| Plan Review Stops For Permit 15090594 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2015-11-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-11-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-11-14 |
Time |
08:00 |
Sent To |
|
|
| Notes |
| 2015-11-14 08:38:23 | BUILDING PLAN REVIEW | | | W. P. B. REVISION: 15090594 | | | W. P. B. PERMIT: 14120130 | | | ADD: 1901 S. DIXIE HWY. | | | CONT: SISCA | | | TEL: ( | | | E-MAIL: | | | | | | 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: SAT.NOV. /2015 | | | | | | ACTION: BUILDING PROVISO | | | | | | | | | | | | 1) COMPLIED. SHEET A1.2 THE NEW LAYOUT OF FURNATURE AND | | | EGRESS PLAN. | | | | | | 2) BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | | | OF THE PERMITED SET OF DRAWINGS SHEET A4.0 ONLY SHOWS | | | THE LOCATION OF THE ROOFTOP RTU UNITS. BOTH S3 & M1.3 | | | BOTH SHOW A ROOF TOP VEIW OF THE PROJECT THE 3 RTU'S | | | AND INTAKE AND ROOF TOP EXHAUST FANS. THERE IS A NOTE | | | THE WALKIN CONDENSING UNIT TO BE REMOTE. FINAL LOCATIN | | | SHALL BE DETERMINED BY OWNER/ ARCHITECT. REVISION # | | | 15090594 DOES NOT SHOW A REVISION TO THE ROOF PLAN NOR | | | WAS SHEET S3 UPDATED TO SHOW NEW LOCATIONS, SHEET M1.3 | | | DOES SHOW ON THE MECHANICAL ROOF TOP SHEET A REVISION | | | SHOWING THE LOCATION FOR 3 NEWLY LOCATED, (NOT | | | HIGHLIGHTED SHOWING A REVISION), ROOF TOP CU UNITS, NO | | | DETAILS UNDER MECHANICAL NOR STRUCTURAL SHEETS!!!!! | | | PLEASE UPDATE ALL RELEVENT SHEETS TO THE NEW LOCATION | | | OF THE 3 NEWLY LOCATED ROOF TOP A/C SPLIT SYSTEMS. WITH | | | 3 CU SPLIT SYSTEMS IF A ROOF TOP A/C STAND IS TO BE | | | INSTALLED. PLEASE PROVIDE THE ATTACHMENT OF THE STAND | | | TO THIS SITE SPECIFIC CONDITION. ALSO PROVIDE | | | ENGINEERING FOR HOW THE C/U UNIT WILL BE ATTACHED TO | | | THE STAND, BY THE ENGINEER OF RECORD. | | | | | | THE STRUCTURAL ENGINEER HAS NOT INDICATED ON ANY PLANS | | | HOW THIS UNIT WILL ATTACH TO THE MWFRS. THE ENGINEER | | | HAS PROVIDED (PERMIT SET OF DRAWINGS) DETAILS ON SHEET | | | S6 FOR THE ATTACHMENT OF THE RTU'S CURB TO THE MWFRS | | | AND THE CLIP SYSTEM FOR MOUNTING THE RTU TO THE CURB. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-10-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-10-07 |
Time |
11:38 |
Rev Time |
|
| Received By |
jwitmer |
Date |
2015-10-07 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2015-10-07 11:05:38 | BUILDING PLAN REVIEW | | | W. P. B. REVISION: 15090594 | | | W. P. B. PERMIT: 14120130 | | | ADD: 1901 S. DIXIE HWY. | | | CONT: SISCA | | | TEL: ( | | | E-MAIL: | | | | | | 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: WED. OCT. 07/2015 | | | ACTION: DENIED | | | | | | 1) SHEET A1.2 THE NEW LAYOUT OF FURNATURE AND EGRESS | | | PLAN APPEARS TO HAVE (2) PINCH POINTS OR MINIMUM | | | REQUIRED EGRESS WIDTH. 2010 FBC-B 1005.1. THERE IS A | | | GREAT DIFFERENCE BETWEEN THE ACCESS AILES AND AISLES. | | | FOR ACCESS AILSES SECTION 1028.9 REFERS YOU BACK TO | | | 1017.4 FOR TABLES AND CHAIRS. THE 2010 FBC-B 1028.9 | | | ASSEMBLY AISLES. SEE 1028.9.1.1 THE MINIMUM WIDTH OF | | | AISLES SERVING SEATING AT TABLES SHALL BE 44 INCHES. | | | PLEASE REVISE SHOWING THE AISLES AT 44 INCHES. THE | | | EXCEPTION IS 36 INCHES WHEN SERVING AN OCCUPANT LOAD OF | | | NOT MORE THAN 50. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2015-11-30 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-11-30 |
Time |
19:25 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-11-30 |
Time |
18:07 |
Sent To |
|
|
| Notes |
| 2015-11-30 19:26:35 | ALL OF THE PREVIOUSLY MENTIONED COMMENTS WERE ADDRESSED | | | AS DELTA 8 REVISION. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-10-15 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-10-15 |
Time |
18:49 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-10-15 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2015-10-15 18:49:23 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE | | | ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH | | | REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE | | | REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED | | | SHALL BE RESUBMITTED FOR ANOTHER REVIEW. | | | 1. IN ADDITION TO THE IN-USE TYPE COVER, THE NEC | | | REQUIRES THAT ALL RECEPTACLES IN WET LOCATIONS BE | | | LISTED/RATED WEATHER RESISTANT. | | | 2. APPLICABLE CODES ARE AS FOLLOWS: FFPC-2012, NFPA | | | 1-2012, NFPA 70 (NEC)-2011, NFPA 72-2010, NFPA 101-2012 | | | AND FBC 5TH EDITION 2014. | | | 3. THE QUOTED FBC SECTION HAS NOTHING TO DO WITH THE | | | RESPECTIVE NOTE OR COMMENT. | | | 4. NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN | | | OUT ADJACENT TO EVERY PEDESTRIAN ENTRY WAY NOT JUST THE | | | MAIN FRONT DOOR. SIGN OUTLET REQ?D BY KANUGA DR. EXIT. | | | 5. DOOR TO ALLEY WAY IS EXCLUDED FROM THE SIGN OUTLET | | | REQUIREMENT. | | | 6. REVISE THE PANEL SCHEDULES AND SUBSEQUENT LOAD CALCS | | | FOR BOTH PANELS A & B. | | | 7. REVISE THE ELECTRICAL RISER DIAGRAM TO MATCH THE | | | PROPOSED SERVICE DISTRIBUTION AND PANEL SCHEDULE. | | | 8. LOCATION OF LIGHTING CONTROL PANEL DIFFERS BETWEEN | | | SHEETS E-1.1 & E-2.1. MAKE THEM MATCH; NEC 210.70(C) | | | REQUIRES THAT THERE BE SUFFICIENT ILLUMINATION AT THE | | | LOCATION OF ELECTRICAL EQUIPMENT. | | | 9. BOTH, THE FBC AND THE NEC REQUIRE STAIR ILLUMINATION | | | FOR NORMAL AND EMERGENCY CONDITIONS. THEREFORE A LIGHT | | | CONTROLLED AT BOTH TOP AND BOTTOM SHALL BE INSTALLED | | | FOR THE STAIRWAY AS WELL AS AN EMERGENCY LIGHT | | | CONNECTED AHEAD OF ANY SWITCHES ON THE SAME CIRCUIT AS | | | THE STAIR LIGHTING. | | | 10. NEC 314.27(C) REQUIRES THAT CEILING OUTLETS FOR | | | PADDLE FANS BE LISTED FOR THE PURPOSE AND CAPABLE OF | | | SUPPORTING THE WEIGHT. | | | 11. BESIDES THE ADDITIONAL LIGHTING REQUIRED FOR THE | | | STAIRWAY, MANDATORY LIGHTING CONTROLS ARE REQUIRED FOR | | | THE SECOND FLOOR STORAGE AREA. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2015-12-08 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2015-12-08 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2015-12-08 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2015-12-08 15:59:25 | REPEAT COMMENT: UPDATED LIFE SAFETY PLAN NOT SUBMITTED. | | | | | | ORIGINAL COMMENT: LIFE SAFETY PLAN: NEW FURNTITURE | | | LAYOUT OBSTRUCTS EGRESS PATHS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2015-11-20 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2015-11-20 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2015-11-20 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2015-11-20 11:29:18 | REPEAT COMMENT: UPDATED LIFE SAFETY PLAN NOT SUBMITTED. | | | | | | ORIGINAL COMMENT: LIFE SAFETY PLAN: NEW FURNTITURE | | | LAYOUT OBSTRUCTS EGRESS PATHS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2015-09-22 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2015-09-22 |
Time |
17:49 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2015-09-22 |
Time |
