Plan Review Details - Permit 15090189
Plan Review Stops For Permit 15090189
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-01-07 Cont ID  
Sent By jgomez Date 2016-01-07 Time 18:08 Rev Time 0.00
Received By jgomez Date 2016-01-07 Time 18:07 Sent To  
Notes
2016-01-07 18:16:15 
 NOTE: THESE COMMENTS APPLY TO PERMIT NUMBERS 15090189
 AND 15090192
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE ENERGY CALCULATIONS SUBMITTED FOR THE NEW
 GARAGE/OFFICE:
 A) CLIMATE ZONE ON PAGE 2 OF 4 IS INCORRECT. SEE TABLE
 R301.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 B) THERE IS NOT KITCHEN. SEC. R103.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 C) CLARIFY WHY THERE IS NOT R-VALUE ON THE FLOOR
 INFORMATION ON PAGE 2 OF 4. NEED INSULATION BETWEEN
 CONDITIONED SPACE AND UN-CONDITIONED SPACE.
 D) THE CEILING R-VALUE ON PAGE 2 OF 4 DOESN'T MATCH
 CEILING R-VALUE GIVEN ON PAGE 1 OF 4.
 E) INSULATED DOOR SHOWN ON PAGE 3 OF 4 DOESN'T MATCH
 PLANS AND PRODUCT APPROVALS SUBMITTED. THIS DOOR NEEDS
 TO BE INCLUDED IN GLASS AREA.
 F) WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T
 MATCH PLANS. REVISE GLASS SQUARE FOOTAGE ON EACH
 BUILDING ORIENTATION TO MATCH PLANS. AND MISSING
 INFORMATION FOR WEST ELEVATION WINDOW.
 G) REVISE WINDOWS OVERHANG SEPARATION TO MATCH PLANS.
 H) COMPLETE/CHECK THE AIR BARRIER AND INSULATION
 INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1
 SUBMITTED.
 NOTE: LABELS FOR DOORS AND WINDOWS U-FACTOR AND SHGC
 FACTORS SPECIFIED ON THE ENERGY CALCULATIONS WILL BE
 REQUIRED FOR INSPECTION WHEN ENERGY CALCULATIONS ARE
 NOT USING THE DEFAULT FACTOR FOR GLAZING.
  
 2- OWNER/AGENT TO SIGN AND DATE ENERGY CALCULATIONS FOR
 THE MAIN HOUSE ADDITION.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) RELOCATED FIXED FRENCH DOORS SHOWN ON DOOR SCHEDULE
 FOR MAIN HOUSE ADDITION (DOOR SCHEDULE NOT CHANGED).
 B) MODIFIED BITUMEN FOR GARAGE/HOME OFFICE TERRACE THAT
 IS DESIGNED TO RECEIVE STONE AS SPECIFIED ON PLANS.
 AND, CLEARLY IDENTIFY APPROVED ASSEMBLY AND PROVIDE
 SIGNED AND SEALED RAS 117 CALCULATIONS IF REQUIRED.
 INFORMATION SUBMITTED IS NOT A PRODUCT APPROVAL.
  
 4- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-12-09 Cont ID  
Sent By jgomez Date 2015-12-09 Time 11:00 Rev Time 0.00
Received By jgomez Date 2015-12-09 Time 11:00 Sent To M
Notes
2015-12-09 11:01:53RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE: THESE COMMENTS APPLY TO PERMIT NUMBERS 15090189
 AND 15090192 (ADDITION AND MAIN HOUSE RESPECTIVELY)
  
 1- ENGINEER'S TERRACE GUARDRAILS AND STAIRS HANDRAIL
 DRAWINGS SUBMITTED TO BE APPROVED BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL. SEC. 107.3.4.2 CITY
 AMENDMENTS.
  
 2- ENERGY CALCULATIONS CALL FOR R-9.2 INSULATION ON THE
 CONCRETE BLOCK WALL. ARCHITECTURAL PLANS CALL FOR R-4.2
 FOIL AND R-5 POLYSTYRENE FOAM INSULATION. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW THE TWO
 INSULATIONS ARE GOING TO BE INSTALLED TOGETHER. SEC.
 R103.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 3- ENERGY CALCULATIONS SUBMITTED FOR THE NEW
 GARAGE/OFFICE:
 NOTE: COORDINATE PLANS AND ENERGY CALCULATIONS TO AVOID
 CONFLICTS OR DELAYS.
  
 A) CLIMATE ZONE ON PAGE 2 OF 4 IS INCORRECT. SEE TABLE
 R301.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 I APOLOGIZE, I MISSED THIS ON FIRST REVIEW.
  
 B) THERE IS NOT KITCHEN ON PLANS. REVISE AS REQUIRED.
 SEC. R103.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). (REPEAT COMMENT).
  
 C) JUSTIFY WHY 6 OCCUPANTS IN THIS HOME OFFICE?. ARE
 THERE 6 OCCUPANTS AT ALL TIMES?. IS THIS A "COMMERCIAL
 OFFICE"?. THE CODE DOESN'T ALLOW ANY FACTOR EXTRA
 FACTORS THAT WILL AFFECT THE EQUIPMENT SIZING. SEC.
 403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 (REPEAT COMMENT).
 NOTE: EQUIPMENT SIZING CALCULATIONS ARE USING 8
 OCCUPANTS. WHY?
  
 D) CLARIFY WHY THERE IS NOT R-VALUE ON THE FLOOR
 INFORMATION ON PAGE 2 OF 4. NEED INSULATION BETWEEN
 CONDITIONED SPACE AND UN-CONDITIONED SPACE. ACCORDING
 TO A/C PLAN SUBMITTED THE GARAGE BELOW IS NOT AIR
 CONDITIONED. ALSO, THE FINISH FLOOR IS WOOD NOT CARPET.
 SEE PLANS AND REVISE AS REQUIRED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT
 COMMENT).
  
 E) ROOF INFORMATION ON PAGE 2 OF 4 DOESN'T MATCH PLANS.
 SEC. R103.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). (REPEAT COMMENT).
  
 F) THE CEILING R-VALUE ON PAGE 2 OF 4 DOESN'T MATCH
 CEILING R-VALUE GIVEN ON PAGE 1 OF 4. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 G) PROVIDE THE WATER HEATER INFORMATION. (REPEAT
 COMMENT).
  
 H) INSULATED DOOR SHOWN ON PAGE 3 OF 4 DOESN'T MATCH
 PLANS AND PRODUCT APPROVALS SUBMITTED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT
 COMMENT).
  
 I) WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T
 MATCH PLANS. REVISE GLASS SQUARE FOOTAGE ON EACH
 BUILDING ORIENTATION TO MATCH PLANS. AND MISSING
 INFORMATION FOR WEST ELEVATION WINDOW. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT
 COMMENT).
  
 J) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R103.2 OF FBC-ENERGY CONSERVATION,
 5TH EDITION (2014). (REPEAT COMMENT).
  
 K) COMPLETE/CHECK THE AIR BARRIER AND INSULATION
 INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1
 SUBMITTED.
  
 NOTE: LABELS FOR DOORS AND WINDOWS U-FACTOR AND SHGC
 FACTORS SPECIFIED ON THE ENERGY CALCULATIONS WILL BE
 REQUIRED FOR INSPECTION WHEN ENERGY CALCULATIONS ARE
 NOT USING THE DEFAULT FACTOR FOR GLAZING.
  
 4- ENERGY CALCULATIONS FORM R402-2014 SUBMITTED FOR THE
 MAIN HOUSE ADDITION:
 NOTE: COORDINATE PLANS AND ENERGY CALCULATIONS TO AVOID
 CONFLICTS OR DELAYS.
  
 A) FLOOR TYPE ON ITEM #8 IS INCORRECT. SEE PLANS AND
 REVISE AS REQUIRED. SEC. R103.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). (REPEAT COMMENT).
  
 B) WALL TYPE AND INSULATION ON ITEM #9 IS INCORRECT.
 SEE PLANS AND REVISE AS REQUIRED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT
 COMMENT).
  
 C) R-VALUE SHOWN ON THE ITEM #10 DOESN'T MATCH R-VALUE
 SHOWN ON PLANS. NOTE: IF USING THIS PRESCRIPTIVE FORM
 THE R-VALUE REQUIRED IS R-30. ARCHITECTURAL PLANS WILL
 NEED TO BE REVISED. SEC. R103.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) HOME OFFICE INSWING ENTRY DOOR AS SHOWN ON PLANS.
 RESPONSE: PLANS NO REVISED SHOWING OUTSWING DOOR.
  
 B) RELOCATED FIXED FRENCH DOORS SHOWN ON DOOR SCHEDULE
 FOR MAIN HOUSE ADDITION.
  
 C) MODIFIED BITUMEN FOR FLAT ROOFS. AND, CLEARLY
 IDENTIFY APPROVED ASSEMBLY AND PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE: NO PRODUCT APPROVAL WAS SUBMITTED. NOTE: RAS
 117 CALCULATIONS FROM QEA NEED CLARIFICATION. ENGINEER
 TO CLARIFY WHY ZONE #2 AND ZONE #3 ARE THE SAME ON THIS
 PROJECT.
  
 D) MODIFIED BITUMEN FOR GARAGE/HOME OFFICE TERRACE THAT
 IS DESIGNED TO RECEIVE STONE AS SPECIFIED ON PLANS.
 AND, CLEARLY IDENTIFY APPROVED ASSEMBLY AND PROVIDE
 SIGNED AND SEALED RAS 117 CALCULATIONS IF SELECTED
 ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY
 SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE: NO PRODUCT APPROVAL WAS SUBMITTED. NOTE: RAS
 117 CALCULATIONS FROM QEA NEED CLARIFICATION. ENGINEER
 TO CLARIFY WHY ZONE #2 AND ZONE #3 ARE THE SAME ON THIS
 PROJECT.
  
 6- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMITT DETACHED OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-26 Cont ID  
Sent By jgomez Date 2015-10-26 Time 12:20 Rev Time 0.00
Received By jgomez Date 2015-10-26 Time 12:10 Sent To  
Notes
2015-10-26 12:22:18RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE: THESE COMMENTS APPLY TO PERMIT NUMBERS 15090189
 AND 15090192.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- SHEET A100: IDENTIFY WHAT'S IN THE NEW LAUNDRY AREA
 AND NEW MUD ROOM. THERE ARE NO NAMES FOR THE STAFF
 DRAWN ON THE FLOOR PLAN. IDENTIFY EVERYTHING THAT IS
 DRAWN IN THE NEW LAUNDRY AREA AND NEW MUD ROOM. SEC.
 107.2.1 CITY AMENDMENTS.
  
 3- SHEET A101:
 A) DOWNSPOUTS SHOWN ON ALL EXTERIOR ELEVATIONS TO
 COMPLY WITH SEC. R318.5 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014). REVISE ELEVATIONS AS REQUIRED.
  
 B) REVISE HEIGHT OF HANDRAIL SHOWN ON THE EAST
 ELEVATION TO COMPLY WITH SEC. R311.7.8.1 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF NEW TERRACE GUARDRAILS
 SHOWING COMPLIANCE WITH THE LIVE LOADS OF TABLE R301.5
 OF FBC-RESIDENTIAL, 5TH EDITION (2014) AND WITH THE
 SPECIFICATIONS OF SEC. R312 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 4- SHEET A102:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 VENTILATION AND ACCESS FOR THE UNDER FLOOR SPACE AT NEW
 LAUNDRY/BATHROOM AREA SHOWING COMPLIANCE WITH SEC. R408
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) DOWNSPOUTS SHOWN ON ALL EXTERIOR ELEVATIONS TO
 COMPLY WITH SEC. R318.5 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014). REVISE ELEVATIONS AS REQUIRED.
  
 5- SPECIFY VENTILATION FOR THE NEW GARAGE/OFFICE
 ADDITION AND FOR THE NEW LAUNDRY/BATHROOM ADDITIONS
 SHOWING COMPLIANCE WITH SEC. R806 OF FBC-RESIDENTIAL,
 5TH EDITION (2014). IF DESIGNING AN UNVENTED ATTIC,
 THEN PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 SHOWING COMPLIANCE WITH SEC. R806.5 OF FBC-RESIDENTIAL,
 5TH EDITION (2014). IF USING ICYNENE OR ANY OTHER FOAM
 INSULATION, THEN PROVIDE MANUFACTURER'S SPECS REVIEWED
 IN WRITING BY THE ARCHITECT OF RECORD.
 NOTE: COORDINATE WITH ENERGY CALCULATIONS TO AVOID
 CONFLICTS OR DELAYS.
  
 6- PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE R-11
 INSULATION SPECIFIED ON WALL SECTION 1 ON SHEET A103
 AND WALL TYPES ON SHEET A104. SEC. R103.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 NOTE: COORDINATE WITH ENERGY CALCULATIONS TO AVOID
 CONFLICTS OR DELAYS.
  
 7- SHEET A104: R-VALUE INSULATION SHOWN ON DOORS AND
 WINDOWS DETAILS TO MATCH R-VALUE SHOWN ON THE WALL
 TYPES. SEC. 107.2.1 CITY AMENDMENTS. NOTE: COORDINATE
 WITH ITEM #7 ABOVE.
  
 8- PROVIDE DETAILS AND SPECIFICATIONS FOR CEILING
 ASSEMBLY BETWEEN GARAGE AND SECOND FLOOR OFFICE SHOWING
 COMPLIANCE WITH INSULATION SPECIFIED ON THE ENERGY
 CALCULATIONS. . SEC. R103.2 OF FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
 NOTE: COORDINATE WITH ENERGY CALCULATIONS TO AVOID
 CONFLICTS OR DELAYS.
  
 9- NEW LAUNDRY/BATHROOM ADDITION ON SHEET S-1: CLARIFY
 FLOOR FRAMING WITH 2X10 PT WOOD JOISTS AND 6" RECESS
 FOR NEW SHOWER. SEC. 107.2.1 CITY AMENDMENTS.
  
 10- ENGINEER TO PROVIDE DESIGN PRESSURES FOR WINDOWS
 AND DOORS. WINDOWS AND DOORS DESIGN PRESSURES SHOWN ON
 THE EXTERIOR ELEVATIONS DON'T CORRESPOND TO THE
 EXPOSURE "C" AND HEIGHT SPECIFIED BY THE ENGINEER ON
 SHEET S-3. SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 11- ENERGY CALCULATIONS SUBMITTED FOR THE NEW
 GARAGE/OFFICE:
 NOTE: COORDINATE PLANS AND ENERGY CALCULATIONS TO AVOID
 CONFLICTS OR DELAYS.
  
 A) CEILING INFORMATION ON ITEM #10 DOESN'T MATCH PLANS.
 PLANS DON'T SHOW VENTED ATTIC. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) THERE IS NOT KITCHEN ON PLANS. REVISE AS REQUIRED.
 SEC. R103.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) JUSTIFY WHY 6 OCCUPANTS IN THIS HOME OFFICE?. ARE
 THERE 6 OCCUPANTS AT ALL TIMES?. IS THIS A "COMMERCIAL
 OFFICE"?. THE CODE DOESN'T ALLOW ANY FACTOR EXTRA
 FACTORS THAT WILL AFFECT THE EQUIPMENT SIZING. SEC.
 403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 D) CLARIFY WHY THERE IS NOT R-VALUE ON THE FLOOR
 INFORMATION ON PAGE 2 OF 4. ALSO, THE FINISH FLOOR IS
 WOOD NOT CARPET. REVISE AS REQUIRED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 E) ROOF INFORMATION ON PAGE 2 OF 4 DOESN'T MATCH PLANS.
 SEC. R103.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 F) ATTIC AND CEILING INFORMATION ON PAGE 2 OF 4 DOESN'T
 MATCH PLANS. ATTIC IS NOT VENTED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 G) INSULATED DOOR SHOWN ON PAGE 3 OF 4 DOESN'T MATCH
 PLANS AND PRODUCT APPROVALS SUBMITTED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 H) WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T
 MATCH PLANS. REVISE GLASS SQUARE FOOTAGE ON EACH
 BUILDING ORIENTATION TO MATCH PLANS. AND MISSING
 INFORMATION FOR WEST ELEVATION WINDOW. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 I) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R103.2 OF FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 NOTE: LABELS FOR DOORS AND WINDOWS U-FACTOR AND SHGC
 FACTORS SPECIFIED ON THE ENERGY CALCULATIONS WILL BE
 REQUIRED FOR INSPECTION WHEN NOT USING THE DEFAULT
 NUMBERS INCORPORATED IN THE PROGRAM.
  
 12- ENERGY CALCULATIONS FORM R402-2014 SUBMITTED FOR
 THE MAIN HOUSE ADDITION:
 NOTE: COORDINATE PLANS AND ENERGY CALCULATIONS TO AVOID
 CONFLICTS OR DELAYS.
 A) FLOOR TYPE ON ITEM #8 IS INCORRECT. SEE PLANS AND
 REVISE AS REQUIRED. SEC. R103.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 B) WALL TYPE AND INSULATION ON ITEM #9 IS INCORRECT.
 SEE PLANS AND REVISE AS REQUIRED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 C) R-VALUE SHOWN ON THE ITEM #10 DOESN'T MATCH R-VALUE
 SHOWN ON PLANS. NOTE: IF USING THIS PRESCRIPTIVE FORM
 THE R-VALUE REQUIRED IS R-30. ARCHITECTURAL PLANS WILL
 NEED TO BE REVISED. SEC. R103.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
  
 13- ENGINEER OF RECORD DRAWING S-1 SPECIFIES MIN. 2500
 PSF SOIL BEARING CAPACITY REQUIRED.. SOIL TEST REPORT
 BY ARDAMAN & ASSOCIATES, INC. DISCUSSIONS AND
 RECOMMENDATIONS ON PAGE 3 SPECIFIES THAT FOUNDATIONS
 CAN BE PROPORTIONED FOR A MAXIMUM ALLOWABLE BEARING
 STRESS OF 2,000 PSF. THIS DISCREPANCY TO BE COORDINATED
 BY ENGINEER OF RECORD AND GEOTECHNICAL ENGINEER. REVISE
 AS REQUIRED TO MATCH. SEC. R301 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) HOME OFFICE INSWING ENTRY DOOR AS SHOWN ON PLANS.
  
 B) RECYCLED SINGLE HUNG WINDOW SHOWN ON PLANS FOR THE
 NEW BATHROOM.
  
 C) RECYCLED FIXED FRENCH DOORS SHOWN ON PLANS FOR THE
 NEW LAUNDRY AREA AND MUD ROOM AREA.
  
 D) MODIFIED BITUMEN FOR FLAT ROOFS. AND, CLEARLY
 IDENTIFY APPROVED ASSEMBLY AND PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 E) MODIFIED BITUMEN FOR GARAGE/HOME OFFICE TERRACE THAT
 IS DESIGNED TO RECEIVE TILE AS SPECIFIED ON PLANS. AND,
 CLEARLY IDENTIFY APPROVED ASSEMBLY AND PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 F) ALL SIMPSON OR USP STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR DESIGNER OF RECORD TO LIST THE FLORIDA
 PRODUCT APPROVAL NUMBER NEXT EACH SPECIFIED CONNECTOR.
  
 G) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 15- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 16- THERE ARE SEVERAL DOORS AND WINDOWS PRODUCT
 APPROVALS SUBMITTED. CLEARLY IDENTIFY PROPOSED LOCATION
 OF EACH DOOR AND WINDOW PRODUCT APPROVAL SUBMITTED. FOR
 EXAMPLE, LAUNDRY AREA, OFFICE, ETC. SEC. 107.2.1 CITY
 AMENDMENTS. CLARIFY WHERE IS FIXED WINDOW NOA
 14-0424.03 SUBMITTED GOING TO BE INSTALLED. PLANS DON'T
 SHOW ANY FIXED WINDOWS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMITT DETACHED OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-10-29 Cont ID  
Sent By ppetty Date 2015-10-29 Time 08:15 Rev Time 0.00
Received By ppetty Date 2015-10-29 Time 08:12 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-11-19 Cont ID  
Sent By fmittner Date 2015-11-19 Time 11:22 Rev Time 0.00
Received By fmittner Date 2015-11-19 Time 11:22 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-10-07 Cont ID  
Sent By fmittner Date 2015-10-07 Time 13:58 Rev Time 0.00
Received By fmittner Date 2015-10-07 Time 13:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-01-07 Cont ID  
Sent By jgomez Date 2016-01-07 Time 19:26 Rev Time 0.00
Received By jgomez Date 2015-12-22 Time 16:09 Sent To  
Notes
2015-12-29 11:34:43TO JG DESK
2015-12-22 16:09:56R31

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-10 Cont ID  
Sent By jgomez Date 2015-12-10 Time 17:56 Rev Time 0.00
Received By jgomez Date 2015-11-19 Time 11:08 Sent To  
Notes
2015-11-19 13:27:16R28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-29 Cont ID  
Sent By ppetty Date 2015-10-29 Time 08:16 Rev Time 0.00
Received By ppetty Date 2015-09-04 Time 09:10 Sent To  
Notes
2015-09-17 08:18:04R33
2015-09-08 09:10:38TRAVELLING WITH 15090192

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-12-09 Cont ID  
Sent By jgomez Date 2015-12-09 Time 11:02 Rev Time 0.00
Received By jgomez Date 2015-12-09 Time 11:02 Sent To  
Notes
2015-12-09 11:02:291- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-10-26 Cont ID  
Sent By jgomez Date 2015-10-26 Time 12:17 Rev Time 0.00
Received By jgomez Date 2015-10-26 Time 12:17 Sent To  
Notes
2015-10-26 12:20:001- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-01-07 Cont ID  
Sent By jgomez Date 2016-01-07 Time 19:37 Rev Time 0.00
Received By jgomez Date 2016-01-07 Time 19:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-12-10 Cont ID  
Sent By jgomez Date 2015-12-10 Time 16:25 Rev Time 0.00
Received By jgomez Date 2015-12-10 Time 17:47 Sent To  
Notes
2015-12-10 17:56:16RESIDENTIAL (R3) ADDITION, SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- SEE BUILDING REVIEW COMMENTS FOR REQUIRED REVISIONS
 TO THE ENERGY CALCULATIONS, THEN REVISE EQUIPMENT
 SIZING CALCULATIONS AS REQUIRED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMITT DETACHED OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-10-27 Cont ID  
Sent By jgomez Date 2015-10-27 Time 12:11 Rev Time 0.00
Received By ccole Date 2015-10-27 Time 17:02 Sent To  
Notes
2015-10-27 17:37:401ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090189
 10/29/15
  
 1) REFER TO SECTION R403.6.1 F BC-14 ENERGY
 CONSERVATION AND PROVIDE COOLING AND HEATING
 CALCULATIONS FOR THE NEW MITSUBISHI AC SYSTEM IN THE
 GARAGE. THE SUBMITTED CALCULATIONS ARE FOR THE 2ND
 FLOOR HOME OFFICE ONLY. THE NOTE ON THE PLAN " FOR
 DEHUMIDIFICATION PURPOSES ONLY" IS NOT APPLICABLE
 BECAUSE THE UNIT IS DESIGNED TO PROVIDE COOLING. FOR
 DEMHUMIDIFICATIONS PURPOSES ONLY, PLEASE PROVIDE A UNIT
 DESIGNED SPECIFICALLY FOR DEHUMIDIFCATION PURPOSES
 ONLY- A DEHUMIDIFIER. PLEASE NOTE IF CONDITIONING IS TO
 BE PROVIDED, THEN HEAT IS REQUIRED IN ACCORDANCE WITH
 SECTION R303.9 FBC-14 RESIDENTIAL.
 2) REFER TO SECTION R101.4.3 FBC-14 ENERGY CONSERVATION
 AND PROVIDE ENERGY CALCULATIONS FOR THE CONDITIONED
 GARAGE ADDITION. THE SUBMITTED CALCULATION IS FOR THE
 2ND FLOOR HOME OFFICE ONLY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-11-23 Cont ID  
Sent By tklarge Date 2015-11-23 Time 05:41 Rev Time 0.00
Received By tklarge Date 2015-11-23 Time 05:06 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-09-29 Cont ID  
Sent By tklarge Date 2015-09-29 Time 15:13 Rev Time 0.00
Received By tklarge Date 2015-09-29 Time 15:03 Sent To  
Notes
2015-09-29 15:10:521) SHOW THE LOCATION OF THE WATER HEATER ON THE FLOOR
 PLAN OF THE GARAGE. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE CAPACITY AND EF RATING OF THE WATER HEATER
 ON BOTH COPIES OF THE ENERGY CALCULATIONS FOR THE
 GARAGE.COMPLY WITH TABLE C404.2 OF THE 2014 FBC-ENERGY.
 3) SIZE THE SCUPPERS AND DOWNSPOUTS FOR THE
 HOME/OFFICE. COMPLY WITH 2014 FBC- RESIDENTIAL SEC.R
 903.4.
 4) PROVISIONS SHALL BE MADE FOR OVERFLOW
 DRAINS/SCUPPERS PER THE 2014 FBC-RESIDENTIAL SEC.
 R903.4.1 & FBC-PLUMBING TABLE 1106.7.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2016-01-07 Cont ID  
Sent By jgomez Date 2016-01-07 Time 19:34 Rev Time 0.00
Received By jgomez Date 2016-01-07 Time 19:34 Sent To  
Notes
2016-01-07 19:34:35APPROVED WITH PROVISO:
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) MODIFIED BITUMEN FOR GARAGE/HOME OFFICE TERRACE THAT
 IS DESIGNED TO RECEIVE STONE AS SPECIFIED ON PLANS.
 AND, CLEARLY IDENTIFY APPROVED ASSEMBLY AND PROVIDE
 SIGNED AND SEALED RAS 117 CALCULATIONS IF REQUIRED.
 INFORMATION SUBMITTED IS NOT A PRODUCT APPROVAL.
  
 2- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS.
  
 NOTE: FLAT ROOF FLORIDA PRODUCT APPROVAL FL16709 IS OK.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2015-12-09 Cont ID  
Sent By jgomez Date 2015-12-09 Time 16:26 Rev Time 0.00
Received By jgomez Date 2015-12-09 Time 16:26 Sent To  
Notes
2015-12-09 16:27:251-- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) MODIFIED BITUMEN FOR FLAT ROOFS. AND, CLEARLY
 IDENTIFY APPROVED ASSEMBLY AND PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE: NO PRODUCT APPROVAL WAS SUBMITTED. NOTE: RAS
 117 CALCULATIONS FROM QEA NEED CLARIFICATION. ENGINEER
 TO CLARIFY WHY ZONE #2 AND ZONE #3 ARE THE SAME ON THIS
 PROJECT.
  
 B) MODIFIED BITUMEN FOR GARAGE/HOME OFFICE TERRACE THAT
 IS DESIGNED TO RECEIVE STONE AS SPECIFIED ON PLANS.
 AND, CLEARLY IDENTIFY APPROVED ASSEMBLY AND PROVIDE
 SIGNED AND SEALED RAS 117 CALCULATIONS IF SELECTED
 ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY
 SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE: NO PRODUCT APPROVAL WAS SUBMITTED. NOTE: RAS
 117 CALCULATIONS FROM QEA NEED CLARIFICATION. ENGINEER
 TO CLARIFY WHY ZONE #2 AND ZONE #3 ARE THE SAME ON THIS
 PROJECT.
  
 4- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-10-27 Cont ID  
Sent By jgomez Date 2015-10-27 Time 12:09 Rev Time 0.00
Received By jgomez Date 2015-10-27 Time 12:09 Sent To  
Notes
2015-10-27 12:10:471- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) MODIFIED BITUMEN FOR FLAT ROOFS. AND, CLEARLY
 IDENTIFY APPROVED ASSEMBLY AND PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) MODIFIED BITUMEN FOR GARAGE/HOME OFFICE TERRACE THAT
 IS DESIGNED TO RECEIVE TILE AS SPECIFIED ON PLANS. AND,
 CLEARLY IDENTIFY APPROVED ASSEMBLY AND PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-10-07 Cont ID  
Sent By fmittner Date 2015-10-07 Time 13:58 Rev Time 0.00
Received By fmittner Date 2015-10-07 Time 13:58 Sent To  
Notes
***NONE***