Plan Review Details - Permit 15090119
Plan Review Stops For Permit 15090119
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-02-03 Cont ID  
Sent By jgomez Date 2016-02-03 Time 09:40 Rev Time 0.00
Received By jgomez Date 2016-02-03 Time 07:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-01-21 Cont ID  
Sent By jgomez Date 2016-01-21 Time 18:30 Rev Time 0.00
Received By jgomez Date 2016-01-21 Time 18:30 Sent To  
Notes
2016-01-21 18:35:37RESIDENTIAL (R3) DOCK AND BOAT LIFT THIRD BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTE:
 1/21/16 TALKED TO LINDA FROM HURRICANE BOAT LIFTS. TOLD
 HER WE NEED THE INFORMATION BELOW TO FINISH PROCESSING
 THE PERMIT.
  
  
 1- BOAT LIFT PLANS BY B&B ENGINEERS:
 A) DRAWINGS SUBMITTED ARE TOO SMALL. LETTERING AND
 DETAILS ARE TOO SMALL FOR SCANNING AND PUBLIC RECORDS
 RETENTION. PROVIDE LARGER DRAWINGS AND LETTERING. SEC.
 107.2.1.4 CITY AMENDMENTS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 B) PROVIDE THE CERTIFICATE AUTHORIZATION NUMBER FOR THE
 ENGINEERING FIRM (B&B ENGINEERS) AS REQUIRED BY F.A.C
 SEC. 61G15-23.002 AND CHAPTER 471 FLORIDA STATUTE.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-01-19 Cont ID  
Sent By jgomez Date 2016-01-19 Time 10:10 Rev Time 0.00
Received By jgomez Date 2016-01-19 Time 10:09 Sent To  
Notes
2016-01-19 10:10:43RESIDENTIAL (R3) DOCK AND BOAT LIFT SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 1- PROVIDE 2 COPIES OF THE REVISED PLANS DESIGNED BY
 MCR ENGINEER'S. ONLY ONE REVISED COPY WAS RE-SUBMITTED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- MCR BOAT-LIFT REVIEW LETTER TO HAVE ENGINEER'S SEAL
 AS REQUIRED BY F.A.C. SEC. 61G15-23.002 AND CHAPTER 471
 F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. AND
 PROVIDE TWO COPIES. ONLY ONE COPY WAS SUBMITTED.
  
 3- BOAT LIFT PLANS BY B&B ENGINEERS:
 A) DRAWINGS SUBMITTED ARE TOO SMALL. LETTERING AND
 DETAILS ARE TOO SMALL FOR SCANNING AND PUBLIC RECORDS
 RETENTION. PROVIDE LARGER DRAWINGS AND LETTERING. SEC.
 107.2.1.4 CITY AMENDMENTS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 B) PROVIDE THE CERTIFICATE AUTHORIZATION NUMBER FOR THE
 ENGINEERING FIRM (B&B ENGINEERS) AS REQUIRED BY F.A.C
 SEC. 61G15-23.002 AND CHAPTER 471 FLORIDA STATUTE.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-23 Cont ID  
Sent By jgomez Date 2015-10-23 Time 17:30 Rev Time 0.00
Received By jgomez Date 2015-10-23 Time 17:30 Sent To E
Notes
2015-10-23 19:01:19RESIDENTIAL (R3) DOCK AND BOAT LIFT BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- DOCK PLANS BY MCR ENGINEER'S:
 A) THE EXPOSURE SPECIFIED ON THE DESIGN BASIS ON SHEET
 3 OF 3 IS INCORRECT. THIS STRUCTURE IS LOCATED IN
 EXPOSURE "D" NOT "B". SEC. R301.2.1.4.3
 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS
 REQUIRED.
  
 B) THE WIND SPEED IS 170 MPH NOT 160 MPH. SEC. R301.2.1
 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS
 REQUIRED.
  
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 DECK INSTALLATION. SPECIFY MATERIAL AND FASTENING TO
 SHOW COMPLIANCE WITH SEC. R301.1 FBC-RESIDENTIAL, 5TH
 EDITION (2014). REVISE AS REQUIRED.
  
