Plan Review Details - Permit 15090428
Plan Review Stops For Permit 15090428
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-10-31 Cont ID  
Sent By skennedy Date 2015-10-31 Time 09:44 Rev Time 0.00
Received By skennedy Date 2015-10-31 Time 09:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-20 Cont ID  
Sent By skennedy Date 2015-10-20 Time 15:47 Rev Time 0.00
Received By skennedy Date 2015-10-20 Time 15:47 Sent To  
Notes
2015-10-20 16:16:391ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL & EXISTING
 BUILDING VOLUMES
  
 THE CODE IN EFFECT LISTED IN THE CODE SUMMARY ON SHEET
 A1.0 IS OUT DATED, SEE ABOVE FOR CURRENT VERSION.
  
 THE PLAN INDICATES ROOFING WINDOWS AND DOORS WILL BE
 REPLACED.
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
 ALTHOUGH THE PLAN NOTES INDICATE AN ENERGY SUBMITTAL
 WILL BE PROVIDED, THE HOME IS EXEMPT FROM THE
 REQUIREMENT AS IT IS CONSIDERED A CONTRIBUTING HISTORIC
 STRUCTURE. EITHER PROVIDE A SUBMITTAL OR REMOVE THE
 NOTES FROM THE PLAN.
  
 FBC-R 315.1 PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-10-31 Cont ID  
Sent By skennedy Date 2015-10-31 Time 09:44 Rev Time 0.00
Received By skennedy Date 2015-10-31 Time 09:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-10-20 Cont ID  
Sent By skennedy Date 2015-10-20 Time 16:29 Rev Time 0.00
Received By skennedy Date 2015-10-20 Time 16:29 Sent To  
Notes
2015-10-20 16:48:361ST REVIEW: FBC 2014 5TH ED.
  
 PLEASE MODIFY THE PLAN TO INDICATE COMPLIANCE WITH THE
 FOLLOWING SECTIONS:
  
 FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED
 BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER
 INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT.
  
 E3703.2 KITCHEN AND DINING AREA RECEPTACLES.
 A MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS SHALL
 BE PROVIDED TO SERVE ALL WALL AND FLOOR RECEPTACLE
 OUTLETS LOCATED IN THE KITCHEN, PANTRY, BREAKFAST AREA,
 DINING AREA OR SIMILAR AREA OF A DWELLING. THE KITCHEN
 COUNTERTOP RECEPTACLES SHALL BE SERVED BY A MINIMUM OF
 TWO 20-AMPERE-RATED BRANCH CIRCUITS, EITHER OR BOTH OF
 WHICH SHALL ALSO BE PERMITTED TO SUPPLY OTHER
 RECEPTACLE OUTLETS IN THE SAME KITCHEN, PANTRY,
 BREAKFAST AND DINING AREA INCLUDING RECEPTACLE OUTLETS
 FOR REFRIGERATION APPLIANCES.
  
 FBCRE4002.14 TAMPER-RESISTANT RECEPTACLES.
 IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE LISTED
 TAMPER-RESISTANT RECEPTACLES.
  
 FBC-R 315.1 ? CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH SLEEPING ROOM.
  
 FBC- 107.3.5.3 ? SMOKE DETECTORS PURSUANT TO FBC-R
 314.3.1 AS REQUIRED FOR NEW DWELLINGS
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-10-29 Cont ID  
Sent By gjohnson Date 2015-10-29 Time 16:43 Rev Time 0.00
Received By gjohnson Date 2015-10-29 Time 16:42 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-09-21 Cont ID  
Sent By gjohnson Date 2015-09-21 Time 16:40 Rev Time 0.00
Received By gjohnson Date 2015-09-21 Time 16:40 Sent To  
Notes
2015-09-21 16:48:24 
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
 GAS COMMENTS:
  
  
  
  
 1. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
 2. TYPE OF GAS, (LP OR NATURAL).
 3. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
 4. GRILL MUST BE SHOWN ON RISER PER WPB AMEND 107.2.1

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-10-07 Cont ID  
Sent By fmittner Date 2015-10-07 Time 13:50 Rev Time 0.00
Received By fmittner Date 2015-10-07 Time 13:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-31 Cont ID  
Sent By skennedy Date 2015-10-31 Time 09:45 Rev Time 0.00
Received By skennedy Date 2015-10-28 Time 13:46 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-20 Cont ID  
Sent By skennedy Date 2015-10-20 Time 16:50 Rev Time 0.00
Received By skennedy Date 2015-09-11 Time 14:50 Sent To  
Notes
2015-09-11 14:51:04R25

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-10-29 Cont ID  
Sent By skennedy Date 2015-10-31 Time 09:45 Rev Time 0.00
Received By gjohnson Date 2015-10-29 Time 16:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-09-22 Cont ID  
Sent By gjohnson Date 2015-09-22 Time 06:49 Rev Time 0.00
Received By gjohnson Date 2015-09-21 Time 16:53 Sent To  
Notes
2015-09-22 07:01:46 
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. SHEET P1 PLUMBING RISER IS NOT SIZED COMPLETELY OR
 PER CODE SHALL BE SIZED TO COMPLY WITH. FBCP SEC 710.1
 MAXIMUM FIXTURE UNIT LOAD.AND TABLE 710.1(1) BUILDING
 DRAINS AND SEWERS.
 2. WASHING MACHINE SHALL BE SHOWN ON RISER AND FLOOR
 PLAN ON SHEET P3 . PER WPB AMEND. SEC 107.2.1
 3. PLEASE PROVIDE WATER RISER. PER.WPB AMEND.
 SEC107.3.5.3(11)

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2015-10-31 Cont ID  
Sent By gjohnson Date 2015-10-29 Time 16:43 Rev Time 0.00
Received By skennedy Date 2015-10-29 Time 16:43 Sent To  
Notes
2015-10-31 09:44:202ND REVIEW: FBC 2014 5TH ED.
  
 NO ROOFING PRODUCT APPRAVAL WAS SUBMITTED. A SEPARATE
 PERMIT WITH A PRODUCT APPROVAL SUBMITTAL REVIEWED BY
 THE DESIGNER OF RECORD IS REQUIRED.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-10-20 Cont ID  
Sent By skennedy Date 2015-10-20 Time 16:48 Rev Time 0.00
Received By skennedy Date 2015-10-20 Time 16:48 Sent To  
Notes
2015-10-20 16:50:111ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL & EXISTING
 BUILDING VOLUMES
  
 THE PLAN INDICATES ROOFING WINDOWS AND DOORS WILL BE
 REPLACED.
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING A SUBMITTAL.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-10-07 Cont ID  
Sent By fmittner Date 2015-10-07 Time 13:50 Rev Time 0.00
Received By fmittner Date 2015-10-07 Time 13:50 Sent To  
Notes
2015-09-18 11:42:489/18/15