| 2015-09-14 14:21:16 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 5TH EDITION 2014 |
| | |
| | TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED |
| | |
| | PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | DOCUMENTS SUBMITTED - ONE SET OF ASTM E 90 FOR QEP 6 MM |
| | CORK, QEP SPEC SHEET, BADGER CORK FLAME SPREAD TEST |
| | |
| | TWO COMPLETE COLLATED SETS OF PERMIT DOCUMENTS |
| | REQUIRED. |
| | |
| | |
| | 1. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART |
| | OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN |
| | DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW |
| | IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT |
| | BELOW WILL NOT BE ALTERED. |
| | |
| | PLEASE PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | 2. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | THE TEST REPORT IS FOR BADGER CORK. THE RELATIONSHIP |
| | BETWEEN BADGER CORK AND QEP IS NOT CLEAR. PROVIDE A |
| | COPY OF ASTM E 84 FOR QEP 6 MM CORK. |
| | |