| 2015-09-10 16:58:37 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15090089 |
| | ADD: 833 SUNSET RD. |
| | CONT: THERMA SEAL ROOF SYSTEMS, LLC |
| | TEL: (561)223-2096 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W |
| | * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: THURS. SEPT. 10/2015 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST THE SUBMITTED FLORIDA PRODUCT APPROVAL |
| | FL 2533-R12 CIRCLED SYSTEM W-62 FOR IDENTIFICATION OF |
| | SYSTEM TO BE INSTALLED. SYSTEM LIMITATION OF -52.5 IN |
| | ROOF ZONE 1. THIS APPROVAL ALLOWS FOR ENHANCED |
| | FASTENING IN ZONES 2 & 3, RAS 117 CALCULATION BY DESIGN |
| | PROFESSIONAL. |
| | |
| | 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| | CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| | DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| | FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND |
| | RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED. |
| | PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE |
| | COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE |
| | SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR |
| | ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH |
| | THE CONSTRUCTION DOCUMENTS. |
| | |
| | 2A) COMPLIED. 3M ROOF TILE ADHESIVE FL 6332-R5 PAGE 3 |
| | OF 9 TABLE 1 TILE TYPE, PROFILE, ADHESIVE PATTY |
| | PLACEMENT AND ALLOWABLE OVERTURNING MOMENT NOT |
| | IDENTIFIED. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED TO DETERMINE CODE COMPLIANCE. |
| | |
| | 2B) COMPLIED. 3M ROOF TILE ADHESIVE FL 6332-R5 PAGE 3 |
| | OF 9 TABLE 2 NOT FILED OUT IDENTIFYING TILE, SUBSTRATE, |
| | ATTACHMENT METHOD NOR ALLOWABLE DESIGN PRESSURES . |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED TO |
| | DETERMINE CODE COMPLIANCE. |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |