Plan Review Details - Permit 15081111
Plan Review Stops For Permit 15081111
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-10-01 Cont ID  
Sent By   Date 2015-10-01 Time 06:00 Rev Time 0.00
Received By   Date 2015-10-01 Time 05:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-09 Cont ID  
Sent By jwitmer Date 2015-09-09 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2015-09-09 Time 06:29 Sent To  
Notes
2015-09-09 07:31:57BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15081111
 ADD: 444 BUNKER RANCH RD.
 CONT: CURY BUILDING & DESIGN
 TEL: (561)718-1398
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT. 09/2015
 ACTION: DENIED
  
 1) SHEET S07 CODE REFERENCE SHEET. LIST THE 2014, 5TH
 EDITION OF THE FLORIDA BUILDING CODE. THE PLANS ARE
 SILENT TO WHAT DESIGN THE PLANS WERE DESIGN TO UNDER
 THE 2014 FBC-EXISTING BUILDING CODE, 301.1.
  
 2) SHEET S07 STUCTURAL NOTES UNDER THE HEADING OF
 MATERIALS THE STRENGTH OF CONCRETE IS DECLARED FOR
 SLABS, COLUMNS AND BEAMS, SHEET S02 THE COLUMN SCHEDULE
 UNIT C6 IS FILLED CELL MASONRY THE PLANS INDICATE THE
 USE OF 3000 PSI CONCRETE, IN FILED CELL MASONRY
 SHOULDN'T THE USE OF GROUT BE USED INSTEAD OF CONCRETE.
 ACI 530 1.16.1. & TABLE 1.16.1 GROUTING MINIMUM SPACES.
  
 3) SHEET S2 FOOTING SCHEDULE FOOTING F2-F6 INDICATES
 THE WIDTH & LENGTH OF THE FOOTING BUT NOT THE HEIGTH.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) SHEET S2 FOOTING SCHEDULE F4 DOES NOT PROVIDE AT
 WHAT CENTER TO CENTER IN INCHES WHAT THE STEEL MATS ARE
 TO BE INSTALLED. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-09-24 Cont ID  
Sent By albarran Date 2015-09-24 Time 16:35 Rev Time 0.00
Received By albarran Date 2015-09-24 Time 15:33 Sent To I
Notes
2015-09-24 16:11:43ELECTRICAL PROVISO TO PERMIT 15081111
 BEFORE POURING CONCRETE, COORDINATE WITH THE ELECTRICAL
 CONTRACTOR ON A LOCATION FOR THE FOUNDATION GROUND AS
 AN ELECTRICAL INSPECTION FOR THE FOUNDATION GROUNDING
 SHALL BE PASSED BEFORE BLDG. INSPECTION IS PASSED.
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2015-11-20 Cont ID  
Sent By mgonzale Date 2015-11-20 Time 11:31 Rev Time 0.00
Received By mgonzale Date 2015-11-20 Time 11:31 Sent To  
Notes
2015-11-20 11:31:58ENG HAS RECEIVED THE SEPARATE SUBMITTAL 11/2015

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2015-10-20 Cont ID  
Sent By Mgonzale Date 2015-10-20 Time   Rev Time 1.00
Received By mgonzale Date 2015-10-20 Time   Sent To I
Notes
2015-10-20 13:37:52A SEPARATE ENGINEERING SUBMITTAL IS REQUIRED.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-09-04 Cont ID  
Sent By cranford Date 2015-09-04 Time 09:47 Rev Time 0.00
Received By mgonzale Date 2015-09-04 Time 09:27 Sent To  
Notes
2015-09-04 09:47:43APPLICATION IS FOR INTERIOR WORK ONLY. SHELL OF
 BUILDING TO REMAIN.
  
 SEPARATE PERMIT REQUIRED FOR DUMPSTER ENCLOSURE.
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-10-07 Cont ID  
Sent By pleduc Date 2015-10-07 Time   Rev Time 0.00
Received By pleduc Date 2015-10-06 Time 16:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-08-31 Cont ID  
Sent By pleduc Date 2015-08-31 Time   Rev Time 0.00
Received By pleduc Date 2015-08-31 Time 12:09 Sent To  
Notes
2015-08-31 12:24:38THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS INSUFFICIENT DETAIL TO COMPLETE A PROPER OR
 COMPLETE PLAN REVIEW.
  
 2) PROVIDE DETAIL AS TO WHAT IS EXISTING AND WHAT IS
 PROPOSED.
  
 3) PROVIDE NOTE AND ENSURE ALL DRAWINGS AND WORK
 COMPLIES:
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 4) ADDITIONAL COMMENTS MAY APPLY BASED ON THE
 RESUBMITTAL.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-05 Cont ID  
Sent By cpuell Date 2015-11-05 Time 11:39 Rev Time 0.00
Received By cpuell Date 2015-09-28 Time 08:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-24 Cont ID  
Sent By albarran Date 2015-09-24 Time 16:36 Rev Time 0.00
Received By albarran Date 2015-08-28 Time 13:09 Sent To I
Notes
2015-09-24 16:45:369/24/15 ADDED AN ELECTRICAL PROVISO. CONTACTED RUNNER
 VIA EMAIL. SENT TO SMALL READY BIN "C". MA
2015-08-28 13:15:44C19

Review Stop P PLUMBING
Rev No 2 Status N Date 2015-10-04 Cont ID  
Sent By tklarge Date 2015-10-04 Time 07:05 Rev Time 0.00
Received By tklarge Date 2015-10-04 Time 06:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-09-01 Cont ID  
Sent By tklarge Date 2015-09-01 Time 05:36 Rev Time 0.00
Received By tklarge Date 2015-09-01 Time 05:22 Sent To  
Notes
2015-09-01 05:30:171) THE APPLICATION NOTES THIS IS FOR A FOUNDATION BUT
 THE PLANS SHOW MUCH MORE WORK THAN A FOUNDATION.
 INDICATE ON THE PLAN WHAT IS NEW AND WHAT IS EXISTING (
 GENERATOR,ELEVATOR, ETC.). WPB AMEND. TO FBC SEC.
 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-10-15 Cont ID  
Sent By dkittred Date 2015-10-15 Time 10:33 Rev Time 0.00
Received By dkittred Date 2015-10-15 Time 09:19 Sent To  
Notes
2015-10-15 10:33:5210/15/15 - INTERIOR WORK ONLY, SITE WORK WILL BE DONE
 BY SEPARATE PERMIT AND ADDRESS PREVIOUS COMMENTS. DK

Review Stop Z ZONING
Rev No 2 Status F Date 2015-09-30 Cont ID  
Sent By dkittred Date 2015-09-30 Time 15:48 Rev Time 0.00
Received By dkittred Date 2015-09-30 Time 15:11 Sent To  
Notes
2015-09-30 15:57:03PLANNING AND ZONING COMMENTS: ***FAILED***
  
 9/30/15
  
 1. NONE OF THE ZONING COMMENTS FROM 9/03/15 WERE
 ADDRESSED IN THE RESUBMITTAL. PLEASE REVIEW ALL
 PREVIOUS COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-09-03 Cont ID  
Sent By dkittred Date 2015-09-03 Time 09:43 Rev Time 0.00
Received By dkittred Date 2015-09-01 Time 10:22 Sent To  
Notes
2015-09-03 09:43:18PLANNING AND ZONING COMMENTS: ***FAILED***
  
 9/3/15
  
 1. SUBMIT A PROPERTY SURVEY WITH EACH SET OF PLANS.
  
 2. NEW 10? X 45? CONCRETE PAD ON THE EAST SIDE OF THE
 BUILDING NEEDS TO BE SHOWN DIMENSIONALLY ACCURATE ON
 THE SITE PLAN WITH SETBACK FROM PROPERTY LINE. CONCRETE
 PAD MUST BE A MINIMUM OF 2 FEET FROM THE PROPERTY LINE.
 PLEASE DIMENSION.
  
 3. LOCATION OF PROPOSED DUMPSTER IS ALSO BEING REVIEWED
 ON SEPARATE SITE WORK PERMIT. DUMPSTER LOCATION WITH
 ORIENTATION FOR PICK-UP OFF OF BUNKER ROAD IS NOT
 RECOMMENDED AND WILL REQUIRE ENGINEERING REVIEW. FINAL
 LOCATION OF THE PAD FOR THE DUMPSTER ENCLOSURE SHALL BE
 DIMENSIONED AND INCLUDE SETBACKS FROM THE PROPERTY
 LINE. A FOUNDATION PLANTING IS REQUIRED AROUND THE
 DUMPSTER ENCLOSURE AND CAN BE ADDRESSED THROUGH A
 SEPARATE LANDSCAPE PERMIT.
  
  
 GENERAL COMMENTS:
  
 4. REVISIONS TO PARKING LOT AND LANDSCAPING ARE TO BE
 REVIEWED UNDER SEPARATE PERMITS.
  
 5. SEPARATE PERMIT REQUIRE FOR GENERATOR. SCREENING OF
 GENERATOR WILL BE REQUIRED.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2015-08-31 11:16:058/31/15


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved