Plan Review Details - Permit 15090376
Plan Review Stops For Permit 15090376
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-09-22 Cont ID  
Sent By shill Date 2015-09-22 Time 10:09 Rev Time 0.00
Received By shill Date 2015-09-22 Time 10:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-09-21 Cont ID  
Sent By shill Date 2015-09-21 Time 18:07 Rev Time 0.00
Received By shill Date 2015-09-21 Time 18:07 Sent To  
Notes
2015-09-21 18:12:56****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. ONE COPY OF THE PRODUCT APPROVAL FOR A 2014 ATTIC
 VENT PRODUCT APPROVAL WAS SUBMITTED.
  
 TWO SETS ARE REQUIRED, FBC 107.
  
 THE PRODUCT APPROVAL WAS SUBMITTED WITH TWO PAGES TO A
 SHEET. THIS RESULTS IN A PRODUCT APPROVAL WHICH IS NOT
 LEGIBLE. THE PRODUCT APPROVAL IS TO BE FULL SIZE (ONE
 PAGE ON AN 8.5" X 11" SHEET OF PAPER). THE PRODUT
 APPROVALS ARE REQUIRED TO BE REVIEWED IN PLAN REVIEW,
 INSPECTED IN THE FIELD, AND SCANNED FOR RECORD
 RETENTION. WHEN PRINTED HALF SIZE, THE PRODUCT APPROVAL
 IS TOO DIFFICULT TO READ.
  
 PROVIDE TWO FULL SIZE COPIES OF THE PRODUCT APPROVAL.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-17 Cont ID  
Sent By shill Date 2015-09-17 Time 11:03 Rev Time 0.00
Received By shill Date 2015-09-17 Time 11:03 Sent To  
Notes
2015-09-17 11:05:51****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LSIT:
  
 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 THE SOLAR VENT. PROVIDE THE COVER SHEET WHICH SHOWS THE
 APPROVAL NUMBER, CODE VERSION, AND STATUS
 (WWW.FLORIDABUILDING.ORG). THE COVER SHEET WILL STATE
 THAT THE CODE IS FBC 2014. THE EVALUATION REPORT
 PROVIDED IS EXPIRED AS IT MAKES REFERENCE TO FBC 2010
 (GOVERNING CODE IS FBC 5TH EDITION, AKA FBC 2014).
  
 2ND REVIEW, DIFFERENT PRODUCT APPROVAL SUBMITTED BUT
 STILL FBC 2010. THIS PRODUCT APPROVAL IS EXPIRED.
 GOVERNING CODE CHANGED EFFECTIVE JUNE 31, 2015, SO
 PRODUCT APPROVALS WITH A CODE OF FBC 2010 ARE ALL
 EXPIRED.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-11 Cont ID  
Sent By shill Date 2015-09-11 Time 18:10 Rev Time 0.00
Received By shill Date 2015-09-11 Time 18:10 Sent To  
Notes
2015-09-11 18:11:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS, FS 471. POOR QUALITY PHOTOCOPIES WERE
 SUBMITTED.
  
 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 THE SOLAR VENT. PROVIDE THE COVER SHEET WHICH SHOWS THE
 APPROVAL NUMBER, CODE VERSION, AND STATUS
 (WWW.FLORIDABUILDING.ORG). IT APPEARS THAT THE
 EVALUATION REPORT PROVIDED IS EXPIRED AS IT MAKES
 REFERENCE TO FBC 2010 (GOVERNING CODE IS FBC 5TH
 EDITION, AKA FBC 2014).
  
 3. SEE INSTALLATION NOTES, ITEM 7.3, "PRODUCT SHALL BE
 INSTALLED ON ROOFS UTILIZING ASPHALT SHINGLES ONLY".
  
 4. REVISE ROOF PLAN TO SHOW THE LOCATION OF PROPOSED
 ROOF VENT AND ROOF SHEATHING INFORMATION (TYPE OF ROOF
 SHEATHING, THICKNESS). THIS INFORMATION IS REQUIRED DUE
 TO LIMITATIONS FOR THE ROOF VENT.
  
 5. PURPOSE OF PROPOSED VENT IS NOT CLEAR. FLAT DECK
 ROOFS TYPICALLY DO NOT HAVE AN ATTIC SPACE. WHAT IS
 BEING VENTED?
  
 6. CONTRACTOR TO CONFIRM THAT A FIRE BARRIER IS
 PROPOSED. CONTRACTOR HAS SELECTED THE ASSEMBLY ON PAGE
 12 OF 13, NOA 12-1019.34, SYSTEM TYPE E. NOTE THAT THE
 SYSTEM PROPOSED INCLUDES A FIRE BARRIER. THIS IS NOT
 OPTIONAL. OPTIONAL ITEMS WILL STATE (OPTIONAL); FOR AN
 EXAMPLE OF AN OPTIONAL COMPONENT, SEE PAGE 9, VAPOR
 RETARDER. SINCE THE FIRE BARRIER IS NOT "OPTIONAL" IT
 IS A PART OF THIS ASSEMBLY AND IS REQUIRED.
  
  
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-09-11 Cont ID  
Sent By fmittner Date 2015-09-11 Time 11:22 Rev Time 0.00
Received By fmittner Date 2015-09-11 Time 11:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-09-21 Cont ID  
Sent By shill Date 2015-09-21 Time 18:13 Rev Time 0.00
Received By shill Date 2015-09-21 Time 18:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-17 Cont ID  
Sent By shill Date 2015-09-17 Time 11:20 Rev Time 0.00
Received By shill Date 2015-09-17 Time 11:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-11 Cont ID  
Sent By shill Date 2015-09-11 Time 18:11 Rev Time 0.00
Received By shill Date 2015-09-10 Time 11:44 Sent To  
Notes
2015-09-11 11:44:43SKENNEDY