Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-09-23 Cont ID  
Sent By jwitmer Date 2015-09-23 Time 17:15 Rev Time 0.00
Received By jwitmer Date 2015-09-23 Time 16:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-10 Cont ID  
Sent By jwitmer Date 2015-09-10 Time 15:15 Rev Time  
Received By jwitmer Date 2015-09-10 Time   Sent To  
Notes
2015-09-10 15:15:31BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090069
 ADD: 3716 S DIXIE HWY
 CONT: C & S EXPERTISE INC.
 TEL: (561)436-5355
 E-MAIL: ??????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. SEPT. 10/2014
 ACTION: DENIED
  
 1) THE PLANS SUBMITTED HAVE NO DESIGNER. THE PERSON
 RESPONSIBLE (QUALIFIER) FOR THE CONTRACTOR IS TO PRINT
 THEIR NAME, SIGN THEIR NAME AND PRINT THEIR LICENSE
 NUMBER ON THE PLANS.
  
 2) THE NOTE FOR THE FLOOR/ CEILING TO HAVE DRYWALL ON
 EQUIPMENT PLATFORMS CATES TO USE OF 5/8 INCH GYPSUM
 BOARD ON EITHER SIDE. I BELIEVE THIS IS A MIS-STATEMENT
 5/8 INCH GYPSUM WILL NOT MEET THE REQUIRED FLOOR LOADS
 THAT WILL BE APPLIED. 2014 FBC-B TABLE 1607.1( 28)
 ACCESSIBLE CEILINGS.
  
 3) PLEASE NOTE ON THEPLANS, THE HEIGHT OF THE GRAB BARS
 SHOW TO THE CENTER OF THE BAR. IN THE 2014 FL
 ACCESSIBILITY CODE 609.4 POSITION OF GRAB BAR, THE
 HEIGHT IS MEASURED TO THE TOP OF THE GRIPPING SURFACE,
 33-36 INCHES, NOT CENTERLINE.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2015-09-15 Cont ID  
Sent By jwitmer Date 2015-09-15 Time 11:56 Rev Time 0.00
Received By skennedy Date 2015-09-15 Time 11:56 Sent To  
Notes
2015-09-15 11:57:20ELECTRIC WAS REVIEWED SEPARATELY UNDER PERMIT #15080450
2015-09-10 15:09:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090069
 ADD: 3716 S DIXIE HWY
 CONT: C & S EXPERTISE INC.
 TEL: (561)436-5355
 E-MAIL: ??????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. SEPT. 10/2014
 ACTION: DENIED
  
 1) THE PLANS SUBMITTED HAVE NO DESIGNER. THE PERSON
 RESPONSIBLE (QUALIFIER) FOR THE CONTRACTOR IS TO PRINT
 THEIR NAME, SIGN THEIR NAME AND PRINT THEIR LICENSE
 NUMBER ON THE PLANS.
  
 2) THE NOTE FOR THE FLOOR/ CEILING TO HAVE DRYWALL ON
 EQUIPMENT PLATFORMS CATES TO USE OF 5/8 INCH GYPSUM
 BOARD ON EITHER SIDE. I BELIEVE THIS IS A MIS-STATEMENT
 5/8 INCH GYPSUM WILL NOT MEET THE REQUIRED FLOOR LOADS
 THAT WILL BE APPLIED. 2014 FBC-B TABLE 1607.1( 28)
 ACCESSIBLE CEILINGS.
  
 3) PLEASE NOTE ON THEPLANS, THE HEIGHT OF THE GRAB BARS
 SHOW TO THE CENTER OF THE BAR. IN THE 2014 FL
 ACCESSIBILITY CODE 609.4 POSITION OF GRAB BAR, THE
 HEIGHT IS MEASURED TO THE TOP OF THE GRIPPING SURFACE,
 33-36 INCHES, NOT CENTERLINE.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-23 Cont ID  
Sent By jwitmer Date 2015-09-23 Time 17:15 Rev Time 0.00
Received By jwitmer Date 2015-09-22 Time 16:12 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-15 Cont ID  
Sent By skennedy Date 2015-09-15 Time 11:56 Rev Time 0.00
Received By skennedy Date 2015-09-02 Time 15:42 Sent To  
Notes
2015-09-02 15:42:29B24

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-09-23 Cont ID  
Sent By jwitmer Date 2015-09-23 Time 17:12 Rev Time 0.00
Received By gjohnson Date 2015-09-23 Time 13:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-09-09 Cont ID  
Sent By gjohnson Date 2015-09-09 Time 13:49 Rev Time 0.00
Received By gjohnson Date 2015-09-09 Time 13:49 Sent To  
Notes
2015-09-09 14:10:301ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1.THE WIDTH OF THE BATHROOM DOES NOT ALLOW FOR 60IN.
 CLEARANCE AT TOILET.
 PER FBC ACC. 2014 SEC.604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL. HTTP://FLORIDABUILDIN
 G2.ICCSAFE.ORG/APP/BOOK/CONTENT/2014_FLORIDA/ACCESSIBIL
 ITY%20CODE/IMAGES/FAC_RK_BITMAP%2079.JPG
 2. FBC ACC. SEC 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE.IF MEASURED 36IN TO CENTER THE BAR
 WILL BE TO HIGH.
 3.SHALL SHOW HEIGHT OF TOILET.
 FBC ACC. SEC 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
 4.PLANS MUST BE SIGNED AND SEALED.
 PER. FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN