Plan Review Details - Permit 15081084
Plan Review Stops For Permit 15081084
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-02-23 Cont ID  
Sent By   Date 2016-02-23 Time 17:00 Rev Time 0.00
Received By   Date 2016-02-23 Time 13:05 Sent To  
Notes
2016-02-23 16:35:16BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15081084
 ADD: 1801 @ PARKER AVE.
 CONT: TBD
 TEL: ( 561)494-1075
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RDD REVIEW
 DATE: TUES. FEB.23 /2016
 ACTION: BUILDING PROVISO:
  
 NOTE: GENERATOR AND FUEL TANK ARE UNDER SEPERATE
 PERMIT!!!!!!
  
 1) PROVISO: DEFERRED SUBMITTAL TRUSS ENGINEEERING TO BE
 REVIEWED BY THE ENGINEER OF RECORD BEFORE SUBMITTAL TO
 THE BUILDING DEPARTMENT.
  
 2) PROVISO: DEFERRED SUBMITTAL FOR THE OUTRIGGER
 ANCHORING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-01-04 Cont ID  
Sent By jwitmer Date 2016-01-04 Time 09:54 Rev Time 0.00
Received By jwitmer Date 2016-01-04 Time 07:15 Sent To  
Notes
2016-01-04 09:54:09BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15081084
 ADD: 1801 @ PARKER AVE.
 CONT: TBD
 TEL: ( 561)494-1075
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. JAN. 04 /2016
 ACTION: DENIED
  
 NOTE: GENERATOR AND FUEL TANK ARE UNDER SEPERATE
 PERMIT!!!!!!
  
 1) COMPLIED. PLANS DESIGNED TO THE 2014 FBC.
  
 2) SEMI- COMPLIED. ALTHOUGH THE FLOOD ELEVATION
 CERTIFICATE IS A FEDERAL FORM AND STATES THAT SURVEYOR,
 ENGINEERS AND OR ARCHITECTS AUTHORIZED BY LAW TO
 CERTIFY ELEVATION INFORMATION, FLORIDA STATE STATUTES
 472.005(3),(4A-4B) ONLY FLORIDA LICENSED SURVEYOR CAN
 FILE OUT THIS FORM.
 THE PERMIT APPLICATION ADDRESS INDICATES THIS STRUCTURE
 IS BUILT IN AN A9 FLOOD ZONE THE BASE ELEVATION 13 FEET
 AND THE CITY REQUIRES AN ADDTIONAL 6 INCH FREEBOARD OR
 MINIMUM OF 13 FT. 6 INCHES. FBC BUILDING 1612 AND CITY
 OF WPB CODE OF ORDINANCES SECTION 94-546.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31/2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 3) 2ND REQUEST. NOTE THE SUBMITTED SOILS REPORT IS A
 COPY OF THE ORIGINAL SIGNATURE NOT THE ORIGINAL. THE
 SECOND ISSUE WITH THE SOILS REPORT THE DOCUMENT IS NOT
 SEALED. THE COVER SHEET DOES NOT LIST HOW MANY PAGES
 ARE UNDER THE SOILS ENGINEER SEAL, NOR IS THERE A
 SEALED INDEX SHEET INDICATING HOW MANY PAGES ARE
 COVERED UNDER THE ENGINEERS SUPPOSED SEAL. THERE ARE
 TWO ENGINEERS NAMES ON THE REPORT, SIGNED, PRINTED AND
 LICENSE NUMBERS, THERE IS NO DOCUMENTATION AS TO WHAT
 PART OF THE SOILS REPORT EACH IS RESPONSIBLE FOR.
  
 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION.
 ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME AND
 BUSINESS ADDRESS, ON ENGINEERING DOCUMENTS. ENGINEERING
 DOCUMENTS WHICH ARE ISSUED FOR PRELIMINARY OR
 CONCEPTUAL USE, SHALL CLEARLY NOTE THE INTENDED PURPOSE
 OF SUCH DOCUMENTS. WHEN ELEMENTS OF THE PROJECT ARE
 SHOWN ON AN ENGINEERING DOCUMENT ONLY FOR INFORMATION
 OR CLARIFICATION AND THE ENGINEER DOES NOT INTEND TO
 ACCEPT RESPONSIBILITY FOR THE ELEMENTS, THE ENGINEER
 SHALL CLEARLY NOTE ON THE DOCUMENTS THE EXTENT OF HIS
 RESPONSIBILITY.
  
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE
 COVERED UNDER THE COVER SHEET OR INDEX SHEET.
  
 SHEET S1 UNDER THE HEADING OF SLAB ON GRADE SOILS
 REPORTS ARE REQUIRED. 2014 FBC-B 1803.5.2 QUESTIONABLE
 SOILS, SOILS GEOTECHNICAL REPORT REQUIRED. SHEET S3
 INDICATES THE INSTALATION OF 20 FOOT STEEL SHEET PILE.
  
 4-6) COMPLIED.
  
 7) 2ND REQUEST. PLEASE PROVIDE COMPLIANCE WITH 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. SWING AND OVERHEAD TYPE
 (C) WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES-
  
 FL 7473-R6 EAGLE ROOFING TILE: ON SHEETS 2 & 3 OF THE
 APPROVAL, THE TILE TYPE WAS NOT IDENTIFIED.
  
 SHEET 3 OF 4, LIMITATION # 5.4 NOT COMPLIED. NO PRODUCT
 APPROVAL WAS SUBMITTED. UNDERLAYMENT SHALL BE THAT
 APPROVED BY EAGLE ROOFING PRODUCTS, LLC, WHICH HOLDS
 FLORIDA PRODUCT APPROVAL FOR USE WITH TILE ROOFING
 SYSTEMS. THE UNDERLAYMENT PRODUCT APPROVAL SHALL
 SPECIFY ALLOWABLE METHOD(S) OF TILE INSTALLATION
 (MECHANICAL ATTACHMENT, MORTAR-SET AND/OR ADHESIVE-SET)
 FOR USE WITH THE SPECIFIC UNDERLAYMENT. FOR MORTAR-SET
 OR ADHESIVE-SET TILE ROOFING APPLICATIONS, THE
 UNDERLAYMENT PRODUCT APPROVAL SHALL SPECIFY ATTACHMENT
 METHODS FOR THE UNDERLAYMENT SYSTEM TO RESIST WIND
 UPLIFT DESIGN LOADS IN ACCORDANCE WITH TABLE 1A OF
 FRSA/TRI APRIL 2012 (04-12).
  
 FRSA/ TRI TABLE IA THE WRONG EXPOSURE AND WIND SPEED IS
 INDENTIFIED AND NO MEAN ROOF HEIGHT GIVEN. EXPOSURE C/
 180 MPH( BUILD CAT. IV) MEAN ROOF HEIGHT OF 15 FEET.
  
 8) 2ND REQUEST. RESPONSE INDICATES THAT CLOSE
 CONSTRUCTION TO RESPOND/ SUPPLY INFORMATION. 2010 FBC
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) 2ND REQUEST. SHEET S-3, S-4,S6, S7 & S9 ALL SHOW
 DETAILS OF THE NEW HIPPED TRUSS ROOF SYSTEM ON TOP OF A
 CONCRETE SLABBED ROOF SYSTEM. NOTE THE PLANS INDICATE A
 (2) POINT ANCHOR LOCATION FOR THE TRUSSES. THE AREA OF
 CONCERN IS THE 4 FOOT AND 6 FOOT TRUSS TAILS WITH NO
 ANCHOR SYSTEM FOR UPLIFT. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. ON THE 1ST REVIEW THE 2 POINTS
 OF ANCHORING WERE SHOWN, THE ISSUE IS WITHOUT THE
 ENGINEERED TRUSS SHEETS THE UPLIFT LOADS FOR THE 4 FOOT
 AND 6 FOOT OVER- HANGS ARE UNKNOWN.
  
 10) 2ND REQUEST. PLEASE PROVIDE TYPE OF APPROVED
 ADHESIVE? SHEET S-6 & S-7 BOTH SHOW NEW DECROTIVE
 OUTRIGGERS OF 8 INCHES IN HEIGHT, THE PLANS DO NOT
 PROVIDE THE WIDTH OF THE OUTRIGGERS, NOR DO THEY
 SPECIFY GRADE OR SPECIES OF WOOD THEY ARE TO BE MADE
 FROM. THE PLANS DO NOT INDICATE HOW THEY ARE TO BE
 ANCHORED TO THE NEW CONCRETE DECK NOR HOW THEY WILL BE
 ANCHORED TO THE EXISITNG SLOPED CONCRETE DECKS?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 11) 2ND REQUEST. ADDITIONAL INFORMATION IS REQUIRED
 SINCE THE EXPOSURE AND WIND SPEED WAS INCORRECT. SHEET
 S-8 DETAIL # 4 SHOWS A HIP AND RIDGE DETAIL WITH WOOD
 2X FOR ANCHORING OF HIP AND RIDGE TILE. THE PLANS DO
 NOT INDICATE HOW THE RIDGE BOARD IS TO BE ATTACHED.
 SHOW COMPLIANCE WITH 2014 FBC-B 1507.3.8 APPLICATION.
 TILE SHALL BE APPLIED ACCORDING TO THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS OR RECOMMENDATIONS OF THE
 FRSA/TRI FLORIDA HIGH WIND CONCRETE AND CLAY ROOF TILE
 INSTALLATION MANUAL, FIFTH EDITION WHERE THE BASIC WIND
 SPEED, VASD, IS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-25 Cont ID  
Sent By jwitmer Date 2015-09-25 Time 17:14 Rev Time  
Received By jwitmer Date 2015-09-25 Time 15:01 Sent To  
Notes
2015-09-25 17:11:44BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15081084
 ADD: 1801 @ PARKER AVE.
 CONT: TBD
 TEL: ( 561)494-1075
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. SEPT. 25/2015
 ACTION: DENIED
  
 1) THE S1 SHEET INDICATES THE PLANS WERE DESIGNED TO
 THE 2010 FBC. NOTE PLANS SUBMITTED TO THE BUILDING
 DEPARTMENT ON JUNE 30/ 2015 OR AFTER THIS DATE ARE TO
 BE DESIGNED TO THE 2014 FBC. THE 2014 FBC WAS ADOPTED
 STATEWIDE ON JUNE 30/ 2015.
  
 2) THE PERMIT APPLICATION ADDRESS INDICATES THIS
 STRUCTURE IS BUILT IN AN A9 FLOOD ZONE THE BASE
 ELEVATION 13 FEET AND THE CITY REQUIRES AN ADDTIONAL 6
 INCH FREEBOARD OR MINIMUM OF 13 FT. 6 INCHES. FBC
 BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31/2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 3) SHEET S1 UNDER THE HEADING OF SLAB ON GRADE SOILS
 REPORTS ARE REQUIRED. 2014 FBC-B 1803.5.2 QUESTIONABLE
 SOILS, SOILS GEOTECHNICAL REPORT REQUIRED. SHEET S3
 INDICATES THE INSTALATION OF 20 FOOT STEEL SHEET PILE.
  
 4) SHEET S-1 INDICATES THIS STRUCTURE IS IN A WIND
 EXPOSURE B. PLEASE CORRECT TO C EXPOSURE, TO THE
 SOUTHWEST NORTH AND NORTHEAST, CONSIDERED A C EXPOSURE
 2014 FBC-B 1609.4. .SURFACE ROUGHNESS C. OPEN TERRAIN
 WITH SCATTERED OBSTRUCTIONS HAVING HEIGHTS GENERALLY
 LESS THAN 30 FEET (9144 MM). THIS CATEGORY INCLUDES
 FLAT OPEN COUNTRY, AND GRASSLANDS. THIS SURFACE
 ROUGHNESS SHALL ALSO APPLY TO ANY BUILDING LOCATED
 WITHIN SURFACE ROUGHNESS BTYPE TERRAIN WHERE THE
 BUILDING IS WITHIN 100 FEET (30 M) HORIZONTALLY IN ANY
 DIRECTION OF OPEN AREAS OF SURFACE ROUGHNESS C OR
 D-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET (182.9
 M) IN THE UPWIND DIRECTION AND A WIDTH GREATER THAN 150
 FEET (46 M).
  
 5) THE PRESSURES FOUND FOR ROOF ZONES 1,2 & 3 AND WALL
 PRESSURES FOR ZONES 4 & 5 WILL NEED TO BE RECALCULATED
 FOR EXPOSURE C WITH A HEIGHT AND EXPOSURE ADJUSTMENT
 FACTOR OF 1.21. 2014 FBC-B TABLE 1609.7(2).
  
 6) THE PRESSURES SHOWN ON SHEET S3 ARE ASSUMED TO BE
 VULT PLEASE ALSO SUBMIT IN VASD SINCE ALL OF THE
 PRODUCT APPROVALS ARE WRITTEN IN VASD.
  
 7) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. SWING AND OVERHEAD TYPE
 (C) WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) SHEET S-3, S-4,S6, S7 & S9 ALL SHOW DETAILS OF THE
 NEW HIPPED TRUSS ROOF SYSTEM ON TOP OF A CONCRETE
 SLABBED ROOF SYSTEM. NOTE THE PLANS INDICATE A (2)
 POINT ANCHOR LOCATION FOR THE TRUSSES. THE AREA OF
 CONCERN IS THE 4 FOOT AND 6 FOOT TRUSS TAILS WITH NO
 ANCHOR SYSTEM FOR UPLIFT. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 10) SHEET S-6 & S-7 BOTH SHOW NEW DECROTIVE OUTRIGGERS
 OF 8 INCHES IN HEIGHT, THE PLANS DO NOT PROVIDE THE
 WIDTH OF THE OUTRIGGERS, NOR DO THEY SPECIFY GRADE OR
 SPECIES OF WOOD THEY ARE TO BE MADE FROM. THE PLANS DO
 NOT INDICATE HOW THEY ARE TO BE ANCHORED TO THE NEW
 CONCRETE DECK NOR HOW THEY WILL BE ANCHORED TO THE
 EXISITNG SLOPED CONCRETE DECKS? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 11) SHEET S-8 DETAIL # 4 SHOWS A HIP AND RIDGE DETAIL
 WITH WOOD 2X FOR ANCHORING OF HIP AND RIDGE TILE. THE
 PLANS DO NOT INDICATE HOW THE RIDGE BOARD IS TO BE
 ATTACHED. SHOW COMPLIANCE WITH 2014 FBC-B 1507.3.8
 APPLICATION. TILE SHALL BE APPLIED ACCORDING TO THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS OR
 RECOMMENDATIONS OF THE FRSA/TRI FLORIDA HIGH WIND
 CONCRETE AND CLAY ROOF TILE INSTALLATION MANUAL, FIFTH
 EDITION WHERE THE BASIC WIND SPEED, VASD, IS DETERMINED
 IN ACCORDANCE WITH SECTION 1609.3.1.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-16 Cont ID  
Sent By albarran Date 2016-02-16 Time 10:44 Rev Time 0.00
Received By albarran Date 2016-02-16 Time 10:22 Sent To I
Notes
2016-02-16 10:45:19ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED,.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-04 Cont ID  
Sent By albarran Date 2015-11-04 Time 15:49 Rev Time 0.00
Received By albarran Date 2015-11-04 Time 14:40 Sent To I
Notes
2015-11-04 15:50:08THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 2010
 EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS
 APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED.
 1. REGARDLESS OF WHEN THESE PLANS WERE DRAWN AND
 SEALED, THEY WERE SUBMITTED FOR PERMITTING AFTER THE
 2014 FBC TOOK EFFECT. THEREFORE ALL THE PLANS SHALL BE
 REVISED TO COMPLY WITH SAME.
 2. FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
 3. CORRECT YOUR LOAD TABULATION. I GET 896 AMP.
 4. TOILET/WATER CLOSET IS MISSING THE REQUIRED LIGHTING
 AND SWITCH.
 5. ALL LIGHTING SHALL COMPLY WITH THE 5TH EDITION OF
 THE 2014 FBC-ENERGY CONSERVATION CODE.
 6. PROVIDE MANUFACTURER'S DATA SHEETS FOR PROPOSED
 GENERATOR.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-31 Cont ID  
Sent By pleduc Date 2015-08-31 Time   Rev Time 0.00
Received By pleduc Date 2015-08-31 Time 14:33 Sent To  
Notes
2015-08-31 14:37:55THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) SHEET C 3, THE EXTERIOR STAIR RAILING HEIGHT
 INDICATED IS NOT CODE COMPLIANT WITH NFPA CHAPTER 7,
 7.2.2.4 GUARDS AND HANDRAILS. NEW HANDRAILS ON STAIRS
 SHALL NOT BE LESS THAN 34 IN. AND NOT MORE THAN 38 IN.
 ABOVE THE SURFACE OF THE TREAD, MEASURED VERTICALLY TO
 THE TOP OF THE RAIL FROM THE LEADING EDGE OF THE TREAD.
  
 2) SHEET S 3, THE INTERIOR STAIR AND HABDRAIL SHALL
 COMPLY WITH NFPA CHAPTER 7 AND # 1 ABOVE.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-23 Cont ID  
Sent By   Date 2016-02-23 Time 17:01 Rev Time 0.00
Received By lmarchan Date 2016-02-19 Time 14:33 Sent To  
Notes
2016-02-19 14:33:49RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-16 Cont ID  
Sent By albarran Date 2016-02-16 Time 10:47 Rev Time 0.00
Received By albarran Date 2015-12-14 Time 11:39 Sent To  
Notes
2016-02-16 10:49:272/16/16 PASSED ELECTRICAL REVIEW AS NOTED BUT MISSING
 OTHER TRADE REVIEWS. CONTRACTOR NOTIFIED VIA PHONE CALL
 AND SAK. SENT FILE TO LARGE "C" DRAWER. MA
2015-12-15 11:39:37C05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-04 Cont ID  
Sent By albarran Date 2015-11-04 Time 15:56 Rev Time 0.00
Received By albarran Date 2015-08-27 Time 16:14 Sent To  
Notes
2015-11-04 16:00:3911/4/15 FAILED ELECTRICAL REVIEW AS NOTED. CITY
 PERSONNEL NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN
 "TBS". MA
2015-08-27 16:15:49C04

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-12-21 Cont ID  
Sent By ccole Date 2015-12-21 Time 13:28 Rev Time 0.00
Received By ccole Date 2015-12-21 Time 13:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-09-08 Cont ID  
Sent By ccole Date 2015-09-08 Time 13:50 Rev Time 0.00
Received By ccole Date 2015-09-08 Time 13:49 Sent To  
Notes
2015-09-08 14:14:391ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15081084
 9/8/15
  
 1) AC COOLING AND HEATING CALCULATIONS, AND ENERGY
 CALCULATIONS FOR A PROJECT AT 444 BUNKER RD. HAVE BEEN
 SUBMITTED, HOWEVER THIS PROJECT IS AT 1801 PARKER AVE.(
 AS LISTED ON THE PERMIT APPLICATION), AND 1700-1799
 PARKER AVE. (AS LISTED ON THE PLANS). PLEASE SUBMIT THE
 CORRECT CALCULATIONS FOR THIS PROJECT.
 2) SUBMIT TWO COPIES OF A FLORIDA PRODUCT APPROVAL OR
 MIAMI-DADE NOA FOR THE LOUVER- REFER TO SECTION
 1609.1.2 FBC-14 BUILDING, AND FL. DEPT. OF COMMUNITY
 AFFAIRS RULE 9N-3.
 3) CLARIFY HOW THE VENTILATION OPENING IN THE PUMP ROOM
 WAS SIZED- PROVIDE A CALCULATION, AND CLARIFY IF AN
 EXHAUST FAN WILL BE INSTALLED TO MOVE THE VENTILATION
 AIR THROUGH THE BUILDING- REFER TO SECTION 403 FBC-14
 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2016-03-25 Cont ID  
Sent By shill Date 2016-03-25 Time 16:09 Rev Time 0.00
Received By shill Date 2016-03-25 Time 16:09 Sent To  
Notes
2016-03-25 16:11:07****CORRECTIONS****
 ELEVATION CERTIFICATE SUBMITTED FOR PLAN REVIEW HAS
 CORRECTIONS. PROVIDE CORRECTED ELEVATION CERTIFICATE AT
 TIME OF FORM BOARD INSPECTION.
 A FORM BOARD SURVEY WITH ELEVATIONS OR A COMPLETED
 "BUILDING UNDER CONSTRUCTION" ELEVATION CERTIFICATE
 WILL BE REQUIRED AT INSPECTION.
 A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE WILL BE
 REQUIRED PRIOR TO FINAL INSPECTION.
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. AN EXPIRED ELEVATION CERTIFICATE FORM WAS USED. THE
 NEW ELEVATION CERTIFICATE WHICH EXPIRES NOV 30, 2018
 BECAME EFFECTIVE ON JANUARY 6, 2016. IT CAN BE FOUND
 ONLINE:
  
 HTTP://NFIPISERVICE.COM/STAKEHOLDER/W_16002/W-16002.HTM
 L
  
 2. ITEM B9 IS BLANK, PLEASE COPMLETE.
  
 3. SEE INSTRUCTIONS, PROVIDE THE SOURCE OF THE LATITUDE
 LONGITUDE COORDINATES IN THE COMMENTS SECTION.
  
  
  

Review Stop P PLUMBING
Rev No 3 Status N Date 2017-02-17 Cont ID  
Sent By tklarge Date 2016-02-23 Time 12:46 Rev Time 0.00
Received By tklarge Date 2016-02-22 Time 03:55 Sent To  
Notes
2016-02-23 12:50:47PLUMBING PERMIT NOT REQUIRED. LIFT STATION IS LOCATED
 IN A DEDICATED EASEMENT.

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-12-20 Cont ID  
Sent By tklarge Date 2015-12-20 Time 10:55 Rev Time 0.00
Received By tklarge Date 2015-12-20 Time 10:12 Sent To  
Notes
2015-12-20 10:18:121) 1) SUBMIT A WATER RISER DIAGRAM FOR THE WATER
 CLOSET, LAVATORY & EMERGENCY EYE-WASH / SHOWER FOR
 REVIEW. WPB AMEND. TO FBC SEC. 107.3.5.1.3. 2ND
 REQUEST. THE SUBMITTED DIAGRAM IS A SANITARY RISER, NOT
 A WATER RISER.
 2) THE GENERATOR SPECS. REFLECT A 1,000 GALLON SUB-BASE
 FUEL TANK BUT SPECIFICATIONS HAVE ALSO BEEN SUBMITTED
 FOR A DOUBLE WALL SECONDARY CONTAINMENT TANK. CLARIFY.
 3) SUBMIT DETAILS FOR THE DEADMEN. NOTE #5 ON SHT. C-4
 NOTES THAT SHOP DRAWINGS & SIGNED & SEALED CALCULATIONS
 TO BE DONE BY FL. REGISTERED ENGINEER TO BE SUBMITTED
 BY CONTRACTOR. MANUFACTURER'S SPECIFICATIONS HAVE BEEN
 SUBMITTED.THIS DOES NOT SATISFY NOTE #5.
 4) FUEL TANKS IN EXCESS OF 550 GALLONS REQUIRE THE
 APPROVAL FROM PALM BEACH COUNTY DEPARTMENT OF
 ENVIRONMENTAL RESOURCE MANAGEMENT PER COUNTY ORDINANCE
 2015-008 AND F.A.C. RULE 62-762.301.
 5) SUBMIT A FUEL OIL PIPING DIAGRAM IF NEW PIPING WILL
 BE INSTALLED. SHOW TYPE OF PIPE, SIZES, ETC.WPB AMEND.
 TO FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-09-08 Cont ID  
Sent By tklarge Date 2015-09-08 Time 04:32 Rev Time 0.00
Received By tklarge Date 2015-09-05 Time 10:58 Sent To  
Notes
2015-09-05 11:43:001) SUBMIT A WATER RISER DIAGRAM FOR THE WATER CLOSET,
 LAVATORY & EMERGENCY EYE-WASH / SHOWER FOR REVIEW. WPB
 AMEND. TO FBC SEC. 107.3.5.1.3.
 2) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS
 FOR THE NEW GENERATOR.SHT. C-1 NOTE B READS "SEE SPECS
 FOR NEW GENERATOR". THERE ARE NO GENERATOR SPECS IN
 THIS SUBMITTAL. WHAT TYPE OF FUEL POWERS THE GENERATOR?
 WPB AMEND. TO FBC SEC. 107.1.
 3) SUBMIT SPECIFICATIONS FOR THE WASTEWATER TANK
 TIE-DOWNS. THE TABLE ON C-4 ONLY SHOWS THE NUMBER OF
 STRAPS. SHOW WHERE ARE THE STRAPS TO BE LOCATED ON THE
 TANK, THE DISTANCE BETWEEN THE STRAPS, THE TYPE, WIDTH,
 AND ANCHORING DETAILS AS TO HOW THE STRAPS WILL BE
 ANCHORED TO THE DEADMEN TO PROVIDE PROTECTION AGAINST
 FLOTATION FORCES..
 4) SUBMIT DETAILS FOR THE DEADMEN. SHT. C-4 NOTES THAT
 SHOP DRAWINGS/ SIGNED & SEALED CALCULATIONS TO BE DONE
 BY FL. REGISTERED ENGINEER TO BE SUBMITTED BY
 CONTRACTOR. THIS CAN BE DONE AS A DEFERRED SUBMITTAL.
 5) SHT. S-3 NOTE #3 - PVC CANNOT BE USED FOR WATER
 DISTRIBUTION. PIPE MATERIAL FOR WATER DISTRIBUTION
 SHALL COMPLY WITH 2014 FBC-PLUMBING, TABLE 605.4. PVC
 CAN BE USED FOR THE WATER SERVICE FROM THE METER TO THE
 BUILDING.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING