Plan Review Details - Permit 15090419
Plan Review Stops For Permit 15090419
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-11-06 Cont ID  
Sent By   Date 2015-11-06 Time 17:29 Rev Time 0.00
Received By   Date 2015-11-06 Time 15:55 Sent To  
Notes
2015-11-23 14:04:3111/23/15 ON MALBARRAN'S DESK. CP

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-24 Cont ID  
Sent By   Date 2015-09-24 Time 12:30 Rev Time 0.00
Received By jwitmer Date 2015-09-24 Time 11:58 Sent To  
Notes
2015-09-24 11:58:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090419
 ADD: 700 S. ROSEMARY AVE. SUITE # 208
 CONT: JOHN A. DURANICO
 TEL: (561)683-9972
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. SEPT. 24/ 2015
 ACTION: DENIED
  
 1) SHEET A-1 SHOWS A NEW ACCESSIBLE STALL IN THE LADIES
 RESTROOM. THE BACK WALL IS NOT DIMENSIONED, BUT THE
 WALLS ACROSS FORM THE STALL LINE UP AND THE 5FT. 4
 INCHES AND 1 FT. 7 1/2 INCHES ADD UP TO EQUAL 6 FT. 9
 1/2 INCHES. THE MINIMUM LENGTH OF THE BACK WALL IS 7
 FT. 1 INCH WITH THE LAV BEING SET AT 15 INCHES FORM THE
 WALL AND A WIDTH OF 19 INCHES. 2014 FBC-ACCESSIBILITY
 CODE 604.3.2 & 604.8.1.
  
 2) THE DOOR SHOULD BE NO FURTHER AWAY FROM THE CORNER
 OF THE TOILIET COMPARTMENT THAN 4 INCHES. 2014
 FBC-ACCESSIBLITY CODE 604.8.1.2.
  
 3) THE DOOR TO THE ACCESSIBLE STALL IS NOT DIMENSIONED,
 PLEASE SHOW COMPLIANCE WITH 2014 FBC-ACCESSIBLITY CODE
 404.2.3.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-11-23 Cont ID  
Sent By albarran Date 2015-11-23 Time 19:31 Rev Time 0.00
Received By albarran Date 2015-11-23 Time 19:20 Sent To I
Notes
2015-11-23 19:33:45THOUGH THIS WAS PREVIOUSLY APPROVED, NEW SHEETS WERE
 SUBMITTED SO IT WAS REVIEWED FOR COMPLIANCE ONCE AGAIN.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-10-22 Cont ID  
Sent By albarran Date 2015-10-22 Time 14:59 Rev Time 0.00
Received By albarran Date 2015-10-22 Time 14:53 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-11-04 Cont ID  
Sent By pleduc Date 2015-11-04 Time   Rev Time 0.00
Received By pleduc Date 2015-11-04 Time 14:59 Sent To  
Notes
2015-11-04 15:05:24THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THESE PREVIOUSLY DOCUMENTED COMMENTS ARE RESTATED FOR
 THIS REVIEW.
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF WALLS
 REQUIRES AN EVALUATION.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-09-14 Cont ID  
Sent By pleduc Date 2015-09-14 Time   Rev Time 0.00
Received By pleduc Date 2015-09-14 Time 11:55 Sent To  
Notes
2015-09-14 12:41:11THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF WALLS
 REQUIRES AN EVALUATION.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-23 Cont ID  
Sent By albarran Date 2015-11-23 Time 19:36 Rev Time 0.00
Received By albarran Date 2015-10-28 Time 09:32 Sent To  
Notes
2015-11-23 19:36:0611/23/15 PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO SMALL READY BIN "M":. MA
2015-10-30 09:33:05B05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-22 Cont ID  
Sent By albarran Date 2015-10-22 Time 15:00 Rev Time 0.00
Received By albarran Date 2015-09-11 Time 15:10 Sent To  
Notes
2015-10-22 15:01:4310/22/15 PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO SMALL READY BIN "M". MA
2015-09-11 15:10:17B10

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2015-11-13 Cont ID  
Sent By ccole Date 2015-11-05 Time 13:35 Rev Time 0.00
Received By ccole Date 2015-11-05 Time 13:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-09-21 Cont ID  
Sent By ccole Date 2015-09-21 Time 15:56 Rev Time 0.00
Received By ccole Date 2015-09-21 Time 15:55 Sent To  
Notes
2015-09-21 16:00:341ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090419
 9/21/15
  
 1) THE SCOPE OF WORK NOTES INDICATE RECONFIGURING OF
 "AC FIXTURES/VENTILATION", HOWEVER THERE ARE NO DETAILS
 ON THE PLANS EXCEPT ONE RELOCATED DIFFUSER. PLEASE SHOW
 ALL OF THE PROPOSED CHANGES ON THE PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-11-02 Cont ID  
Sent By gjohnson Date 2015-11-02 Time 17:01 Rev Time 0.00
Received By gjohnson Date 2015-11-02 Time 17:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-09-30 Cont ID  
Sent By gjohnson Date 2015-09-30 Time 16:00 Rev Time 0.00
Received By gjohnson Date 2015-09-30 Time 15:59 Sent To  
Notes
***NONE***