Plan Review Details - Permit 15090333
Plan Review Stops For Permit 15090333
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-12-10 Cont ID  
Sent By jwitmer Date 2015-12-10 Time 07:00 Rev Time 0.00
Received By jwitmer Date 2015-12-10 Time 06:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-29 Cont ID  
Sent By jwitmer Date 2015-09-29 Time 06:46 Rev Time 0.00
Received By jwitmer Date 2015-09-29 Time 05:48 Sent To  
Notes
2015-09-29 06:56:42 
 BUILDING PLAN REVIEW
 W. P. B. REVISION: 15090333
 W. P. B. PERMIT: 14061187
 ADD: 900 FLORIDA AVE.
 CONT: COASTAL
 TEL: (
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. SEPT. 29/ 2015
 ACTION: DENIED
  
 1) COMPLIED. ROBERT BROWN HAD RECEIVED A REQUEST FOR
 EXTENSION BUT HAD NOT ENTERED IT IN THE COMPTER. PLEASE
 NOTE PERMIT NUMBER 14061187 EXPIRED ON 8/25/15 SEE
 LISTED EXPERATION DATE OF EXTENTION. WILL NEED TO
 RENEWAL PERMIT. CONTRACTOR WILL
 NEED TO SUPPLY A LETTER WHY THE PERMIT SHOULD BE
 RENEWED.
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION. 105.3.2 TIME LIMITATION OF APPLICATION.
 AN APPLICATION FOR A PERMIT FOR ANY PROPOSED WORK SHALL
 BE DEEMED TO HAVE BEEN ABANDONED AND INVALID, SIX
 MONTHS AFTER THE DATE OF FILING, OR FOR ANY SIX MONTH
 PERIOD OF ABANDONMENT OR SUSPENSION DURING THE
 APPLICATION PROCESS, UNLESS SUCH APPLICATION HAS BEEN
 PURSUED IN GOOD FAITH OR A PERMIT HAS BEEN ISSUED;
 EXCEPT THAT THE BUILDING OFFICIAL IS AUTHORIZED TO
 GRANT ONE OR MORE EXTENSIONS OF TIME FOR ADDITIONAL
 PERIODS NOT EXCEEDING THREE MONTHS EACH. THE EXTENSION
 SHALL BE REQUESTED IN WRITING PRIOR TO THE ABANDONMENT
 DATE AND JUSTIFIABLE CAUSE DEMONSTRATED. ABANDONED
 APPLICATIONS SHALL SUBJECT TO DESTRUCTION IN ACCORDANCE
 WITH STATE LAW. THE FEE FOR RENEWAL, EXTENSION OF A
 PERMIT
 APPLICATION SHALL BE SET FORTH BY THE ADMINISTRATIVE
 AUTHORITY.
  
 2) UPDATE ALL GA FLOOR PLAN SHEET TO CORRESPOND WITH
 GA3.00 WITH THE AMOUNT OF REQUIRED ACCESSIBLEPARKING
 AND VAN REQUIRED PARKING, DISCREPANCY IN PLANS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 2A) SHEET 0101-GA0.01 INDICATES THERE ARE 127 SELF PARK
 STALLS WHICH WILL REQUIRE A TOTAL OF 5 ACCESSIBLE
 PARKING SPACES, ON SHEETS 0105-GA1.00 & 0101-GA0.01
 ONLY SHOW ONE ACCESSIBLE PARKING SPACE. OF THE 5
 ACCESSIBLE PARKING SPACES, ONE IS TO BE MARKED, VAN
 ACCESSIBLE, SEE 2010 FBC-ACCESS. CODE 208.2.4. VAN
 PARKING SPACES. 208.2 MINIMUM NUMBER ACCESSIBLE PARKING
 SPACES.
  
 2B) VAN ACCESSIBLE PARKING SPACES SHALL BE IDENTIFIED
 AS REQUIRED BY 2010 FBC-ACCESS. CODE 502.6.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-12-16 Cont ID  
Sent By skennedy Date 2015-12-16 Time 10:13 Rev Time 0.00
Received By skennedy Date 2015-12-16 Time 10:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-11-13 Cont ID  
Sent By albarran Date 2015-11-13 Time 17:00 Rev Time 0.00
Received By skennedy Date 2015-11-13 Time 17:00 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-12-16 Cont ID  
Sent By cranford Date 2015-12-16 Time 15:48 Rev Time 0.00
Received By cranford Date 2015-12-16 Time 15:48 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-11-19 Cont ID  
Sent By mgonzale Date 2015-11-19 Time 09:08 Rev Time 0.00
Received By cranford Date 2015-11-19 Time 08:01 Sent To  
Notes
2015-11-19 09:09:25ALSO SEE E14020003

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-12-09 Cont ID  
Sent By wjolin Date 2015-12-09 Time 11:34 Rev Time 0.00
Received By wjolin Date 2015-12-09 Time 11:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-09-18 Cont ID  
Sent By wjolin Date 2015-09-18 Time 13:35 Rev Time 0.00
Received By wjolin Date 2015-09-18 Time 13:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-16 Cont ID  
Sent By lmarchan Date 2015-12-16 Time 16:06 Rev Time 0.00
Received By lmarchan Date 2015-11-20 Time 15:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-19 Cont ID  
Sent By cranford Date 2015-11-19 Time 09:09 Rev Time 0.00
Received By cranford Date 2015-09-16 Time 09:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-12-01 Cont ID  
Sent By tklarge Date 2015-12-01 Time 11:49 Rev Time 0.00
Received By tklarge Date 2015-11-30 Time 06:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-10-02 Cont ID  
Sent By jwitmer Date 2015-10-02 Time 06:55 Rev Time 0.00
Received By tklarge Date 2015-10-02 Time 05:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-03-08 Cont ID  
Sent By skennedy Date 2016-03-08 Time 10:43 Rev Time 0.00
Received By skennedy Date 2016-02-29 Time 14:37 Sent To  
Notes
2016-02-29 14:38:06PEDDS ROUTED TO SKENNEDY

Review Stop Z ZONING
Rev No 2 Status P Date 2015-12-15 Cont ID  
Sent By eschneid Date 2015-12-15 Time 16:39 Rev Time 0.50
Received By eschneid Date 2015-12-15 Time 16:16 Sent To  
Notes
2015-12-15 16:40:40PASSED W/PROVISOS
  
 1) IN ACCORDANCE WITH SECTION 94-111(E)(1) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS, SINCE TANDEM
 PARKING SPACES ARE BEING USED TO PROVIDE REQUIRED
 PARKING THE APPLICANT SHALL RECORD A RESTRICTIVE
 COVENANT REQUIRING THAT THE SURFACE PARKING LOT BE
 MAINTAINED AS A VALET ONLY FACILITY. THE RESTRICTIVE
 COVENANT SHALL BE RECORDED PRIOR TO THE ISSUANCE OF THE
 CERTIFICATE OF OCCUPANCY FOR THE HILTON CONVENTION
 CENTER HOTEL.
  
 2) SITE LIGHTING REQUIRES SEPARATE PERMIT WITH PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2015-10-02 Cont ID  
Sent By eschneid Date 2015-10-02 Time 14:12 Rev Time 0.25
Received By eschneid Date 2015-10-02 Time 14:12 Sent To  
Notes
2015-10-02 14:19:11FAILED
  
 THE NEW PARKING LOT LAYOUT HAS NOT BEEN REVIEWED BY THE
 PLANS AND PLATS REVIEW COMMITTEE. THE REVIEW IS
 SCHEDULED FOR THE OCTOBER 14, 2015 PPRC MEETING.
  
 ZONING STAFF WILL NOT REVIEW THE SUBMITTAL UNTIL AFTER
 THE COMMENTS FROM THE PPRC HAVE BEEN ISSUED AND ANY
 CORRECTIONS MADE.
  
 THIS WILL NOT COUNT AS A REVIEW ROUND FOR ZONING.
  
 PLEASE NOTE THAT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT WILL BE REQUIRED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.