| 2016-03-21 15:26:18 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 5TH EDITION RESIDENTIAL |
| | |
| | 1. FROM PREVIOUS LIST, PLANS ARE TO INCLUDE THE METHOD |
| | USED FOR DESIGN (ONE OF THE METHODS IN SECTION 301). IF |
| | ENGINEERING (ASCE7-10) IS USED AS THE METHOD OF DESIGN, |
| | PROVIDE CALCULATIONS. SEE FBC R 301.1.1 FOR |
| | PRESCRIPTIVE METHODS. |
| | |
| | NOT ADDRESSED. REVIEW WILL BE DONE AFTER THE |
| | INFORMATION HAS BEEN PROVIDED. AN ACCURATE REVIEW IS |
| | NOT POSSIBLE WITHOUT THIS INFORMATION. IT IS NOT CLEAR |
| | HOW THE STRUCTURAL ELEMENTS HAVE BEEN SELECTED ? SIZE |
| | OF MEMBERS, SPANS, AMOUNT OF STEEL, NUMBER OF |
| | FASTENERS, FASTENERS SPECIFIED, ETC. I AM UNABLE TO |
| | DETERMINE WHETHER OR NOT THIS DESIGN WILL RESIST WIND |
| | LOADS. MORE INFORMATION ? SUCH AS PRESCRIPTIVE DESIGN |
| | DETAILS, CALCULATIONS FOR STRUCTURAL ELEMENTS, ETC. IS |
| | REQUIRED. |
| | |
| | 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR |
| | COMPONENTS AND CLADDING. AS FLINTLASTIC SPEC SHEETS |
| | WERE SUBMITTED, IT APPEARS THAT A ROOF IS PROPOSED. |
| | PROVIDE THE PRODUCT APPROVAL FOR THE ROOF COVERING, AND |
| | ON THE PRODUCT APPROVAL, INDICATE WHICH OPTION IS |
| | PROPOSED. IF THE PRODUCT APPROVAL DOES NOT REQUIRE |
| | ENGINEERING FOR ENHANCED FASTENING, IT IS POSSIBLE THAT |
| | THIS MAY BE DONE FOR YOU (BUT YOU NEED TO PROVIDE THE |
| | ROOF COVERING PRODUCT APPROVAL). |
| | |
| | NOT ADDRESSED. PRODUCT APPROVAL ALSO REQUIRED FOR |
| | STRUCTURAL COMPONENTS. |
| | |
| | 3. PLANS ARE INCOMPLETE. A COMPLETE REVIEW CANNOT BE |
| | DONE AT THIS TIME. |
| | |
| | FOR INSTANCE, SEE FBC 802.1.5, TRUSSES SHALL BE |
| | CONNECTED TO WALL PLATES BY THE USE OF APPROVED |
| | CONNECTORS HAVING A RESISTANCE TO DESIGN UPLIFT, |
| | LATERAL AND SHEAR FORCES. THESE LOADS ARE NOT ON THE |
| | PLAN, SO IT IS NOT CLEAR HOW A CONNECTOR CAN BE |
| | SPECIFIED. SEE ALSO FBC 107.2.1.2. PLAN STATES THAT |
| | THIS INFORMATION WILL BE ON THE TRUSS ENGINEERING, BUT |
| | THAT WAS NOT PROVIDED. |
| | |
| | A LEDGER IS SHOWN, NO FASTENING SPECIFIED. |
| | |
| | A BLOCK WALL IS SHOWN, BUT NO STRUCTURAL INFORMATION |
| | SHOWN OTHER THAN THE FOUNDATION PLAN. WITHOUT |
| | CALCULATIONS, IT IS NOT POSSIBLE TO DETERMINE WHETHER |
| | OR NOT THE FOOTING SIZE IS ADEQUATE FOR THE WALL TO |
| | RESIST WIND LOADS. |
| | |
| | 4. FBC 107.2.1, ALL INFORMATION, |
| | DRAWINGS,SPECIFICATIONS AND ACCOMPANYING DATA SHALL |
| | BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE |
| | FOR THE DESIGN. (SEE ALSO SECTION 107.3.5): |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5). |
| | |