Plan Review Details - Permit 15090051
Plan Review Stops For Permit 15090051
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-10-31 Cont ID  
Sent By skennedy Date 2015-10-31 Time 10:16 Rev Time 0.00
Received By skennedy Date 2015-10-31 Time 10:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-20 Cont ID  
Sent By skennedy Date 2015-10-20 Time 14:34 Rev Time 0.00
Received By skennedy Date 2015-10-20 Time 14:34 Sent To  
Notes
2015-10-20 14:41:591ST REVIEW: FBC 2014 5TH ED.
  
 UPDATE THE PLAN TO INDICATE COMPLIANCE WITH THE
 FOLLOWING:
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE IMPACT RESISTANT SKYLIGHT
 SUBMITTAL.
  
 FBC-R310.1 EMERGENCY ESCAPE AND RESCUE REQUIRED IN
 BEDROOM 2 AS FOLLOWS: WHERE EMERGENCY ESCAPE AND RESCUE
 OPENINGS ARE PROVIDED THEY SHALL HAVE A SILL HEIGHT OF
 NOT MORE THAN 44 INCHES (1118 MM) MEASURED FROM THE
 FINISHED FLOOR TO THE BOTTOM OF THE CLEAR OPENING.
 R310.1.1 MINIMUM OPENING AREA GRADE FLOOR OPENINGS
 SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5 SQUARE FEET
 R310.1.2 MINIMUM OPENING HEIGHT.
 THE MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24 INCHES
 R310.1.3 MINIMUM OPENING WIDTH.
 THE MINIMUM NET CLEAR OPENING WIDTH SHALL BE 20 INCHES
  
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-10-31 Cont ID  
Sent By skennedy Date 2015-10-31 Time 10:16 Rev Time 0.00
Received By skennedy Date 2015-10-31 Time 10:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-10-20 Cont ID  
Sent By skennedy Date 2015-10-20 Time 14:31 Rev Time 0.00
Received By skennedy Date 2015-10-20 Time 14:31 Sent To  
Notes
2015-10-20 14:34:141ST REVIEW: FBC 2014 5TH ED.
  
 MODIFY THE ELECTRICAL PLAN TO DEMOSTRATE CARBON
 MONOXIDE ALARMS TO BE PROVIDED WITHIN 10 FEET OF EACH
 SLEEPING ROOM PER FBC-R 315.1.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-31 Cont ID  
Sent By skennedy Date 2015-10-31 Time 10:17 Rev Time 0.00
Received By skennedy Date 2015-10-27 Time 09:45 Sent To  
Notes
2015-10-28 09:45:59GJOHNSON'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-20 Cont ID  
Sent By skennedy Date 2015-10-20 Time 14:42 Rev Time 0.00
Received By skennedy Date 2015-09-02 Time 16:32 Sent To  
Notes
2015-09-17 08:14:48R21

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-10-31 Cont ID  
Sent By skennedy Date 2015-10-31 Time 10:16 Rev Time 0.00
Received By skennedy Date 2015-10-31 Time 10:16 Sent To  
Notes
2015-10-31 10:16:38PROVIDE REVISION

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-10-20 Cont ID  
Sent By skennedy Date 2015-10-20 Time 14:20 Rev Time 0.00
Received By skennedy Date 2015-10-20 Time 14:20 Sent To  
Notes
2015-10-20 14:31:171ST REVIEW: FBC 2014 5TH ED.
  
 PROVIDE A DUCT PLAN FOR THE RELOCATION OF THE AHU OR
 ELECT TO SUBMIT ONE AS A REVISION.
  
 FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW
 SUPPLY DUCTS & BALANCED AIR METHODS PER FBC-R M16. SHOW
 OR NOTE THE CONDENSATION DISPOSAL METHOD AND AUXILIARY
 DRAIN PER FBC-RM1411.3.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-10-28 Cont ID  
Sent By gjohnson Date 2015-10-28 Time 14:45 Rev Time 0.00
Received By gjohnson Date 2015-10-28 Time 14:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-09-09 Cont ID  
Sent By gjohnson Date 2015-09-09 Time 16:26 Rev Time 0.00
Received By gjohnson Date 2015-09-09 Time 16:26 Sent To  
Notes
2015-09-09 17:08:431ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1.LAUNDRY SHALL TIE INTO BUILDING DRAIN DOWN STREAM OF
 BATHROOM GROUP.
 PER FBC RES. PLUMB. SEC. P3108.1
  
  
 2. IN PLUMBING NOTES P3 INDICATES EXISTING WASHING
 MACHINE BEING RELOCATED TO NEW LOCATION NEED TO SHOW
 NEW LOCATION OR INDICATE NO EXISTING .
 PER WPB AMEND. 107.2.1
  
 3. PROVIDE SPECS FOR TANKLESS WATER HEATER
 GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECTS THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE FBC,
 FUEL GAS, SEC.301.3.
  