| Plan Review Stops For Permit 15080984 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2015-08-31 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2015-08-26 |
Time |
17:26 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2015-08-31 |
Time |
16:47 |
Sent To |
|
|
| Notes |
| 2015-08-26 17:25:32 | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | 561-805-6711 | | | [email protected] | | | | | | | | | COMMENTS: | | | 1. PIPING UNDER BUILDINGS SHALL BE SLEEVED TO COMPLY | | | WITH. | | | FBC G 404.14 | | | 2. SHOW LAYOUT ON FLOOR PLAN WPB AMEND. 107.2.1 | | | 3. NEED SPEC SHEETS FOR ALL APPLIANCES . WPB AMEND. | | | 107.1.2 | | | | | | 1.CONTRACTOR ADDRESSED ISSUE PIPING NOT UNDER HOUSE | | | 2.PROVIDED LAY OUT | | | 3.SPECS TO BE ON JOB SITE NOTED ON PLAN |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2015-08-26 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2015-08-26 15:00:13 | PLUMB -$5000 |
|
|
|