| Plan Review Stops For Permit 15090079 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2015-09-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-09-23 |
Time |
16:55 |
Rev Time |
|
| Received By |
jwitmer |
Date |
2015-09-23 |
Time |
16:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2015-11-09 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-11-09 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-11-09 |
Time |
15:52 |
Sent To |
I |
|
| Notes |
| 2015-11-09 16:57:09 | ALMOST ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN | | | SATISFACTORILY ADDRESSED. THOSE THAT HAVE NOT HAVE BEEN | | | MENTIONED TO THE DESIGN PROFESSIONAL TO AVOID SURPRISES | | | IN THE FIELD. THEY ARE: | | | INCORRECT CODE MENTIONED ON THE PLANS. THIS WORK SHALL | | | COMPLY WITH THE 2011 EDITION OF THE NEC. | | | MANDATORY SWITCHING REQUIREMENTS OF THE FBC-E SHALL BE | | | COMPLIED WITH | | | RECESSED LIGHTING SHALL BE SEALED TO LIMIT THE TRANSFER | | | OF AIR BETWEEN CONDITIONED AND NON CONDITIONED SPACE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2015-11-05 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-11-05 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-11-05 |
Time |
12:54 |
Sent To |
M |
|
| Notes |
| 2015-11-05 14:01:06 | APPLICANT ERRONEOUSLY SUBMITTED SHEETS FOR JOB PERMIT | | | 15081103 | | | . | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2015-11-03 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-11-03 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-11-03 |
Time |
13:48 |
Sent To |
I |
|
| Notes |
| 2015-11-03 15:10:55 | THOUGH THESE DRAWINGS WERE ONCE BEFORE REVIEWED. THE | | | FAILURE TO PROVIDE A NARRATIVE PROMPTED ME TO CONDUCT A | | | COMPLETE REVIEW OF THE PLANS FOR A SECOND TIME. | | | THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE | | | 2011 EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE); | | | THE 5TH EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS | | | APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED. | | | | | | 1. THE CODE ANALYSIS BOX IS REFERENCING STANDARDS FROM | | | THE 2010 FBC, NO LONGER IN EFFECT. THE APPLICABLE CODE | | | TO WHICH YOU SHALL CONFORM IS AS MENTIONED ABOVE. | | | 2. I NOTICE THAT THE FIXTURE SCHEDULE INDICATES THE USE | | | OF RECESSED LUMINARIES WITHOUT MENTIONING THE | | | REQUIREMENTS OF FBC-ENERGY CONSERVATION SECTION | | | 402.4.8, WHICH REQUIRES THAT ALL RECESSED LIGHTING BE | | | IC RATED AND SEALED TO PREVENT AIR LEAKAGE FROM THE | | | CONDITIONED AIR SPACE INTO THE NON-CONDITIONED AIR | | | SPACE. | | | 3. YOU SHALL SUBMIT LIGHT DENSITY ALLOWANCE | | | CALCULATIONS AS INDICATED IN FBC-E SECTIONS 405.5. | | | 4. NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN | | | OUTLET AT EVERY PEDESTRIAN ENTRY, FOR EVERY COMMERCIAL | | | OCCUPANCY. | | | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE | | | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE | | | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE | | | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. | | | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-10-01 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-10-01 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-10-01 |
Time |
10:37 |
Sent To |
I |
|
| Notes |
| 2015-10-01 12:32:26 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE | | | ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH | | | REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE | | | REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED | | | SHALL BE RESUBMITTED FOR ANOTHER REVIEW. | | | | | | 1. GENERAL LIGHTING NOTES #6 QUOTED A SECTION OF THE | | | FBC THAT HAS NO BEARING TO THIS JOB. | | | 2. GENERAL LIGHTING NOTES #7 QUOTED AN INCORRECT CODE. | | | THIS JOB IS GOVERNED BY THE 2011 EDITION OF THE NEC. | | | 3. ALL LIGHTING SHALL COMPLY WITH 5TH EDITION | | | FBC-ENERGY CONSERVATION 2014 SECTION C405. | | | A) YOU SHALL PROVIDE A LIGHT DENSITY ALLOWANCE CHART | | | SHOWING LIGHTING COMPLIANCE. | | | B) YOU SHALL PROVIDE A LIGHTING DIAGRAM | | | C) YOUR FEEDERS SHALL BE DESIGNED FOR A MAXIMUM 2% | | | VOLTAGE DROP & BRANCH CIRCUITS FOR NO MORE THAN 3% VD. | | | 4. EXIT LIGHTS AS REQUIRED BY FBC SECTION 1011 SHALL BE | | | INDICATED ON DRAWINGS. | | | 5. GENERAL ELECTRICAL NOTES #6 AGAIN QUOTED THE 2008 | | | NEC AND NOT THE 2011. | | | 6. YOU SHALL PROVIDE LOAD CALCS IN ACCORDANCE WITH NEC | | | 220.16. | | | 7. YOU SHALL SUBMIT A SITE SPECIFIC ELECTRICAL RISER | | | DIAGRAM INDICATING THE CONDUCTOR SIZING FOR VOLTAGE | | | DROP ALLOWANCES AND THE LOCATION OF ALL PANELS | | | ASSOCIATED WITH THE SITE. | | | 8. A CIRCUIT DIRECTORY AS REQUIRED BY NEC 408.4. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2015-09-08 |
|
|
Cont ID |
|
| Sent By |
Stallwor |
Date |
2015-09-08 |
Time |
|
Rev Time |
|
| Received By |
fstal |
Date |
2015-09-08 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2015-11-09 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-11-09 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-11-09 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2015-11-09 14:54:23 | RE-SUBMITTAL FORM SUBMITTED WITH CORRECT DRAWINGS. SENT | | | TO MIKE ALBARRAN FOR ELECTRICAL REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-11-05 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-11-05 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-11-05 |
Time |
11:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-11-03 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-11-03 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-10-27 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2015-11-03 15:12:07 | 11/3/15 FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED | | | VIA PHONE CALL. SENT TO LARGE DENIED BIN TBD> MA | | 2015-10-28 09:44:54 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-10-01 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-10-01 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-09-02 |
Time |
16:06 |
Sent To |
|
|
| Notes |
| 2015-10-01 12:53:41 | 10/1/15 FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED | | | VIA EMAIL. SENT TO LARGE DENIED BIN "TBD". MA | | 2015-09-02 16:06:21 | B30 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2015-10-28 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-10-28 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-10-28 |
Time |
16:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-09-11 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-09-11 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-09-11 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2015-09-11 09:56:23 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15090079 | | | 9/11/15 | | | | | | 1) SHEET M/FP01.01: SHOW THE DIMENSIONS OF THE NEW VAV | | | 1-15 BRANCH DUCTS AT THE POINT OF CONNECTION, AND IN | | | AND OUT OF THE VAV BOX. | | | 2) SUBMIT A CUT SHEET FOR THE VAV BOX. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|