Plan Review Details - Permit 15090174
Plan Review Stops For Permit 15090174
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-20 Cont ID  
Sent By tklarge Date 2015-10-20 Time 06:25 Rev Time 0.00
Received By tklarge Date 2015-10-13 Time 13:28 Sent To  
Notes
2015-10-13 13:30:12RESUB ROUTED TO TKLARGE

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-10-20 Cont ID  
Sent By tklarge Date 2015-10-20 Time 06:25 Rev Time 0.00
Received By tklarge Date 2015-10-20 Time 05:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-09-24 Cont ID  
Sent By tklarge Date 2015-09-24 Time 05:38 Rev Time 0.00
Received By tklarge Date 2015-09-24 Time 02:50 Sent To  
Notes
2015-09-24 05:37:541)SUBMIT UPDATED CERTIFICATIONS FOR THE FOR THE
 COLLECTOR. THERE IS AN UPDATED CERTIFICATE LISTED ON
 THE FSEC WEBSITE.
 2) THE PUMP AND WATER STORAGE TANK COMPANIES ARE NOT
 LISTED ON THE FSEC WEBSITE. I COULD NOT FIND ANY INFO
 ON THE FSEC WEBSITE FOR THESE PRODUCTS. CLARIFY.
 3)THERE ARE COLLECTOR MOUNTING DETAILS FROM A COMPANY
 CALLED MORNING STAR SOLAR COLLECTORS. THIS IS NOT THE
 COMPLANY WHOSE NAME IS ON THE FSEC CERTIFICATION.
 CLARIFY.
 4) THE COLLECTOR MOUNTING DETAILS FROM MORNINGSTAR ARE
 BARELY LEGIBLE AND THERE ARE ALSO MOUNTING DETAILS THAT
 ARE ON THE SIGNED AND SEALED SHEET FROM ALLEN GEZELMAN.
 CLARIFY.
 5) THE PLANS ARE DIFFICULT TO READ. THE PLANS SHALL BE
 DRAWN AT A MINIMUM OF AN 1/8 INCH SCALE PER THE WPB
 AMEND. TO FBC SEC. 107.2.1.4.
 6) THE PIPING DIAGRAM FOR THE COLLECTOR AND WATER
 HEATER HAS NO PIPE SIZES ON ANY OF THE PIPE FOR THIS
 SYSTEM. SHOW THE PIPE SIZES ON BOTH SETS. WPB AMEND. TO
 FBC SEC. 107.2.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  