| 2015-10-23 19:01:19 | RESIDENTIAL (R3) DOCK AND BOAT LIFT BUILDING REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- DOCK PLANS BY MCR ENGINEER'S: |
| | A) THE EXPOSURE SPECIFIED ON THE DESIGN BASIS ON SHEET |
| | 3 OF 3 IS INCORRECT. THIS STRUCTURE IS LOCATED IN |
| | EXPOSURE "D" NOT "B". SEC. R301.2.1.4.3 |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS |
| | REQUIRED. |
| | |
| | B) THE WIND SPEED IS 170 MPH NOT 160 MPH. SEC. R301.2.1 |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS |
| | REQUIRED. |
| | |
| | C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | DECK INSTALLATION. SPECIFY MATERIAL AND FASTENING TO |
| | SHOW COMPLIANCE WITH SEC. R301.1 FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). REVISE AS REQUIRED. |
| | |
| | D) PROVIDE THE CERTIFICATE AUTHORIZATION NUMBER FOR THE |
| | ENGINEERING FIRM (MCR ENGINEER'S) AS REQUIRED BY F.A.C |
| | SEC. 61G15-23.002 AND CHAPTER 471 FLORIDA STATUTE. |
| | |
| | E) THERE IS A NOTE AT THE BOTTOM RIGHT HAND SIDE OF |
| | PAGE 3 OF 3 STATING " THESE DESIGNS AND DRAWINGS FOR |
| | MARLAND CONSTRUCTION COMPANY TO DEPICT WORK FOR DIEROLF |
| | RESIDENCE ONLY". CLARIFY AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 2- ENGINEER OF RECORD FOR THE NEW DOCK TO REVIEW AND |
| | APPROVE IN WRITING THE PROPOSED BOAT LIFT TO VERIFY |
| | COMPLIANCE WITH THE BOAT LIFT SUPPORT. SEC. 107.3.4.1 |
| | CITY AMENDMENTS. |
| | |
| | 2- BOAT LIFT PLANS BY B&B ENGINEERS: |
| | A) PROVIDE COMPLETE INFORMATION FOR SITE SPECIFIC |
| | INSTALLATION. SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | |
| | B) DRAWINGS SUBMITTED ARE TOO SMALL. LETTERING AND |
| | DETAILS ARE TOO SMALL. PROVIDE LARGER DRAWINGS AND |
| | LETTERING. SEC. 107.2.1.4 CITY AMENDMENTS. |
| | |
| | C) PROVIDE THE CERTIFICATE AUTHORIZATION NUMBER FOR THE |
| | ENGINEERING FIRM (B&B ENGINEERS) AS REQUIRED BY F.A.C |
| | SEC. 61G15-23.002 AND CHAPTER 471 FLORIDA STATUTE. |
| | |