 D) PROVIDE THE CERTIFICATE AUTHORIZATION NUMBER FOR THE
 ENGINEERING FIRM (MCR ENGINEER'S) AS REQUIRED BY F.A.C
 SEC. 61G15-23.002 AND CHAPTER 471 FLORIDA STATUTE.
  
 E) THERE IS A NOTE AT THE BOTTOM RIGHT HAND SIDE OF
 PAGE 3 OF 3 STATING " THESE DESIGNS AND DRAWINGS FOR
 MARLAND CONSTRUCTION COMPANY TO DEPICT WORK FOR DIEROLF
 RESIDENCE ONLY". CLARIFY AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 2- ENGINEER OF RECORD FOR THE NEW DOCK TO REVIEW AND
 APPROVE IN WRITING THE PROPOSED BOAT LIFT TO VERIFY
 COMPLIANCE WITH THE BOAT LIFT SUPPORT. SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 2- BOAT LIFT PLANS BY B&B ENGINEERS:
 A) PROVIDE COMPLETE INFORMATION FOR SITE SPECIFIC
 INSTALLATION. SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 B) DRAWINGS SUBMITTED ARE TOO SMALL. LETTERING AND
 DETAILS ARE TOO SMALL. PROVIDE LARGER DRAWINGS AND
 LETTERING. SEC. 107.2.1.4 CITY AMENDMENTS.
  
 C) PROVIDE THE CERTIFICATE AUTHORIZATION NUMBER FOR THE
 ENGINEERING FIRM (B&B ENGINEERS) AS REQUIRED BY F.A.C
 SEC. 61G15-23.002 AND CHAPTER 471 FLORIDA STATUTE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-10-26 Cont ID  
Sent By jgomez Date 2015-10-26 Time 10:13 Rev Time 0.00
Received By skennedy Date 2015-10-26 Time 10:10 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2015-09-29 Cont ID  
Sent By cranford Date 2015-09-29 Time 08:40 Rev Time 0.00
Received By cranford Date 2015-09-29 Time 08:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-02-03 Cont ID  
Sent By jgomez Date 2016-02-03 Time 09:40 Rev Time 0.00
Received By jgomez Date 2016-02-01 Time 13:14 Sent To  
Notes
2016-02-02 13:14:30RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-01-21 Cont ID  
Sent By jgomez Date 2016-01-21 Time 18:30 Rev Time 0.00
Received By jgomez Date 2016-01-19 Time 13:39 Sent To  
Notes
2016-01-20 13:39:31RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-19 Cont ID  
Sent By jgomez Date 2016-01-19 Time 10:09 Rev Time 0.00
Received By jgomez Date 2016-01-04 Time 16:20 Sent To  
Notes
2016-01-04 16:21:05RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-26 Cont ID  
Sent By skennedy Date 2015-10-26 Time 10:13 Rev Time 0.00
Received By skennedy Date 2015-09-03 Time 09:21 Sent To  
Notes
2015-09-17 08:11:53R15

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-02-03 Cont ID  
Sent By gjohnson Date 2016-02-03 Time 14:48 Rev Time 0.00
Received By gjohnson Date 2016-02-03 Time 14:48 Sent To  
Notes
2016-02-03 13:27:42NEW DRAWINGS SUBMITTED. NEED RE-STAMP. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-09-09 Cont ID  
Sent By gjohnson Date 2015-09-09 Time 17:31 Rev Time 0.00
Received By gjohnson Date 2015-09-09 Time 17:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-02-03 Cont ID  
Sent By ajones Date 2016-02-03 Time 09:48 Rev Time 0.00
Received By ajones Date 2016-02-03 Time 09:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-09-30 Cont ID  
Sent By sgraham Date 2015-09-30 Time 10:05 Rev Time 0.00
Received By sgraham Date 2015-09-30 Time 10:05 Sent To  
Notes
***NONE***