17:49 |
Sent To |
|
|
| Notes |
| 2015-09-22 17:49:46 | LIFE SAFETY PLAN: NEW FURNTITURE LAYOUT OBSTRUCTS | | | EGRESS PATHS. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
F |
Date |
2015-12-04 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2015-12-04 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2015-12-04 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2015-12-04 16:08:36 | GLASS IN FIELD IS TINITED. HPB APPROVED ONLY CLEAR | | | GLAZING. QUESTIONS CONTACT FRIEDERIKE MITTNER AT | | | 822-1457. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2015-10-28 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2015-10-28 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2015-10-28 |
Time |
11:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-12-04 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2015-12-04 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2015-11-10 |
Time |
10:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-10-28 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2015-10-28 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2015-09-15 |
Time |
13:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2015-11-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-11-17 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-11-17 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2015-11-17 14:08:42 | MECHANICAL PROVISO | | | REVISION PERMIT #15090594 | | | MASTER PERMIT #14120130 | | | 11/17/15 | | | | | | 1) SHEET M1.3 ROOF PLAN MUST BE REVISED TO SHOW THE | | | LOCATIONS OF THE WALK-IN BOX REFRIGERATION CONDENSERS, | | | AND THE MINI-PAK UNIT BY COLDZONE (SEE PERMIT | | | #15110411). | | | 2) WIND LOAD ENGINEERING FOR TIE DOWN OF THE ROOFTOP | | | CONDENSERS AND FOR THE MINI-PAK UNIT SHALL BE SUBMITTED | | | TO THE BUILDING DEPARTMENT PRIOR TO INSPECTION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-10-22 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2015-10-22 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-10-22 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2015-10-22 13:58:27 | 1ST REVIEW: FBC 2010 MECHANICAL | | | REVISION PERMIT #15090594 | | | MASTER PERMIT #14120130 | | | 10/22/15 | | | | | | 1) SHEET M0.1: PROVIDE EQUIPMENT SCHEDULES FOR THE NEW | | | DEF-1 AND PEF-1. | | | 2) M1.1: SHOW THE LOCATIONS OF THE DEF-1 AND PEF-1 | | | EXHAUST OPENINGS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2015-11-13 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2015-11-13 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2015-11-13 |
Time |
15:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2015-10-02 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-10-02 |
Time |
07:36 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-10-01 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2015-10-01 14:36:53 | 1) SUBMIT A NARRATIVE THAT CLEARLY NOTES/EXPLAINS THE | | | CHANGES THAT WERE MADE TO THE SANITARY, GREASY WASTE, | | | WATER AND GAS SYSTEMS. WPB AMENDMENTS TO FBC | | | SEC.107.2.1. | | | 2) THE GREASE FROM THE HOODS IS NOT PERMITTED TO | | | DISCHARGE TO THE GREASE INTERCEPTOR PER 2014 | | | FBC-PLUMBING SEC.1003.1 AND SEC. 202 ( SEE DEFINITION | | | OF GREASE LADEN WASTE). | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2015-10-28 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2015-10-28 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2015-10-28 |
Time |
11:49 |
Sent To |
|
|
| Notes |
|
|