MAKE THEM MATCH; NEC 210.70(C)
 REQUIRES THAT THERE BE SUFFICIENT ILLUMINATION AT THE
 LOCATION OF ELECTRICAL EQUIPMENT.
 9. BOTH, THE FBC AND THE NEC REQUIRE STAIR ILLUMINATION
 FOR NORMAL AND EMERGENCY CONDITIONS. THEREFORE A LIGHT
 CONTROLLED AT BOTH TOP AND BOTTOM SHALL BE INSTALLED
 FOR THE STAIRWAY AS WELL AS AN EMERGENCY LIGHT
 CONNECTED AHEAD OF ANY SWITCHES ON THE SAME CIRCUIT AS
 THE STAIR LIGHTING.
 10. NEC 314.27(C) REQUIRES THAT CEILING OUTLETS FOR
 PADDLE FANS BE LISTED FOR THE PURPOSE AND CAPABLE OF
 SUPPORTING THE WEIGHT.
 11. BESIDES THE ADDITIONAL LIGHTING REQUIRED FOR THE
 STAIRWAY, MANDATORY LIGHTING CONTROLS ARE REQUIRED FOR
 THE SECOND FLOOR STORAGE AREA.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-12-08 Cont ID  
Sent By wjolin Date 2015-12-08 Time 15:59 Rev Time 0.00
Received By wjolin Date 2015-12-08 Time 15:59 Sent To  
Notes
2015-12-08 15:59:25REPEAT COMMENT: UPDATED LIFE SAFETY PLAN NOT SUBMITTED.
  
 ORIGINAL COMMENT: LIFE SAFETY PLAN: NEW FURNTITURE
 LAYOUT OBSTRUCTS EGRESS PATHS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2015-11-20 Cont ID  
Sent By wjolin Date 2015-11-20 Time 11:29 Rev Time 0.00
Received By wjolin Date 2015-11-20 Time 11:19 Sent To  
Notes
2015-11-20 11:29:18REPEAT COMMENT: UPDATED LIFE SAFETY PLAN NOT SUBMITTED.
  
 ORIGINAL COMMENT: LIFE SAFETY PLAN: NEW FURNTITURE
 LAYOUT OBSTRUCTS EGRESS PATHS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-09-22 Cont ID  
Sent By wjolin Date 2015-09-22 Time 17:49 Rev Time 0.00
Received By wjolin Date 2015-09-22 Time 17:49 Sent To  
Notes
2015-09-22 17:49:46LIFE SAFETY PLAN: NEW FURNTITURE LAYOUT OBSTRUCTS
 EGRESS PATHS.

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2015-12-04 Cont ID  
Sent By fmittner Date 2015-12-04 Time 16:07 Rev Time 0.00
Received By fmittner Date 2015-12-04 Time 16:07 Sent To  
Notes
2015-12-04 16:08:36GLASS IN FIELD IS TINITED. HPB APPROVED ONLY CLEAR
 GLAZING. QUESTIONS CONTACT FRIEDERIKE MITTNER AT
 822-1457.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-10-28 Cont ID  
Sent By fmittner Date 2015-10-28 Time 11:35 Rev Time 0.00
Received By fmittner Date 2015-10-28 Time 11:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-04 Cont ID  
Sent By cpuell Date 2015-12-04 Time 16:27 Rev Time 0.00
Received By cpuell Date 2015-11-10 Time 10:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-28 Cont ID  
Sent By lmarchan Date 2015-10-28 Time 11:56 Rev Time 0.00
Received By lmarchan Date 2015-09-15 Time 13:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-11-17 Cont ID  
Sent By ccole Date 2015-11-17 Time 13:57 Rev Time 0.00
Received By ccole Date 2015-11-17 Time 13:57 Sent To  
Notes
2015-11-17 14:08:42MECHANICAL PROVISO
 REVISION PERMIT #15090594
 MASTER PERMIT #14120130
 11/17/15
  
 1) SHEET M1.3 ROOF PLAN MUST BE REVISED TO SHOW THE
 LOCATIONS OF THE WALK-IN BOX REFRIGERATION CONDENSERS,
 AND THE MINI-PAK UNIT BY COLDZONE (SEE PERMIT
 #15110411).
 2) WIND LOAD ENGINEERING FOR TIE DOWN OF THE ROOFTOP
 CONDENSERS AND FOR THE MINI-PAK UNIT SHALL BE SUBMITTED
 TO THE BUILDING DEPARTMENT PRIOR TO INSPECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-10-22 Cont ID  
Sent By hmoser Date 2015-10-22 Time 13:45 Rev Time 0.00
Received By ccole Date 2015-10-22 Time 13:45 Sent To  
Notes
2015-10-22 13:58:271ST REVIEW: FBC 2010 MECHANICAL
 REVISION PERMIT #15090594
 MASTER PERMIT #14120130
 10/22/15
  
 1) SHEET M0.1: PROVIDE EQUIPMENT SCHEDULES FOR THE NEW
 DEF-1 AND PEF-1.
 2) M1.1: SHOW THE LOCATIONS OF THE DEF-1 AND PEF-1
 EXHAUST OPENINGS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-11-13 Cont ID  
Sent By gjohnson Date 2015-11-13 Time 15:39 Rev Time 0.00
Received By gjohnson Date 2015-11-13 Time 15:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-10-02 Cont ID  
Sent By tklarge Date 2015-10-02 Time 07:36 Rev Time 0.00
Received By tklarge Date 2015-10-01 Time 14:33 Sent To  
Notes
2015-10-01 14:36:531) SUBMIT A NARRATIVE THAT CLEARLY NOTES/EXPLAINS THE
 CHANGES THAT WERE MADE TO THE SANITARY, GREASY WASTE,
 WATER AND GAS SYSTEMS. WPB AMENDMENTS TO FBC
 SEC.107.2.1.
 2) THE GREASE FROM THE HOODS IS NOT PERMITTED TO
 DISCHARGE TO THE GREASE INTERCEPTOR PER 2014
 FBC-PLUMBING SEC.1003.1 AND SEC. 202 ( SEE DEFINITION
 OF GREASE LADEN WASTE).
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-10-28 Cont ID  
Sent By fmittner Date 2015-10-28 Time 11:49 Rev Time 0.00
Received By fmittner Date 2015-10-28 Time 11:49 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved