Plan Review Details - Permit 15090350
| Plan Review Stops For Permit 15090350 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2015-10-06 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-10-06 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-10-06 |
Time |
08:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-09-16 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-09-16 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-09-16 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2015-09-16 14:18:07 | 1ST REVIEW: FBC 2014 5TH ED. | | | | | | PLANS ARE DEFICIENT. PROVIDE DETAILS PER THE BELOW | | | SECTION: | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS | | | SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING | | | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | | BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2015-10-06 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-10-06 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-10-06 |
Time |
08:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-09-16 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-09-16 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-09-16 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2015-09-16 14:18:42 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2100 | | | | | | PLANS ARE DEFICIENT. PROVIDE DETAILS PER THE BELOW | | | SECTION: | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS | | | SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING | | | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | | BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2015-10-06 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-10-06 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-10-06 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2015-10-06 08:48:13 | BY SEPARATE PERMIT. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2015-09-16 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-09-16 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-09-16 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2015-09-16 14:19:09 | 1ST REVIEW: FBC 2014 5TH ED. | | | | | | PLANS ARE DEFICIENT. PROVIDE DETAILS PER THE BELOW | | | SECTION: | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS | | | SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING | | | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | | BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-09-16 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-09-16 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-09-10 |
Time |
14:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2015-10-06 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-10-06 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-10-06 |
Time |
08:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2015-09-16 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-09-16 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-09-16 |
Time |
14:15 |
Sent To |
Z |
|
| Notes |
| 2015-09-16 14:18:18 | 1ST REVIEW: FBC 2014 5TH ED. | | | | | | PLANS ARE DEFICIENT. PROVIDE DETAILS PER THE BELOW | | | SECTION: | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS | | | SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING | | | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | | BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2015-09-16 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-09-16 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-09-16 |
Time |
14:40 |
Sent To |
B |
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |