| 2015-09-14 17:11:30 | RESIDENTIAL (R2) FLOORING ALTERATION. BUILDING REVIEW |
| | COMMENTS. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | 1- SOUND INSULATION MATERIAL: |
| | A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE |
| | DEVELOPED TEST DONE IN ACCORDANCE WITH ASTM E 84 OR UL |
| | 723 AS REQUIRED BY SEC. 720.1 OF FBC 5TH EDITION |
| | (2014). |
| | |
| | B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS |
| | (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS |
| | REQUIRED BY SEC. 1207.2 OF FBC 5TH EDITION (2014). |
| | |
| | NOTE: TEST SAMPLE TO MATCH ACTUAL BUILDING |
| | CONSTRUCTION. THICKNESS OF SLAB, SUSPENDED ACOUSTICAL |
| | CEILING, ETC. |
| | |
| | C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS |
| | (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS |
| | REQUIRED BY SEC. 1207.3 OF FBC 5TH EDITION (2014). |
| | |
| | NOTE: TEST SAMPLE TO MATCH ACTUAL BUILDING |
| | CONSTRUCTION. FOR EXAMPLE: THICKNESS OF SLAB, SUSPENDED |
| | ACOUSTICAL CEILINGS (IF INSTALLED), ETC. |
| | |
| | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INLCUDE ALL LABOR, MATERIALS AND |
| | CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC. |
| | 109.3 CITY AMENDMENTS. SPECIFY ROOM AREAS TO HAVE FLOOR |
| | TILE INSTALLATION AND TOTAL SQUARE FOOTAGE. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |